Third Notice BLD | 12/22/2008 | 12/22/2008 | 3/12/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
Second Notice has not been responded to.
|
Second Notice BLD | 9/22/2008 | 9/22/2008 | 12/22/2008 | | DONE |
Cathy Brown
|
|
|
First Notice has not been responded to.
|
First Notice | | 8/12/2008 | 9/22/2008 | | DONE |
|
|
|
|
Permanent Occupancy | | | 8/12/2008 | | DONE |
|
|
|
|
BLD-Final | 7/30/2008 | 7/31/2008 | 7/31/2008 | A | PASS |
Mike Jordan
|
|
|
zack Phone #: ###-####. All issues resolved. ok for perm occ. no card to sign.
|
BLD-Final | 5/30/2008 | 5/30/2008 | 5/30/2008 | P | PART |
Mike Jordan
|
|
|
Keith Phone #: ###-####. Temp occ. granted. Still needs to install grab bars and lower seat in ada shower.
|
BLD-Final | 5/29/2008 | 5/30/2008 | 5/30/2008 | A | FAIL |
Mike Jordan
|
|
|
Keith, please call 30 minutes prior; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt.. Needs to remove locking hardware at main enterance, not allowed on I4 occ.
|
Temporary Occupancy | 5/30/2008 | 8/28/2008 | 5/30/2008 | | DONE |
Cathy Weisshaupt
|
|
|
|
FIRE-Final Inspection | 5/28/2008 | 5/29/2008 | 5/29/2008 | P | PASS |
Troy Cobbley
|
|
|
Fire life safety completed. KR
|
FIRE-Alarm Testing | 5/28/2008 | 5/29/2008 | 5/29/2008 | P | PASS |
Troy Cobbley
|
|
|
Fire life safety completed. See fir08-00098 for alarm testing. KR
|
FIRE-Final Inspection | 5/27/2008 | 5/28/2008 | 5/28/2008 | A | FAIL |
Troy Cobbley
|
|
|
Life safety completed . Can not final until sprinkler flow switch is repaired. KR
|
BLD-Energy code compliance | 3/31/2008 | 3/31/2008 | 3/31/2008 | P | PASS |
Mike Jordan
|
|
|
keith Phone #: ###-####
|
BLD-Framing/Rough-in | 3/31/2008 | 3/31/2008 | 3/31/2008 | P | PASS |
Mike Jordan
|
|
|
keith Phone #: ###-####. All issues resolved. ok to insul.
|
BLD-Framing/Rough-in | 3/28/2008 | 3/28/2008 | 3/28/2008 | P | FAIL |
Mike Jordan
|
|
|
Keith; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
|
BLD-Framing/Rough-in | 3/25/2008 | 3/26/2008 | 3/26/2008 | A | FAIL |
Mike Jordan
|
|
|
keith Phone #: ###-####. Still needs plumbing and fire insp. No approved plans.
|
OVERRIDE | | | 3/20/2008 | | |
|
|
|
|
OVERRIDE | | | 3/20/2008 | | |
|
|
|
|
OVERRIDE | | | 3/20/2008 | | |
|
|
|
|
Telephone call | | | 3/20/2008 | | |
|
|
|
faxed copy of fees & called wes steele at ###-#### that permit is ready & need achd
|
Permit Ready to Issue | | | 3/20/2008 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 3/20/2008 | | DONE |
|
|
|
|
Plan assigned to (DRS) | 2/12/2008 | | 3/19/2008 | | PASS |
Dan Stuart
|
|
|
3/19/2008 11:47:36 DRS - activity updated through activity BLDA022 from case BLD08-00169.
|
Routing - PLUMBING | 3/18/2008 | | 3/19/2008 | | PASS |
Bill VanDegrift
|
|
|
verify thermol expantion protection sizing prior to final. provide a floor sink for the kitchen sink and dishwasher.
|
Routing - PLAN CHECK | 3/19/2008 | | 3/19/2008 | | PASS |
Dan Stuart
|
|
|
To permit desk to issue.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/19/2008 | | PASS |
|
|
|
|
Print Occupancy Form | | | 3/19/2008 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 3/7/2008 | | 3/18/2008 | | PEND |
Dan Stuart
|
|
|
Plans routing to plumbing for review.
|
Plan resubmittals received | | | 3/18/2008 | | DONE |
|
|
|
received 1 explanation sheet,1 letter,1 menu sheet,1 approval sheet from Central District Health, and 2 copies of sheets 1,3,5,SN sent to Dan S.
|
Routing - FIRE | 3/6/2008 | | 3/7/2008 | | PASS |
Scott Arellano
|
|
|
Attached IFC comments to plans
|
1st review completed | | | 3/7/2008 | | FAIL |
|
|
|
Failed Plan Check
|
Plan resubmittals requested | | | 3/6/2008 | | DONE |
|
|
|
Faxed copy to architect.
|
Routing - PLAN CHECK | 2/12/2008 | | 3/6/2008 | | FAIL |
Dan Stuart
|
|
|
Plan review faxed to Wes Steele with copy to Travis Burrows, Dave Evans Const. Routing to fire code analyst.
|
Routing - PLANNING | 2/12/2008 | | 2/12/2008 | | PASS |
Andrea Tuning
|
|
|
Andrea Tuning - Approved per DRH07-00412 & CAA07-00185 & CAR07-00066
|
Routing - PUBLIC WORKS | 2/12/2008 | | 2/12/2008 | | PASS |
Beverly Hall
|
|
|
|
Pending Assignment by MYS | 2/6/2008 | | 2/12/2008 | | DONE |
Marlene Southard
|
|
|
2/12/2008 10:32:49 MYS - activity updated through activity BLDA168 from case BLD08-00169.
|
Routing PW Sewer Rating | 2/12/2008 | | 2/12/2008 | | PASS |
Louise Waldorf
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 2/6/2008 | | |
|
|
|
got CDHD stamp/sign on plans
|
Recd Pcfee & Taken To Pln CK | | | 2/6/2008 | | DONE |
|
|
|
|
Application received | | | 1/29/2008 | | |
|
|
|
need CDHD sign/stamp prior to processing plans for review
|