Third Notice BLD | 9/22/2008 | 9/22/2008 | 12/22/2008 | | DONE |
Cathy Brown
|
|
|
This permit finaled on the web by Danielle Groat
|
Second Notice BLD | 8/11/2008 | 8/11/2008 | 9/22/2008 | | DONE |
Cathy Brown
|
|
|
First Notice has not been responded to.
|
First Notice | | 6/10/2008 | 8/11/2008 | | DONE |
|
|
|
|
Meeting | | | 7/23/2008 | | DONE |
|
|
|
Meeting with Jay Lungren, GM, Cate Idaho Equipment, (###-####) regarding proposed storage on racks. they will eliminate the top horizontal rack beam so highest beam will be at below 8', to eliminate seisic design requirements. Overall storage height to be maintained at less than 12' high, with signs posted at top of rack uprigts (12' high) indicating "No storage above this level"; to eliminate HP storage requirements. Sprinkler system is reportedly designed for OH 2, 0.20gpm/sf/over 1500sf area.
|
Permanent Occupancy UNPAID FEE | | | 6/10/2008 | | |
|
|
|
|
BLD-Final | 6/4/2008 | 6/5/2008 | 6/5/2008 | P | PASS |
Jim Storey
|
|
|
Kevin Phone #: ###-#### final ok
|
FIRE-Final Inspection | 6/4/2008 | 6/5/2008 | 6/5/2008 | A | PASS |
Troy Cobbley
|
|
|
fire life saftey passed
|
FIRE-Final Inspection | 6/3/2008 | 6/4/2008 | 6/4/2008 | P | FAIL |
Troy Cobbley
|
|
|
Needs the project related fire alarm and fire sprinkler permits finaled prior to this inspection. Contractor and I discussed the fire dept access requirements.
|
BLD-Conference | 6/2/2008 | 6/3/2008 | 6/3/2008 | A | PART |
Jim Storey
|
|
|
kevin Phone #: ###-#### only one locking door at entry/ remove flush bolts on office inactive leaf/ sink must be 34 max height/ protect trap under sink.
|
PubWorks Occupancy Approval | 6/6/2008 | 6/6/2008 | 6/3/2008 | | DONE |
|
|
|
Signed final occupancy 06/03/08 R. Rokovitz.
|
Code Occupancy Approval | 6/2/2008 | 6/2/2008 | 6/2/2008 | P | PASS |
Wm. Michael Meloy
|
|
|
Compliance met
|
FIRE-Final Inspection | 5/30/2008 | 6/2/2008 | 6/2/2008 | P | CANC |
Troy Cobbley
|
|
|
kevin - fire life safety Phone #: ###-#### Inspection cancelled from web by: Patricia Smith
|
BLD-Framing/Rough-in | 4/24/2008 | 4/25/2008 | 4/25/2008 | P | PASS |
Jim Storey
|
|
|
ceiling grid Phone #: ###-####
|
BLD-Energy code compliance | 3/26/2008 | 3/27/2008 | 3/27/2008 | A | PASS |
Jim Storey
|
|
|
kevin Phone #: ###-####
|
BLD-Framing/Rough-in | 3/20/2008 | 3/21/2008 | 3/21/2008 | P | PART |
Tom Arcoraci
|
|
|
kevin - call if you are going to be later than 3:30 Phone #: ###-#### west side ok
|
Plan resubmittals received | | | 3/21/2008 | | |
|
|
|
Received 1 cover transmittal and 2 copies of sheets C1.0 & C2.0 and taken to Scott Arellano 3-21-08 @ 9:34am BAS
|
Telephone call | | | 3/21/2008 | | DONE |
|
|
|
Left voice message for Dennis Montgomery at Treasure Valley Engineers that stamped and approved set of plans need picked up///3-21-08 @ 12:25pm BAS
|
Plan resubmittals received | | | 3/21/2008 | | DONE |
|
|
|
Received plan modification reflecting the removal of the FD vehicle turnaround from plan sheet C1.0 & C2.0. Delivered one set of plan sheet C1.0 and C2.0 to records; issued the field set to Treasure Valley Engineers.
|
Meeting | | | 3/20/2008 | | DONE |
|
|
|
Met with Mark Senteno regarding the removal of the required FD vehicle access turnaround. Captain Senteno has determined that the combination of ample yard space with compact gravel surfacing material able to support the fire apparatus and the initial driveway turnaround will satisy Fire Department concerns.
|
BLD-Other | 3/5/2008 | 3/5/2008 | 3/6/2008 | P | PASS |
Jim Storey
|
|
|
rick Note: cover Phone #: ###-#### exterior sheathing ok to cover.
|
BLD-Aging Inspection | 2/14/2008 | 2/14/2008 | 2/14/2008 | | PASS |
Jim Storey
|
|
|
foundiation and steel ereaction completed with si at this time pending review of the reports at framing insp to be requisted when ready.
