Third Notice BLD | 1/29/2009 | 1/29/2009 | 2/5/2009 | | DONE |
Cathy Brown
|
|
|
Second Notice has not been responded to.
|
Second Notice BLD | 1/2/2009 | 1/2/2009 | 1/29/2009 | | DONE |
Cathy Brown
|
|
|
First Notice has not been responded to.
|
First Notice | | 11/25/2008 | 1/2/2009 | | DONE |
|
|
|
|
Permanent Occupancy | | | 11/25/2008 | | DONE |
Barbara Stitt
|
|
|
|
Zoning Approval | 11/18/2008 | 11/18/2008 | 11/18/2008 | | PASS |
Josh Wilson
|
|
|
Landscaping has been completed for release of bond and permanent occupancy.
|
BLD-Final | 10/30/2008 | 10/31/2008 | 10/31/2008 | A | PASS |
Jim Sly
|
|
|
Scheduled by a contractor via Hello! on 10/30/2008 at 4:12:50 PM. Contact: ###-####. Landscape bonded....OK for Perm Occ.
|
Temporary Occupancy UNPAID FEE | | | 10/31/2008 | | DONE |
|
|
|
|
BLD-Final | 10/29/2008 | 10/30/2008 | 10/30/2008 | P | FAIL |
Jim Sly
|
|
|
Scheduled by a contractor via Hello! on 10/29/2008 at 4:35:32 PM. Contact: ###-####. Provide 1hr protection at ceiling duct ....Med gas room.
|
Zoning Approval Temp | 10/30/2008 | 10/30/2008 | 10/30/2008 | | PASS |
Josh Wilson
|
|
|
Temporary occupancy per bond BND08-00088 for unfinished landscaping.
|
BLD-Final | 10/29/2008 | 10/29/2008 | 10/29/2008 | P | NR |
Jim Sly
|
|
|
John ###-####
|
FIRE-Final Inspection | 10/28/2008 | 10/29/2008 | 10/29/2008 | A | PASS |
Troy Cobbley
|
|
|
life safety passed
|
FIRE-Final Inspection | 10/27/2008 | 10/28/2008 | 10/28/2008 | P | FAIL |
Troy Cobbley
|
|
|
See the city approved plans for the deficiencies which have been listed on the review comments.
|
FIRE-Conference | 10/27/2008 | 10/27/2008 | 10/27/2008 | P | DONE |
Troy Cobbley
|
|
|
I discussed the installation requirements for duct smoke detectors.
|
BLD-Other | 10/2/2008 | 10/2/2008 | 10/2/2008 | P | DONE |
Jim Sly
|
|
|
Scheduled by a contractor via Hello! on 10/2/2008 at 10:13:26 AM. Contact: ###-####. Grid ok
|
BLD-Energy code compliance | 7/7/2008 | 7/7/2008 | 7/7/2008 | P | PEND |
Mike Jordan
|
|
|
ivey Phone #: ###-####
|
BLD-Framing/Rough-in | 7/2/2008 | 7/2/2008 | 7/2/2008 | P | PASS |
Jim Sly
|
|
|
John- wall Phone #: ###-#### Frame and shear OK
|
BLD-Footing | 5/19/2008 | 5/20/2008 | 5/20/2008 | A | PART |
Jim Sly
|
|
|
russ-and colum inspection please Phone #: ###-#### Column pads at entry OK....columns OK.
|
BLD-Conference | 4/1/2008 | 4/2/2008 | 4/2/2008 | A | CANC |
Jim Sly
|
|
|
Russ ###-####
|
BLD-Foundation | 3/20/2008 | 3/21/2008 | 3/21/2008 | A | PASS |
Jim Sly
|
|
|
russ Phone #: ###-####
|
BLD-Footing | 3/7/2008 | 3/7/2008 | 3/7/2008 | P | PASS |
Jim Sly
|
|
|
Scheduled by a contractor via Hello! on 3/7/2008 at 10:38:00 AM. Contact: ###-####.
