Permit Information
Permit NumberBLD07-02112
StatusFinaled
Name STOCK CONSTRUCTION MANAGEMENT
Site Address 9095 S FEDERAL WAY
Project NameBerry Family Building
Customer Number 
ePlanReviewNo
Description
Berry Family Building (Shell) - To construct a new 26,000 square foot, two story, office, retail and warehouse building and related site improvements. This building is constructed of masonry exterior walls and steel structural floor and roof framing. This building was reviewed as unseparated used. The building is fully fire sprinkled. The sprinklers are used for area and story increase. First Floor: 18,160 sq. ft., Second Floor: 7,840 sq. ft.. This is a shell permit only and no occupancy is allowed under this permit. Separate tenant improvement permits will be required to finish this building for occupancy. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary (BLD)  1/9/2012  
PubWorks Occupancy Approval12/30/200912/30/200912/30/2009 DONE
DetailsTiffany Lowery
Telephone call  12/16/2009 DONE
DetailsTisha Gallop
called and left vm for Eric still need breakdown of final values, Stock Const. is now on hold for no inspections or permit until I receive this.
Telephone call  11/25/2009 DONE
DetailsTisha Gallop
called and left vm for Eric Holenka/Stock Const. need breakdown of contractors to process final value he gave, told him if not hear from him within two weeks will put company on hold.
Third Notice 11/5/200911/5/2009 DONE
Telephone call  11/5/2009 DONE
DetailsTisha Gallop
called Eric Holenka/Stock Const. and left vm need additional info for final value. Breakdown of plumbing contractor values since more than one.
Third Notice 10/17/200910/26/2009 DONE
faxed, mailed and called
Telephone call  10/26/2009 DONE
DetailsTisha Gallop
called and left two vm, one for Eric Holenka and one in the general mailbox need final values. Note: got correct fax number from the company's general voice message.
Third Notice 9/8/200910/7/2009 DONE
mailed
Telephone call  10/7/2009 DONE
DetailsTisha Gallop
called Stock Const. and left voice message need good fax number
Second Notice 7/23/20099/8/2009 DONE
First Notice6/11/20096/11/20097/23/2009 DONE
DetailsJim Storey
BLD-Final6/10/20096/10/20096/11/2009PPASS
DetailsJim Storey
Please call at least a half hour prior for access meeting-Harry Phone #: ###-####
DOC - Permit Finaled6/11/20096/11/20096/11/2009PPASS
DetailsJim Storey
FIRE-Final Inspection6/8/20096/9/20096/9/2009PPASS
DetailsForrest France
Shell building fire life safety inspection passed, no inspection record on site for signature, additional address numbers to be posted at the east side of the structure per discussion.
BLD-Aging Inspection6/5/20096/5/20096/5/2009 PART
DetailsJim Storey
will call for final 6/8/09
Zoning Approval3/24/20093/24/20093/25/2009 DONE
DetailsSarah Schafer
BLD-Aging Inspection3/23/20093/23/20093/24/2009PPART
DetailsForrest France
Project related fire alarm permit has been finaled, need fire life safety inspection prior to building final.
BLD-Aging Inspection3/23/20093/23/20093/23/2009 DEFR
DetailsJim Storey
talked with eric at stock const. to call for p&z final insp.
BLD-Aging Inspection1/19/20091/19/20091/20/2009 NR
DetailsJim Storey
pending p&z activity in note field. no requist for final on bld
FIRE-Final Inspection10/23/200810/23/200810/23/2008PNR
DetailsForrest France
Need project related fire alarm permit final prior to building fire life safety approval.
BLD-Aging Inspection9/12/20089/12/20089/12/2008 PASS
DetailsJim Storey
wip
BLD-Other7/3/20087/7/20087/7/2008APART
DetailsJim Storey
harry Note: ceiling grid Phone #: ###-####
BLD-Conference6/25/20086/25/20086/25/2008PPASS
DetailsJim Storey
harry Phone #: ###-####
BLD-Framing/Rough-in6/12/20086/13/20086/13/2008APASS
DetailsJim Storey
Harry; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt 2nd floor ok to cover.
BLD-Framing/Rough-in6/5/20086/5/20086/5/2008PPASS
DetailsJim Storey
perry Phone #: ###-#### first floor ok to cover.
BLD-Framing/Rough-in5/23/20085/27/20085/27/2008APART
DetailsTom Arcoraci
harry Phone #: ###-#### int shear ok for one sde cover
BLD-Framing/Rough-in5/8/20085/12/20085/12/2008APART
DetailsJim Storey
mitch Phone #: ###-#### rfi to engineer for sheer wall edge blk or not for screw sch./ verrifcation of pin only for sheer wall interior shot pin only/ bolts still need tightened before 2 nd floor concrete is to be placed/
BLD-Footing1/8/20081/9/20081/9/2008PPASS
DetailsJim Storey
Scheduled by a contractor via Hello! on 1/8/2008 at 3:31:42 PM. Contact: ###-####. center pad ft and rebar mats ok pending si testing of the concrete.