|
(F) Reprint permit | | | 11/16/2007 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 11/15/2007 | | DONE |
|
|
|
|
Print Occupancy Form | | | 11/14/2007 | | DONE |
|
|
|
|
Telephone call | | | 11/14/2007 | | DONE |
|
|
|
left message w sandy for rick bugatsch at ###-#### - permit ready and fees given - also need ACHD receipt
|
Permit Ready to Issue | | | 11/14/2007 | | DONE |
|
|
|
|
Plan resubmittals received | | | 11/13/2007 | | |
|
|
|
Received 1 cover letter, 1 response letter from Rick Bugatsch dated 11/13/07, 2 copies of sheets A1 & A3 inserted into plans by Houston Bugatsch office and taken back to John Menard///11/13/07 @ 1:31pm BAS
|
Plan Reviewer's activity | | | 11/13/2007 | | PASS |
|
|
|
Reviewed and approved nonstructural revisions. JCM
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/13/2007 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 10/17/2007 | | 11/13/2007 | | PASS |
|
|
|
|
Plan assigned to (JCM) | 8/13/2007 | | 11/13/2007 | | PASS |
|
|
|
11/13/2007 14:38:41 JCM - activity updated through activity BLDA022 from case BLD07-02067.
|
Plan resubmittals received | | | 11/5/2007 | | |
|
|
|
Received 1 cover transmittal, 1 plan review responce letter dated 11/1/07 from Rick Bugatsch, 2 copies of the following sheets- A1, A2,A3, A5, M3.0, M3.1, E2.0, E3.0 and inserted into plans by Joshua Houston from the Architects office on 11/5/07 @ 8:21am and taken back to John's desk
|
Plan Reviewer's activity | | | 11/5/2007 | | PASS |
|
|
|
Reviewed and approved structural responses. JCM
|
Plan resubmittals requested | | | 11/5/2007 | | DONE |
|
|
|
|
Routing - FIRE | 10/15/2007 | | 10/17/2007 | | PASS |
|
|
|
Attached updated IFC review comments to plans.
|
Routing - PUBLIC WORKS | 10/9/2007 | | 10/15/2007 | | PASS |
|
|
|
|
Routing PW Drainage | 10/10/2007 | | 10/15/2007 | | PASS |
|
|
|
|
Routing - PLAN CHECK | 9/19/2007 | | 10/9/2007 | | |
|
|
|
|
Plan resubmittals received | | | 10/5/2007 | | |
|
|
|
received transmittal letter from treasure valley engineers & united water map, (8) pages of fire code review---also "2" sheets each of C1.OC1.1, C2.O, C3.O--plans taken back to John Menard
|
1st review completed | | | 9/19/2007 | | FAIL |
|
|
|
|
Routing - FIRE | 9/14/2007 | | 9/19/2007 | | FAIL |
|
|
|
Faxed and emailed review resubmittal items to architect.
|
Routing - PLAN CHECK | 8/27/2007 | | 9/14/2007 | | FAIL |
|
|
|
John Menard
|
Plan resubmittals requested | | | 9/14/2007 | | DONE |
|
|
|
E-mailed the architect a copy of the plan review requesting revisions. JCM
|
Routing - PLANNING | 8/21/2007 | | 8/24/2007 | | PASS |
|
|
|
Approved per DRH07-00078 and routed to Diane Perkins for review for teh associated CU. ANT
CUP07-00065 - PASS - DCP, routed to plan check 8/24/07
|
Routing Off Site - STRUCTURAL | 8/14/2007 | | 8/23/2007 | | FAIL |
|
|
|
Received comment list from the consulting structural engineer requesting revisions. JCM
|
Plan resubmittals requested | | | 8/23/2007 | | DONE |
|
|
|
Faxed the architect a copy of the structural plan review requesting revisions.
|
Routing - PLUMBING | 8/21/2007 | | 8/21/2007 | | PASS |
|
|
|
water piping to P-8s in the garage and the make up water to the boiler must be protected by an r.p..
|
Routing - Erosion and Sediment | 8/20/2007 | | 8/21/2007 | | PASS |
|
|
|
ESC plan approved with attached conditions.
|
Routing - PUBLIC WORKS | 8/14/2007 | | 8/20/2007 | | FAIL |
|
|
|
|
Routing PW Drainage | 8/14/2007 | | 8/20/2007 | | FAIL |
Brian Murphy
|
|
|
WASH PAD CONNECTED TO STORMWATER SYSTEM
|
Routing PW Sewer Rating | 8/14/2007 | | 8/20/2007 | | PASS |
|
|
|
|
Routing PW Solid Waste | 8/14/2007 | | 8/20/2007 | | PASS |
|
|
|
|
Routing PW Sewer Design | 8/14/2007 | | 8/16/2007 | | PASS |
|
|
|
|
Routing PW Street Lights | 8/14/2007 | | 8/16/2007 | | PASS |
|
|
|
|
Routing - PLANNING Land Div | 8/14/2007 | | 8/14/2007 | | PASS |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 8/14/2007 | | |
|
|
|
|
Plan routing begun/NEW & ADDTN | | | 8/14/2007 | | |
|
|
|
|
Pending Assignment by MYS | 8/8/2007 | | 8/13/2007 | | DONE |
|
|
|
8/13/2007 08:17:44 JCM - activity updated through activity BLDA166 from case BLD07-02067.
|
Recd Pcfee & Taken To Pln CK | | | 8/8/2007 | | DONE |
|
|
|
|
Application received | | | 8/8/2007 | | |
|
|
|
|