Permit Information
Permit NumberBLD07-03062
StatusFinaled
Name FAIRVIEW MILWAUKEE L L C
Site Address 1517 N MILWAUKEE ST
Project Name 
Customer Number 
ePlanReviewNo
Description
*(IOU SUSHI)* I am not providing a contractor registration number because I am exempt per idaho state code 54-5205 To remodel an existing 1700 sq ft restaurant for new food service tenant per approved plans. Work to include, construction of a new counter, installation of new type-one hood system, installation of new sinks, miscellaneous installation of kitchen appliances, this building is fully fire sprinklered ANY ALTERATIONS TO THE SPRINKLER SYSTEM WILL REQUIRE A SEPARATE PERMIT and shall be installed and maintained per NFPA #13 as regulated by the fire department. This space was formerly occupied by "TYCB" RmH
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice BLD3/5/20083/5/200810/23/2008 DONE
DetailsCathy Brown
Second Notice has not been responded to.
Second Notice BLD2/6/20082/6/20083/5/2008 DONE
DetailsCathy Brown
First Notice has not been responded to.
First Notice 1/25/20082/6/2008 DONE
BLD-Final1/24/20081/25/20081/25/2008APASS
DetailsJim Sly
rocky Phone #: ###-####
OK for Perm Occ. :)
Permanent Occupancy UNPAID FEE  1/25/2008  
FIRE-Final Inspection1/22/20081/22/20081/22/2008PPASS
DetailsTroy Cobbley
life safety passed
FIRE-Final Inspection1/18/20081/18/20081/18/2008PFAIL
DetailsTroy Cobbley
provide sticker at main exit as discussed, install all ceiling tile, remove the hooks off of the rear exit door and repair or remove the non functional emergency light.
BLD-Final1/15/20081/16/20081/16/2008ANR
DetailsMike Jordan
rocky Phone #: ###-####. Needs mech, and fire/life/safety finals first. Contractor was contacted.
FIRE-Final Inspection12/12/200712/13/200712/13/2007AFAIL
DetailsTroy Cobbley
Repair the exit signs and emergency lights, provide sticker at the main exit, install the hood, hood suppression system and fire alarm interconnection. All of this work requires separate permits. Provide permit for the fire sprinkler work that needs done such as the sprinkler head that is too close to the wall and protection in the cooler that has not been installed yet. Provide fire extinguishers. Provide lever hardware on the restroom door.
FIRE-Final Inspection12/6/200712/7/200712/7/2007AFAIL
DetailsTroy Cobbley
rocky Phone #: ###-#### I could not get ahold of the contact. Space was open. I noticed problems with the exit signs, emergency lights and sprinkler heads. No approved plans were on site.
Plan assigned to (R_H)11/28/200711/28/200712/6/2007 PASS
12/6/2007 09:36:22 RMH - activity updated through activity BLDA022 from case BLD07-03062.
Case Summary (BLD)  12/6/2007 DONE
1st review completed  12/6/2007  
PLANS/APPL TAKEN TO FRONT DESK  12/6/2007 DONE
Print Occupancy Form  12/6/2007 DONE
CHANGE STATUS TO (RDY)  12/6/2007 DONE
Telephone call  12/6/2007 DONE
called left message with Jane permit ready and fee given ALSO NEED G C RCE #
Issue PAID IN FULL permit  12/6/2007 DONE
Routing - PLAN CHECK11/28/2007 12/6/2007 PASS
Routing - PUBLIC WORKS11/28/2007 11/29/2007 PASS
Routing PW Environmental11/29/2007 11/29/2007 PASS
Plans approved w/ 25gpm Big Dipper grease device indicated on plans sheet. Facility subject to pretreatment regulations of West Boise Sewer District.
Routing PW Sewer Rating11/29/2007 11/29/2007 PASS
Routing - PLUMBING11/29/2007 11/29/2007 PASS
check fixture loading on 3/4" water service and increase line size if required. vent on indirect waste to exit seperatly. premise backflow or point of use backflow may be required,
Plans ACCEPTED BY PLAN TECH  11/28/2007  
Need Contractor Registration #
Application received  11/27/2007