BLD-Aging Inspection | 11/1/2010 | 11/1/2010 | 11/1/2010 | | CANC |
Mike Jordan
|
|
|
|
DOC - Permit Expired | 11/1/2010 | 11/1/2010 | 11/1/2010 | A | PASS |
Mike Jordan
|
|
|
Tenant no longer occupies space. Space is empty. Permit is expired.
|
BLD-Final | 10/30/2007 | 10/31/2007 | 10/31/2007 | A | NR |
Mike Jordan
|
|
|
barb Phone #: ###-####. life/.safety failed.
|
FIRE-Final Inspection | 10/30/2007 | 10/30/2007 | 10/30/2007 | P | FAIL |
Troy Cobbley
|
|
|
More faux walls and ceilings have been built that require fire protection that are not shown on the sprinkler permit.
|
FIRE-Conference | 9/20/2007 | 9/21/2007 | 9/21/2007 | P | DONE |
Troy Cobbley
|
|
|
I let the tenant know that since building the displays caused obstructions to the overhead sprinkler coverage and that sprinkler protection would be required within and in the combustible concealed spaces of the structures. They mentioned codes I was not familiar with that they claimed excluded the sprinkler coverage. I deferred them to Sam Rogers for building/fire codes that would allow the deletion of sprinkler coverage.
|
BLD-Final | 9/20/2007 | 9/21/2007 | 9/21/2007 | A | NR |
Mike Jordan
|
|
|
sunny Phone #: ###-####. Fire/life/safety has not passed.
|
FIRE-Final Inspection | 9/20/2007 | 9/20/2007 | 9/20/2007 | P | FAIL |
Troy Cobbley
|
|
|
Enclosed combustible patios have been constructed in the warehouse/showroom. These require sprinkler protection. I went over this with the owner. The fire extinguishers need their annual inspection and the exit sign/emergency lights need tested.
|
BLD-Final | 9/19/2007 | 9/20/2007 | 9/20/2007 | A | CANC |
Mike Jordan
|
|
|
sunny Phone #: ###-####
|
FIRE-Final Inspection | 9/19/2007 | 9/19/2007 | 9/19/2007 | P | CANC |
Troy Cobbley
|
|
|
sunny Phone #: ###-####
|
BLD-Final | 9/4/2007 | 9/5/2007 | 9/5/2007 | P | NR |
Mike Jordan
|
|
|
Scheduled by a contractor via Hello! on 9/4/2007 at 1:45:02 PM. Contact: ###-####.
|
FIRE-Final Inspection | 9/4/2007 | 9/5/2007 | 9/5/2007 | A | CANC |
Troy Cobbley
|
|
|
Per a phone conversation with the contractor the doors are not installed yet. No inspection was performed.
|
Telephone call | | | 8/15/2007 | | |
|
|
|
E-mail from Mike with Alpine Idaho to verify they are not GC-everything changed to Seveth Sun--see documents
|
BLD-Energy code compliance | 8/10/2007 | 8/10/2007 | 8/10/2007 | P | PASS |
Mike Jordan
|
|
|
Sunny, early afternoon if possible; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt. ok. Will need to inspect framing on new passthru when complete.
|
BLD-Framing/Rough-in | 8/8/2007 | 8/9/2007 | 8/9/2007 | A | PART |
Mike Jordan
|
|
|
sonny Phone #: ###-####. New interior stell stud wall for conditioned warehouse area. Still need to inspect new pass through. ok to insul.
|
BLD-Framing/Rough-in | 8/7/2007 | 8/7/2007 | 8/7/2007 | P | NR |
Mike Jordan
|
|
|
Scheduled by a contractor via Hello! on 8/7/2007 at 7:22:28 AM. Contact: ###-####. Needs elec ri and apoproved plans.
|
Telephone call | | | 8/6/2007 | | |
|
|
|
Fax from Seventh Sun to let me know they are the GC and no work has been done yet. Contacted Mike with Alpine Idaho and they are not the GC will send letter stating that.
|
Issue PAID IN FULL permit | | | 7/20/2007 | | DONE |
|
|
|
|
Print Occupancy Form | | | 7/17/2007 | | DONE |
|
|
|
|
Telephone call | | | 7/17/2007 | | DONE |
|
|
|
left vm for matt rhees at ###-#### - permit ready and fees given - also need gc name and rce#
|
Permit Ready to Issue | | | 7/17/2007 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 7/16/2007 | | 7/16/2007 | | PASS |
|
|
|
|
Routing - FIRE | 7/16/2007 | | 7/16/2007 | | PASS |
|
|
|
minor remodle field verrify
|
Case Summary (BLD) | | | 7/16/2007 | | DONE |
|
|
|
|
1st review completed | | | 7/16/2007 | | |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/16/2007 | | DONE |
|
|
|
|
Application received | | | 7/11/2007 | | |
|
|
|
|
Pending Assignment by MYS | 7/11/2007 | | | | |
|
|
|
|