Permit Information
Permit NumberBLD07-01784
StatusFinaled
Name STOCK CONSTRUCTION MANAGEMENT
Site Address 512 N 8TH ST
Project NameST MICHAEL'S
Customer Number 
ePlanReviewNo
Description
(ST. MICHAEL'S EPISCOPAL CHURCH - BISHOP TUTTLE HOUSE AND SITE WORK - PHASE I) The Bishop Tuttle House and the Funsten House will be fire sprinklered for story increase and for code trade-offs. To remodel the 3,424 square foot basement and 3,616 square foot 1st story of the Bishop Tuttle House of St. Michael's Episcopal Church. A 950 square foot 1st story mezzanine addition will also be constructed. Work is to include 2 restrooms accessible to the disabled, an elevator shaft, an elevator, interior nonbearing walls, suspended ceilings, a stairway to the new mezzanine, and finishes. The Bishop Tuttle House and the Funsten house will be fully fire sprinklered in conjunction with this permit. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. The combination of parcels must be completed before this permit is finaled. DRH07-00182 (see also DRH01-00010 and CUP01-00002) **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice 1/13/20101/5/2010 DONE
Third Notice 11/30/200912/29/2009 DONE
faxed and e-mailed Erik Holinka
Second Notice 11/14/200911/25/2009 DONE
First Notice 10/25/200911/4/2009 DONE
sent by mail
Permanent Occupancy  10/15/2009 DONE
BLD-Final10/9/200910/9/200910/9/2009PPASS
DetailsDave Hannah
Eric Phone #: ###-#### ok for perm occ
FIRE-Final Inspection10/8/200910/9/200910/9/2009APASS
DetailsTroy Cobbley
Life safety passed. Building inspector please verify that the emergency light in the basement corridor was repaired.
PubWorks Occupancy Approval10/9/200910/9/200910/9/2009 DONE
DetailsTiffany Lowery
Print Occupancy Form  10/9/2009 DONE
FIRE-Final Inspection10/5/200910/5/200910/5/2009PPART
DetailsForrest France
Project related fire sprinkler permit finaled. See latest inspection notes for remainder of C/N items.
FIRE-Final Inspection8/12/20098/14/20098/14/2009PPART
DetailsForrest France
Fie life safety walkthrough completed for both buildings, circled items on fire code review notes in need of attention including max. occupant load signs, fire extinguishers-one missing second level, remove manual flush bolt at one pair of doors, need to test EM lighting at some locations with power off, fire sprinkler permit pending corrections, remainder of issues okayed.
Zoning Approval8/7/20098/7/20098/7/2009 DONE
DetailsAndrea Tuning
FIRE-Conference7/31/20098/3/20098/3/2009ADONE
DetailsForrest France
Regarding items needed for final including project related FIR permit work.
BLD-Final7/30/20097/31/20097/31/2009ANR
DetailsTony Young
Eric Phone #: ###-####
need trades 1st
BLD-Final7/22/20097/24/20097/24/2009PCANC
DetailsJim Storey
Jerry Phone #: ###-#### Harry called to cancel this inspection
BLD-Final7/2/20097/6/20097/2/2009PCANC
DetailsTony Young
Jerry Phone #: ###-#### Inspection cancelled from web by: Patricia Smith
BLD-Conference10/23/200810/24/200810/24/2008APASS
DetailsDave Hannah
jerry Phone #: ###-#### Note:please call 1/2 hr prior to meet with handrail on ramp in basement ok to build as discused
BLD-Conference10/15/200810/15/200810/15/2008PFAIL
DetailsTony Young
David; Phone #: ###-####
no final inspection approval has been made on this permit,, therfore no one should be occupying the remodeled area in my opinion,, I recomended that David consult w/ plan review, zoning for the CUP, the contractor, owner, architect and possibly the f/l/s and building inspectors for the outcome
BLD-Energy code compliance5/1/20085/1/20085/1/2008PPART
DetailsTony Young
jerry - insulation Phone #: ###-####
ceiling area by mech room ok to cover,, no trades in this area
BLD-Framing/Rough-in4/7/20084/7/20084/7/2008PPART
DetailsTony Young
jerry Phone #: ###-####
2 furr out walls on elevator shaft plywood nailing ok,, fixes in progress
BLD-Framing/Rough-in4/3/20084/4/20084/4/2008APART
DetailsDave Hannah
jerry Phone #: ###-#### ok to cover inside of elev shaft
BLD-Framing/Rough-in4/1/20084/2/20084/2/2008AFAIL
DetailsDave Hannah
Scheduled by a contractor via Hello! on 4/1/2008 at 7:59:29 AM. Contact: ###-####. needs to fire block at floor lines in elev shaft
BLD-Framing/Rough-in3/13/20083/13/20083/13/2008PPART
DetailsDave Hannah
jerry - partial Phone #: ###-#### new trusses and new soffit on ext
BLD-Wall cover3/5/20083/5/20083/5/2008PPART
DetailsDave Hannah
Jerry; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt first layer of sheet rock ok ok to install second lay ceiling under elevator control room
BLD-Wall cover2/25/20082/25/20082/25/2008PPART
DetailsTony Young
Jerry; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
basement class rooms ok to cover,, 1st layer under mech room in kitchen ceiling ok
BLD-Framing/Rough-in2/13/20082/14/20082/14/2008APART
DetailsTom Arcoraci
jerry Phone #: ###-#### ok to dry in roof
BLD-Footing12/19/200712/20/200712/20/2007APART
DetailsTony Young
jerry Phone #: ###-####
ok pending special inspection report
BLD-Conference12/10/200712/10/200712/10/2007PPART
DetailsTony Young
jerry Phone #: ###-#### Note: Please call 1/2 hr prior to inspection ;
? about re-desihning ADA restrooms due to unforseen structural elements,,, ok,, need to show plan review for approval and record keeping
Issue PAID IN FULL permit  12/6/2007 DONE
Telephone call  12/5/2007  
called Ben Hill ###-#### and told him revised fees per sewer recalculations.
