Second Notice BLD | 1/9/2008 | 1/9/2008 | 1/18/2008 | | DONE |
Cathy Brown
|
|
|
First Notice has not been responded to.
|
First Notice | 11/13/2007 | 11/13/2007 | 1/9/2008 | | DONE |
Jim Storey
|
|
|
|
BLD-Final | 11/9/2007 | 11/13/2007 | 11/13/2007 | P | PASS |
Jim Storey
|
|
|
mike Phone #: ###-####
|
DOC - Permit Finaled | 11/13/2007 | 11/13/2007 | 11/13/2007 | P | PASS |
Jim Storey
|
|
|
|
FIRE-Final Inspection | 11/9/2007 | 11/13/2007 | 11/13/2007 | A | PASS |
Forrest France
|
|
|
All repairs were made as per Forrest notes.
|
FIRE-Final Inspection | 11/7/2007 | 11/8/2007 | 11/8/2007 | A | FAIL |
Forrest France
|
|
|
Need to add exit signs at locations as discussed, EM lighting at two locations is not functional, PFE's are okay, will test remaider of EM lighting at next inspection.
|
BLD-Final | 11/7/2007 | 11/8/2007 | 11/8/2007 | P | CANC |
Jim Storey
|
|
|
mike gulley; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt unable to final to fire inspect not correct
|
Issue PAID IN FULL permit | | | 10/31/2007 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 10/30/2007 | | DONE |
|
|
|
|
Telephone call | | | 10/30/2007 | | DONE |
|
|
|
left message w mary for brandi johns at ###-#### - permit ready and fees given - also need gc name and rce#
|
Permit Ready to Issue | | | 10/30/2007 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 10/26/2007 | | 10/29/2007 | | PASS |
|
|
|
|
1st review completed | | | 10/29/2007 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/29/2007 | | DONE |
|
|
|
|
Plan assigned to (R_H) | 9/28/2007 | | 10/29/2007 | | PASS |
|
|
|
10/29/2007 13:57:28 RMH - activity updated through activity BLDA022 from case BLD07-02475.
|
Routing - FIRE | 10/23/2007 | | 10/26/2007 | | PASS |
|
|
|
Attached review comments to plans. This rack permit is for the previously submitted sprinkler permit FIR06-0531 which was erroneously indicated on the application to be attached to BLD06-01697. The latest sprinkler review for FIR06-00531 has now been edited to show this permit (BLD07-02475) as the correct associated permit, and the projects have been clerically corrected. SLR 10/26/07
|
1st review completed | | | 10/26/2007 | | PASS |
|
|
|
|
Case Summary (BLD) | | | 10/23/2007 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 9/28/2007 | | 10/23/2007 | | PEND |
|
|
|
|
Pending Assignment by MYS | 9/13/2007 | | 9/28/2007 | | DONE |
|
|
|
9/28/2007 11:13:18 MYS - activity updated through activity BLDA175 from case BLD07-02475.
|
Plans ACCEPTED BY PLAN TECH | | | 9/14/2007 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 9/13/2007 | | |
|
|
|
|
Application received | | | 9/13/2007 | | |
|
|
|
|