FIRE-Supply Line Hydro1/4/20081/4/20081/4/2008PCANC
DetailsForrest France
Incorrect inspection type, was intended for the plumbing permit work.
BLD-Footing12/3/200712/4/200712/4/2007PPASS
DetailsJim Storey
Scheduled by a contractor via Hello! on 12/3/2007 at 4:03:23 PM. Contact: ###-####.
BLD-Footing11/28/200711/29/200711/29/2007APASS
DetailsJim Storey
Scheduled by a contractor via Hello! on 11/28/2007 at 12:34:12 PM. Contact: ###-####. if possible mid-morning north ft ok
BLD-Footing11/27/200711/28/200711/28/2007APASS
DetailsJim Storey
Note: If possible MID MORNING Scheduled by a contractor via Hello! on 11/27/2007 at 12:09:17 PM. Contact: ###-####. south side ok ft
(F) Reprint permit  10/30/2007  
Issue PAID IN FULL permit  10/29/2007 DONE
Inspection Record Card- Bld  10/10/2007 DONE
Telephone call  10/10/2007 DONE
left vm for scott marshall at ###-#### - permit ready and fees given - also need ACHD receipt and rp name
Permit Ready to Issue  10/10/2007 DONE
Plan assigned to (JCM)8/17/20078/17/200710/9/2007 PASS
10/9/2007 13:40:56 JCM - activity updated through activity BLDA022 from case BLD07-02112.
Routing - PUBLIC WORKS9/27/2007 10/9/2007 PASS
Routing PW Drainage9/27/2007 10/9/2007 PASS
Routing - PLAN CHECK10/9/2007 10/9/2007 PASS
PLANS/APPL TAKEN TO FRONT DESK  10/9/2007 DONE
Routing - FIRE9/24/2007 9/27/2007 PASS
Attached updated IFC review comments to plans.
Routing - PLAN CHECK9/16/2007 9/24/2007 PASS
Plan resubmittals received  9/24/2007  
received transmittal( 2 pages) from lkv arch, building permit fire review, (7) pages. also "2" sheets of C-1.O, & C-1.1--plans taken to John Menard
Plan Reviewer's activity  9/24/2007 PASS
Reviewed and approved structural and nonstructural revisions. JCM
Plan resubmittals received  9/19/2007  
received transmittal from lkv arch & "5" pages each with comments & structural review letter -also "3" sets of plans including each sheet of A-6.O, A-6.1-plans taken to John Menard/--brought in more plans--transmittal letter from lkv arch, letter to John Menard, & plan review report (4) pages-also the cover sheet, & (3) sets of plans with each sheet -including--SL-1.1, A-3.1, A-.3.2--Pamela Johnson inserted the resubmittals in plans-- taken to John Menard
1st review completed  9/16/2007 FAIL
Routing - FIRE9/11/2007 9/16/2007 FAIL
Emailed and Faxed resubmittal items to architect. Attached review comments to plans.
Routing - PLAN CHECK9/5/2007 9/11/2007 FAIL
Plan resubmittals requested  9/11/2007 DONE
E-mailed the architect a copy of the plan review requesting revisions. JCM
Plan resubmittals received  9/7/2007 DONE
Received 1 transmittal, and 5 copys of sheet C-1.0,C-1.1,C-1.2 resubmittals have been inserted into plans and taken back to John M.
Plan resubmittals requested  9/6/2007 DONE
E-mailed the architect a copy of the structural review requesting revisions. JCM
Routing - PLANNING8/30/2007 9/5/2007 PASS
Approved per DRH07-00283 and routed to Diane P. for CU review.

Diane P. CUP07-00063 - PASS, DCP
Routing Off Site - STRUCTURAL8/17/2007 9/4/2007 FAIL
Called Action Couriers for pick up - Received comment list from consulting structural engineer requesting revisions. JCM
Routing - PLUMBING8/27/2007 8/30/2007 PASS
per plans and 2003 upc.
Routing - Erosion and Sediment8/24/2007 8/27/2007 PASS
ESC plan approved with attached conditions.
Routing PW Sewer Rating8/20/2007 8/24/2007 PASS
Fees to assessed with tenant improvement plans
Routing PW Solid Waste8/20/2007 8/24/2007 PASS
Routing PW Environmental8/24/2007 8/24/2007 PASS
Common grease line shown in shell core to single GI indicated on civil plan sheet. Approved design of a 1500 gallon GI shall be used.
Routing PW Drainage8/20/2007 8/22/2007 FAIL
DetailsBrian Murphy
Seperation to groundwater. Access road drainage.
Routing PW Street Lights8/20/2007 8/21/2007 PASS
Routing PW Sewer Design8/20/2007 8/20/2007 PASS
Routing - PLANNING Land Div8/17/2007 8/20/2007 PASS
Plan routing begun/NEW & ADDTN  8/17/2007  
Pending Assignment by MYS8/13/2007 8/17/2007 DONE
8/17/2007 12:42:42 DLD - activity updated through activity BLDA166 from case BLD07-02112.
Plans ACCEPTED BY PLAN TECH  8/17/2007  
Application received  8/13/2007