Inspection Record Card- Bld  11/29/2007 DONE
Telephone call  11/29/2007 DONE
left vm for eric at ###-#### - permit ready and fees given
Permit Ready to Issue  11/29/2007 DONE
Plan assigned to (CJW)7/19/2007 11/28/2007 PASS
11/28/2007 10:28:50 CJW - activity updated through activity BLDA022 from case BLD07-01784.
Routing - PLAN CHECK11/27/2007 11/28/2007 PASS
Prepared the drawings to go to the permits desk.
PLANS/APPL TAKEN TO FRONT DESK  11/28/2007 DONE
Routing - PUBLIC WORKS11/27/2007 11/27/2007 PASS
Routing PW Drainage11/27/2007 11/27/2007 PASS
Routing - PLAN CHECK11/26/2007 11/27/2007 DONE
(11-26-07) Waiting for PW to call it back. (11-27-07) Took drawings back to PW.
Routing - PLANNING11/23/2007 11/26/2007 DONE
Should have gone to PW. No routing time lost because November 24 and 25 were a weekend.
Routing - Erosion and Sediment11/20/2007 11/23/2007 PASS
Passed ESC review 7-30-07
Routing - FIRE11/19/2007 11/20/2007 PASS
Attached updated IFC review comments to plans.
Routing - PLANNING11/16/2007 11/19/2007 PASS
Approved per DRH07-00182. ANT 11-19-07
Routing PW Drainage11/1/2007 11/16/2007 FAIL
DetailsBrian Murphy
Called Dan Thompson need O&M, Geotech letter and 3 more copies of grading plan. Brian Murphy ###-####.
Routing - PUBLIC WORKS10/30/2007 11/16/2007 FAIL
Routing PW Solid Waste10/30/2007 11/1/2007 PASS
Gates must have a pin to hold them in the open position so the do not swing into parked cars or trash truck. Noted on plans.
Routing - PLAN CHECK9/19/2007 10/30/2007 PASS
Drawings approved after resubmittal review.
Plan resubmittals received  10/24/2007  
Received 1 responce letter dated 10-15-07 from Ben Hill (2pgs), 2 copies of Geotechnical report (7pgs), 2 copies of ESC plan (10pgs), 2 copies of letter from Pinnacle Engineers regarding Funsten Roof Mechanical Units, 2 copies of Calculations, 2 copies of sheets- L-1.0, A0.0, A1.0, A2.0, A2.3, A8.1, C1.1, C1.2, C2.1, S1.2, S2.1, P1.0, P3.0, P4.0, M1.1, M1.2, M3.0, M4.0 and taken to Carl Westfall
1st review completed  9/19/2007 FAIL
Routing - FIRE9/14/2007 9/19/2007 FAIL
Faxed and emailed resubmittal items to architect.
Routing - PLAN CHECK8/8/2007 9/14/2007 FAIL
The IBC plan review was started on September 7, 2007 and was finished on September 14, 2007. Revised drawings and other information was required. See the plan review report.
Routing - PLANNING8/7/2007 8/8/2007 FAIL
Andrea Tuning DRH07-00182

Applicant has the utility yard/trash enlcosure opening into a proposed parking stall. To be operational and functional, the applicant will be required to relocate the gate into the utility yard/trash enclosure so that it does not interefere with the proposed parking space.
Routing - PLUMBING7/30/2007 8/7/2007 PASS
per plans and 2003 upc
Routing - Erosion and Sediment7/27/2007 7/30/2007 PASS
ESC plan approved with attached conditions.
Routing PW Solid Waste7/20/2007 7/27/2007 FAIL
1) Enclosure must not be blocked by parking space; 2) Detail of enclosure, including minimum dimensions and illustration of gate opening, is required; 3) Possible fire hazard due to proximity of electrical equipment in enclosure; 4) How is trash truck supposed to access enclosure?
Routing - PUBLIC WORKS7/19/2007 7/27/2007 FAIL
Routing PW Environmental7/25/2007 7/25/2007 PASS
1500 gal GI OK for new kitchen
Routing PW Sewer Design7/20/2007 7/25/2007 PASS
Routing PW Sewer Rating7/20/2007 7/25/2007 PASS
Routing PW Street Lights7/20/2007 7/24/2007 PASS
Routing PW Drainage7/20/2007 7/24/2007 FAIL
Pending Assignment by MYS7/10/2007 7/19/2007 DONE
7/19/2007 15:24:23 MYS - activity updated through activity BLDA172 from case BLD07-01784.
Plans ACCEPTED BY PLAN TECH  7/10/2007 DONE
all e sheets have not been stamped, no mec/ele compliance
Recd Pcfee & Taken To Pln CK  7/10/2007 DONE
Application received  7/9/2007  
Plans ACCEPTED BY PLAN TECH  7/9/2007 FAIL
NEED CHECK FOR INITIAL PLAN CHECK FEE PAID BEFORE MOVING ON ///DLD 7-9-07