|
(F) Reprint permit | | | 2/20/2008 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 2/19/2008 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 2/12/2008 | | 2/14/2008 | | PASS |
John Menard
|
|
|
|
Plan assigned to (JCM) | 12/20/2007 | | 2/14/2008 | | PASS |
John Menard
|
|
|
2/14/2008 08:31:58 JCM - activity updated through activity BLDA022 from case BLD07-03229.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/14/2008 | | DONE |
|
|
|
|
Print Occupancy Form | | | 2/14/2008 | | DONE |
|
|
|
|
Telephone call | | | 2/14/2008 | | DONE |
|
|
|
t/c w jay rice at ###-#### - permit ready and fees given - also need ACHD receipt
|
Permit Ready to Issue | | | 2/14/2008 | | DONE |
|
|
|
|
Plan Reviewer's activity | | | 2/13/2008 | | PASS |
|
|
|
Reviewed and approved structural and nonstructural revisions. JCM
|
Plan resubmittals requested | | | 2/12/2008 | | DONE |
|
|
|
Faxed the architect a copy of structural comments requesting revisions. JCM
|
Routing Off Site - STRUCTURAL | 2/5/2008 | | 2/12/2008 | | FAIL |
John Menard
|
|
|
Called Action Courier for pick up-2-5-08 @ 2:10pm BAS
|
Routing - PLAN CHECK | 2/9/2008 | | 2/12/2008 | | |
John Menard
|
|
|
|
Routing - PLANNING | 2/12/2008 | | 2/12/2008 | | PASS |
Josh Wilson
|
|
|
PASS per revised site plan submitted 2-11-08
|
Plan resubmittals received | | | 2/11/2008 | | |
|
|
|
received resonse letter, and two copies of sheets A-1, A-2, A-7, A-8; inserted by arch. rep. and taken back to John Menard
|
Routing - FIRE | 2/5/2008 | | 2/9/2008 | | PASS |
Scott Arellano
|
|
|
Attached IFC comments to plans
|
Plan resubmittals requested | | | 2/5/2008 | | DONE |
|
|
|
Faxed the architect a comment list requesting additional revisions. JCM
|
Routing - PLAN CHECK | 1/16/2008 | | 2/5/2008 | | FAIL |
John Menard
|
|
|
|
Plan resubmittals received | | | 2/4/2008 | | |
|
|
|
Received repsonse letter, letter to Scott Arellano and two copies of sheets SD-1, A-1, A-2, A-3, A-4, A-7, A-8, S2.1, S2.2, S2.3, S3.1, S3.2, S3.3, E3, E4; inserted by arch. rep. and taken back to John Menard
|
1st review completed | | | 1/16/2008 | | FAIL |
|
|
|
Failed Structural, Plan Check, Fire
|
Routing - FIRE | 1/14/2008 | | 1/16/2008 | | FAIL |
Scott Arellano
|
|
|
Faxed and emailed resubmittal items to architect.
|
Plan resubmittals received | | | 1/15/2008 | | DONE |
|
|
|
received 2 letters of transmittals, 3 response code reviews and 3 copies of sheets S0.1,S1.1,S1.2,S1.3,S2.1,S2.2,S2.3,S3.1,S3.2,S3.3,S5.1 inserted by Darla and returned to Fire///dld
|
Plan resubmittals requested | | | 1/14/2008 | | DONE |
|
|
|
E-mailed the architect a copy of the plan review requesting revisions. JCM
|
Routing - PLAN CHECK | 1/4/2008 | | 1/14/2008 | | FAIL |
John Menard
|
|
|
John Menard
|
Routing - PLANNING | 1/3/2008 | | 1/4/2008 | | FAIL |
Josh Wilson
|
|
|
Site plan does not comply with Condition 1b of DR approval
DRH07-00528 Josh W.
|
Routing - PLUMBING | 1/3/2008 | | 1/3/2008 | | PASS |
Bill VanDegrift
|
|
|
max. length of 1 1/2" vent is 20'. provide each floor drain with a vent.
|
Routing - Erosion and Sediment | 1/2/2008 | | 1/3/2008 | | PASS |
Steven Webb
|
|
|
ESC plan approved with attached conditions.
|
Routing - PUBLIC WORKS | 12/21/2007 | | 1/2/2008 | | PASS |
Beverly Hall
|
|
|
|
Routing PW Drainage | 12/26/2007 | | 1/2/2008 | | PASS |
Brian Murphy
|
|
|
|
Plan resubmittals requested | | | 1/2/2008 | | DONE |
|
|
|
Faxed the architect a copy of the structural plan review requesting revisions. JCM
|
Routing Off Site - STRUCTURAL | 12/20/2007 | | 12/28/2007 | | FAIL |
|
|
|
Received comment list from consulting structural engineer requesting revisions. JCM
|
Routing PW Street Lights | 12/21/2007 | | 12/26/2007 | | PASS |
|
|
|
|
Routing PW Sewer Rating | 12/26/2007 | | 12/26/2007 | | PASS |
|
|
|
|
Routing PW Solid Waste | 12/26/2007 | | 12/26/2007 | | PASS |
|
|
|
|
Routing PW Environmental | 12/26/2007 | | 12/26/2007 | | PASS |
|
|
|
Proper management of dental office wastes required. Implement BMPs developed by Idaho State Dental Association. Call Boise Public Works ###-#### for more information. Silver & mercury amalgam recovery required.
|
Routing PW Sewer Design | 12/21/2007 | | 12/21/2007 | | PASS |
|
|
|
|
Routing - PLANNING Land Div | 12/20/2007 | | 12/21/2007 | | PASS |
|
|
|
Lifestyle sub
|
Telephone call | | | 12/20/2007 | | DONE |
|
|
|
called Action Courers for pick up
|
Application received | | | 12/20/2007 | | |
|
|
|
|
Pending Assignment by MYS | 12/20/2007 | | 12/20/2007 | | DONE |
|
|
|
12/20/2007 10:13:53 JCM - activity updated through activity BLDA166 from case BLD07-03229.
|
Plan routing begun/NEW & ADDTN | | | 12/20/2007 | | |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 12/20/2007 | | |
|
|
|
|