Case Summary (BLD) | | | 3/6/2012 | | |
|
|
|
|
Third Notice BLD | 9/22/2008 | 9/22/2008 | 12/24/2008 | | DONE |
Cathy Brown
|
|
|
Second Notice has not been responded to.
|
Second Notice BLD | 8/11/2008 | 8/11/2008 | 9/22/2008 | | DONE |
Cathy Brown
|
|
|
First Notice has not been responded to.
|
First Notice | | 7/16/2008 | 8/11/2008 | | DONE |
|
|
|
|
Override - Condition Holds | | | 7/16/2008 | | |
|
|
|
|
Permanent Occupancy UNPAID FEE | | | 7/16/2008 | | |
|
|
|
|
BLD-Final | 7/15/2008 | 7/15/2008 | 7/15/2008 | P | PASS |
Jim Storey
|
|
|
Herb Phone #: ###-####
|
FIRE-Final Inspection | 7/15/2008 | 7/15/2008 | 7/15/2008 | P | PASS |
Forrest France
|
|
|
All corrections were made per notes from last inspection. KR
|
Override - Condition Holds | 7/15/2008 | 1/1/1900 | 7/15/2008 | | |
|
|
|
fire insp
|
FIRE-Final Inspection | 7/9/2008 | 7/10/2008 | 7/10/2008 | A | FAIL |
Forrest France
|
|
|
Sprinkler plans are not finaled. Fire extinguisher in warehouse and truck shop need to be 4A, wrong extiguishers were installed. Fire extinguishers in offices need to be hung, Egress lighting at all exit from office spaces were not installed and misc emergency lights did not function. All egeress and emergency lights need to be retested.KR
|
Code Occupancy Approval | | | 6/26/2008 | | DONE |
|
|
|
Inspection shows compliance w/ landscaping, curbing, striping requirements
|
CHANGE STATUS TO (ISS) | | | 6/25/2008 | | DONE |
|
|
|
|
(F) Reprint permit | | | 6/25/2008 | | DONE |
|
|
|
|
OVERRIDE | | | 6/11/2008 | | |
|
|
|
|
Print Occupancy Form | | | 6/11/2008 | | DONE |
|
|
|
|
Telephone call | | | 6/11/2008 | | DONE |
|
|
|
left message w leslie for rocky towle at ###-#### - permit ready and fees given
|
Override - Condition Holds | | | 6/11/2008 | | |
|
|
|
|
Permit Ready to Issue | | | 6/11/2008 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 5/29/2008 | | 6/10/2008 | | PASS |
John Menard
|
|
|
|
Plan Reviewer's activity | | | 6/10/2008 | | PASS |
John Menard
|
|
|
Reviewed and approved modification for installation of required smoke and heat vents. Information on vents with fire reviewer. JCM
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/10/2008 | | DONE |
John Menard
|
|
|
|
Plan assigned to (JCM) | 5/29/2008 | | 6/10/2008 | | PASS |
John Menard
|
|
|
6/10/2008 13:46:47 JCM - activity updated through activity BLDA022 from case BLD07-01884.
|
BLD-Framing/Rough-in | 5/29/2008 | 5/30/2008 | 5/30/2008 | A | PASS |
Jim Storey
|
|
|
herb - ###-#### - ceiling cover
|
Plan Modification Accepted | | | 5/29/2008 | | |
|
|
|
Plan Modification accepted for Bld07-01884 (Western Trailers) to add (8) smoke/fire vents to the roof over the parts warehouse. Submitted on sheet A1.1; routed to John Menard
|
Routing - FIRE | 5/29/2008 | | 5/29/2008 | | PASS |
Scott Arellano
|
|
|
Attached IFC comments to plans
|
Override - Parcel Holds | | | 5/29/2008 | | |
|
|
|
|
Override - Condition Holds | | | 5/29/2008 | | |
|
|
|
|
BLD-Energy code compliance | 4/10/2008 | 4/11/2008 | 4/11/2008 | P | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 4/10/2008 at 3:28:51 PM. Contact: ###-####.
|
BLD-Framing/Rough-in | 4/8/2008 | 4/9/2008 | 4/9/2008 | A | PASS |
Jim Storey
|
|
|
herb Phone #: ###-####
|
BLD-Aging Inspection | 2/29/2008 | 2/29/2008 | 2/29/2008 | | PASS |
Jim Storey
|
|
|
wip
|
BLD-Footing | 9/26/2007 | 9/26/2007 | 9/26/2007 | P | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 9/26/2007 at 8:44:22 AM. Contact: ###-####.center pad ft ok
|
BLD-Footing | 9/24/2007 | 9/24/2007 | 9/24/2007 | P | PART |
Jim Storey
|
|
|
herb Phone #: ###-#### need si from engineer to justafy n/a .
|
(F) Reprint permit | | | 9/24/2007 | | |
|
|
|
|
Routing - PLAN CHECK | 9/20/2007 | | 9/21/2007 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/21/2007 | | DONE |
|
|
|
|
Print Occupancy Form | | | 9/21/2007 | | DONE |
|
|
|
|
Telephone call | | | 9/21/2007 | | DONE |
|
|
|
left message w andy for rocky towle at ###-#### - permit ready and fees given - also need ACHD receipt
|
Permit Ready to Issue | | | 9/21/2007 | | DONE |
|
|
|
|
Issue PAID IN FULL permit | | | 9/21/2007 | | DONE |
|
|
|
|
Plan assigned to (JCM) | 7/24/2007 | | 9/21/2007 | | PASS |
|
|
|
9/21/2007 08:23:18 JCM - activity updated through activity BLDA022 from case BLD07-01884.
|
Routing - FIRE | 9/19/2007 | | 9/20/2007 | | PASS |
|
|
|
Attached updated review comments to plans.
