Third Notice BLD | 6/6/2008 | 6/6/2008 | 7/22/2008 | | DONE |
Cathy Brown
|
|
|
Second Notice has not been responded to.
|
Second Notice BLD | 4/23/2008 | 4/23/2008 | 6/6/2008 | | DONE |
Cathy Brown
|
|
|
First Notice has not been responded to.
|
First Notice | | 2/1/2008 | 4/23/2008 | | DONE |
|
|
|
|
Permanent Occupancy UNPAID FEE | | | 2/1/2008 | | |
|
|
|
|
BLD-Final | 1/31/2008 | 1/31/2008 | 1/31/2008 | P | PASS |
Dave Hannah
|
|
|
don Phone #: ###-#### ok fo perm occ
|
FIRE-Final Inspection | 1/30/2008 | 1/31/2008 | 1/31/2008 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed
|
Additional plans submitted | | | 1/30/2008 | | DONE |
|
|
|
New plan sheet M1.0 submitted having smoke/fire dampers originallu indicated on mechanical plans deleted from scope of work. The wall between the office and lab area is not a rated wall and opening protection is not required by code. I checked with architect Justin Touchstone to verify his intent to remove the SF dampers. He confirmed and I approved the new plan Sheet M1.0. A copy given to contractor and a copy of new sheet to records.
|
Plan resubmittals received | | | 1/30/2008 | | PASS |
|
|
|
New plan sheet M1.0 submitted removing the smoke/fire dampers between the office area and new lab area. Not required by code but shown on original plans by mechanical designer. Fire inspector had failed the final inspection until an alarm permit was aquired and the S/F dampers connected to existing FACP panel OR the S/F dampers were removed from plan and approved by plan review.
|
FIRE-Final Inspection | 1/25/2008 | 1/29/2008 | 1/29/2008 | A | FAIL |
Forrest France
|
|
|
A fire alarm permit will be necessary to interconnect the new smoke detectors at the two FSD's to the FACP or provide an approved building plan modification for deletion of the dampers, need to remove the manual flush bolts at the lathe room inactive door leaf, also the fire sprinkler permit needs to be finaled prior to life safety.
|
FIRE-Sprinkler Rough-in | 1/28/2008 | 1/29/2008 | 1/29/2008 | A | FAIL |
Forrest France
|
|
|
Mixed response heads are not allowed within the same fire area at the new lab and lathe rooms.
|
BLD-Other | 1/25/2008 | 1/28/2008 | 1/28/2008 | A | PART |
Jim Storey
|
|
|
don wilcox-drop down ceiling inspection please Phone #: ###-#### need clips or spreader bar / auto flush bolts on double doors.
|
BLD-Framing/Rough-in | 1/8/2008 | 1/8/2008 | 1/8/2008 | P | PASS |
Jim Storey
|
|
|
don Phone #: ###-####
|
Print Occupancy Form | | | 12/19/2007 | | DONE |
|
|
|
|
Telephone call | | | 12/19/2007 | | DONE |
|
|
|
left vm for don wilcox at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 12/19/2007 | | DONE |
|
|
|
|
Issue PAID IN FULL permit | | | 12/19/2007 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/18/2007 | | PASS |
|
|
|
|
Routing - PUBLIC WORKS | 11/16/2007 | | 12/18/2007 | | PASS |
|
|
|
|
Plan assigned to (DRS) | 12/10/2007 | | 12/18/2007 | | PASS |
|
|
|
12/18/2007 16:39:20 DRS - activity updated through activity BLDA022 from case BLD07-02828.
|
Routing - PLAN CHECK | 12/13/2007 | | 12/18/2007 | | PASS |
|
|
|
Resubmittals of 12/17/07 inserted into plans. No further requirements. Routing to permit desk to issue.
|
Plan resubmittals received | | | 12/17/2007 | | |
|
|
|
received one response letter from architect, three copies of response letter from engineer, structural calcs and pages A1.1, A1.2; taken to Dan Stuart
|
1st review completed | | | 12/13/2007 | | FAIL |
|
|
|
Failed plan check
|
Routing - FIRE | 12/11/2007 | | 12/13/2007 | | PASS |
Scott Arellano
|
|
|
Plans are approved with red line annotations. Attached IFC review comments to plans.
|
Routing - PLAN CHECK | 12/10/2007 | | 12/11/2007 | | FAIL |
|
|
|
Copy of plan review corrections e-mailed to J Touchstone. Plans routed to fire code analyst.
|
Plan resubmittals requested | | | 12/11/2007 | | DONE |
|
|
|
E-mailed to J. Touchstone.
|
Plan assigned to (R_H) | 11/16/2007 | | 12/10/2007 | | DONE |
|
|
|
Reasigned to Dan Stuart
|
Plan resubmittals received | | | 12/5/2007 | | |
|
|
|
Received letter to Ron Hill addressing the specific uses of the lab and mill areas; inserted into plans and taken back to Ron
|
Routing PW Environmental | 11/19/2007 | | 11/19/2007 | | PASS |
|
|
|
Facility operations subject to future Pretreatment inspection. No new plumbing indicated on TI plans.
Walt Baumgartner ###-####
|
Routing PW Sewer Rating | 11/19/2007 | | 11/19/2007 | | PASS |
|
|
|
|
Routing - Addressing | 11/16/2007 | | 11/16/2007 | | PASS |
|
|
|
|
Pending Assignment by MYS | 10/30/2007 | | 11/16/2007 | | DONE |
|
|
|
11/16/2007 11:55:14 MYS - activity updated through activity BLDA175 from case BLD07-02828.
|
Plans ACCEPTED BY PLAN TECH | | | 10/31/2007 | | |
|
|
|
|
Application received | | | 10/30/2007 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 10/30/2007 | | |
|
|
|
|