|
Additional plans submitted | | | 9/20/2007 | | DONE |
|
|
|
Recieved Hazardous materials list from owner.
|
Routing - PLUMBING | 9/17/2007 | | 9/19/2007 | | PASS |
|
|
|
per plans and 2003 upc
|
Routing - PUBLIC WORKS | 9/14/2007 | | 9/17/2007 | | PASS |
|
|
|
|
Routing PW Solid Waste | 9/17/2007 | | 9/17/2007 | | PASS |
|
|
|
|
Routing - PLANNING | 9/11/2007 | | 9/14/2007 | | PASS |
|
|
|
REDLINES SHEET L1
|
Plan resubmittals received | | | 9/12/2007 | | |
|
|
|
Received 2 copies of page A0.1; inserted into plans by runner and took plans back to Josh Wilson
|
Routing - PUBLIC WORKS | 9/7/2007 | | 9/11/2007 | | FAIL |
|
|
|
Solid Waste failed. See entry.
|
Routing PW Solid Waste | 9/11/2007 | | 9/11/2007 | | FAIL |
|
|
|
Proposed changes to plans not made.
|
Plan Reviewer's activity | | | 9/7/2007 | | PASS |
|
|
|
Reviewed and approved structural and nonstructural revisions. JCM
|
Routing - PLAN CHECK | 8/16/2007 | | 9/7/2007 | | PASS |
|
|
|
|
Plan resubmittals received | | | 8/29/2007 | | |
|
|
|
Received 1 cover transmittal from Design Resources, 1 plan review responce from Design Resources (2 Pgs), 1 cover transmittal from K2 Construction, 2 copies of Plan review responces and letter for Structural from Butler Manufacturing, 2 copies of Footing & Foundations structual calcs from Harrison Engineering, 2 copies of the following sheets-S5, C-5, P1.2, P1.3, M1.2, M1.3, A1.1, A1.2, A1.3, A1.4, A3.3, A4.1, A7.4 and taken to John Menard
|
1st review completed | | | 8/16/2007 | | FAIL |
|
|
|
|
Routing - FIRE | 8/13/2007 | | 8/16/2007 | | FAIL |
|
|
|
Faxed resubmittal item to architect.
|
Routing - PLAN CHECK | 8/9/2007 | | 8/13/2007 | | FAIL |
|
|
|
John Menard
|
Routing - PLANNING | 8/6/2007 | | 8/9/2007 | | FAIL |
|
|
|
Spoke with applicant-- submitting new site plan
DRH07-00013-Josh Wilson
|
Routing - PLUMBING | 7/31/2007 | | 8/6/2007 | | FAIL |
|
|
|
note 5 page P1.2- increase cold water pipe size to 1 1/4". provide sewer pump detail, septic tank, etc.
|
Routing Off Site - STRUCTURAL | 7/24/2007 | | 8/1/2007 | | FAIL |
|
|
|
Called action Courier to pick up on 7/24/07 @ 11:00am BAS - received comment list from consulting structural engineer requesting revisions. JCM
|
Plan Reviewer's activity | | | 8/1/2007 | | FAIL |
|
|
|
Reviewed plans and found revisions required.
|
Plan resubmittals requested | | | 8/1/2007 | | DONE |
|
|
|
E-mailed the architect a copy of the plan review requesting revisions. JCM
|
Plan resubmittals requested | | | 8/1/2007 | | DONE |
|
|
|
Faxed the architect a copy of the structural plan review requesting revisions.
|
Routing - Erosion and Sediment | 7/30/2007 | | 7/31/2007 | | PASS |
|
|
|
ESC plan approved with attached conditions.
|
Routing - PUBLIC WORKS | 7/24/2007 | | 7/30/2007 | | FAIL |
|
|
|
|
Routing PW Sewer Rating | 7/25/2007 | | 7/30/2007 | | PASS |
|
|
|
|
Routing PW Environmental | 7/25/2007 | | 7/30/2007 | | PASS |
|
|
|
Use approved design for truck wash oil/sediment interceptor.
|
Routing PW Solid Waste | 7/25/2007 | | 7/27/2007 | | FAIL |
|
|
|
1. Clarification of trash and recycling containers size 2. If roll-offs need 65-70 Ft. clearence in front of containers.
|
Routing PW Drainage | 7/25/2007 | | 7/26/2007 | | PASS |
|
|
|
|
Routing PW Sewer Design | 7/25/2007 | | 7/26/2007 | | PASS |
|
|
|
|
Routing PW Street Lights | 7/25/2007 | | 7/25/2007 | | PASS |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 7/24/2007 | | DONE |
|
|
|
All plans brought back stamped & signed///7/23/07 BAS
|
Routing - PLANNING Land Div | 7/24/2007 | | 7/24/2007 | | PASS |
|
|
|
Parcel is larger than 5 acres
|
Plans ACCEPTED BY PLAN TECH | | | 7/23/2007 | | FAIL |
|
|
|
Missing stampand signature on steel building plans-all plans were taken off site by Design Resources to be stamped and signed and returned///7/23/07 @ 1:45pm BAS
|
Plan routing begun/NEW & ADDTN | | | 7/23/2007 | | |
|
|
|
|
CHANGE STATUS TO (PND) | | | 7/23/2007 | | DONE |
|
|
|
Plans taken off site by Design Resouce to be stamped & signed///7/23/07 @ 1:45pm BAS
|
Recd Pcfee & Taken To Pln CK | | | 7/19/2007 | | |
|
|
|
|
Application received | | | 7/18/2007 | | |
|
|
|
|
BLD-Final | 7/9/2008 | 7/10/2008 | | P | |
Jim Storey
|
|
|
Hurb Phone #: ###-####
|