BLD-Final | 4/14/2011 | 4/15/2011 | 4/15/2011 | A | PASS |
Tony Young
|
|
|
DAN Phone #: ###-####,, ok for occupancy,, pending any other trades
|
BLD-Final | 4/14/2011 | 4/14/2011 | 4/15/2011 | P | PASS |
Tony Young
|
|
|
DAN Phone #: ###-####
|
FIRE-Final Inspection | 4/14/2011 | 4/15/2011 | 4/15/2011 | A | PASS |
Troy Cobbley
|
|
|
life safety passed
|
Permanent Occupancy | | | 4/15/2011 | | DONE |
Tisha Gallop
|
|
|
|
BLD-Energy code compliance | 3/7/2011 | 3/8/2011 | 3/8/2011 | A | PASS |
Tony Young
|
|
|
David Phone #: ###-####,, ok now
|
BLD-Energy code compliance | 3/4/2011 | 3/7/2011 | 3/7/2011 | A | PART |
Tony Young
|
|
|
David Phone #: ###-####,, need sprinklers signed off,, then ok
|
BLD-Framing/Rough-in | 3/4/2011 | 3/7/2011 | 3/7/2011 | A | FAIL |
Tony Young
|
|
|
David Phone #: ###-####,, need sprinkler rough pass,, then ok
|
BLD-Wall cover | 1/20/2011 | 1/24/2011 | 1/24/2011 | P | PART |
Jim Sly
|
|
|
Dan Phone #: ###-#### Common rated walls Only.....OK
|
Telephone call | | | 1/18/2011 | | DONE |
Sam Zahorka
|
|
|
Received a telephone call from the contractor Dave Mckinnon requesting conformation on the compliance of the code year for Mechanical work. I assured him the permit is authorized to comply with the 2006 IBC and the 2003 IMC. He requested a letter stating this. I contacted the Structural Inspector Tony Young and then sent a letter as requested.
|
CHANGE STATUS TO (ISS) | | | 1/11/2011 | | DONE |
Tisha Gallop
|
|
|
paid for and picked up approved plan mod
|
Plan assigned to (SRZ) | 1/10/2011 | 1/10/2011 | 1/10/2011 | | PASS |
Sam Zahorka
|
|
|
|
Routing - PLAN CHECK | 1/10/2011 | | 1/10/2011 | | PASS |
Sam Zahorka
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/10/2011 | | DONE |
Sam Zahorka
|
|
|
|
Case Summary (BLD) | | | 1/10/2011 | | DONE |
Sam Zahorka
|
|
|
|
Permit Ready to Issue | | | 1/10/2011 | | DONE |
Tisha Gallop
|
|
|
|
Print Occupancy Form | | | 1/10/2011 | | DONE |
Tisha Gallop
|
|
|
|
Telephone call | | | 1/10/2011 | | DONE |
Tisha Gallop
|
|
|
called Dave McKinnon and told him permit is ready and fees.
|
Plan Modification Accepted | | | 1/7/2011 | | DONE |
Tisha Gallop
|
|
|
Plan Modification accepted for Bld08-00228 (live/work unit 29) to modify arrangement of interior non bearing walls; submitted on floorplan; routed to Sam Zahorka.
|
BLD-Framing/Rough-in | 1/5/2011 | 1/5/2011 | 1/5/2011 | P | NR |
Jim Storey
|
|
|
dan - partial cover Phone #: ###-####
|
BLD-Aging Inspection | 12/28/2010 | 12/28/2010 | 1/5/2011 | | PEND |
Tony Young
|
|
|
|
Print Occupancy Form | | | 12/29/2010 | | DONE |
Tisha Gallop
|
|
|
|
Case Summary (BLD) | | | 12/23/2010 | | DONE |
Sam Zahorka
|
|
|
|
Routing - PLAN CHECK | 12/23/2010 | | 12/23/2010 | | PASS |
Sam Zahorka
|
|
|
Plan modification approved.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/23/2010 | | DONE |
Sam Zahorka
|
|
|
|
Telephone call | | | 12/23/2010 | | DONE |
|
|
|
t/c w david - permit (plan mod) ready and fees given
|
Permit Ready to Issue | | | 12/23/2010 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 12/23/2010 | | DONE |
Christina Prado
|
|
|
|
(F) Reprint permit | | | 12/23/2010 | | DONE |
Christina Prado
|
|
|
|
Plan Modification Accepted | | | 12/20/2010 | | |
|
|
|
Plan modification excepted for the changes of a residential interior,reducing kitched area,making master suite bugger & turning axis on interior to make more living space. There will be no change in the certificate of value.
|
CHANGE STATUS TO (REV) | | | 12/20/2010 | | |
Barbara Stitt
|
|
|
|
BLD-Aging Inspection | 10/27/2010 | 10/27/2010 | 10/27/2010 | | PASS |
Tony Young
|
|
|
|
BLD-Aging Inspection | 8/26/2010 | 8/26/2010 | 8/27/2010 | | PEND |
Tony Young
|
|
|
|
BLD - Request for Extension | 6/21/2010 | 6/22/2010 | 6/22/2010 | A | PASS |
Tony Young
|
|
|
Dave- call prior to going Phone #: ###-####
|
BLD-Aging Inspection | 6/17/2010 | 6/17/2010 | 6/21/2010 | | PEND |
Tony Young
|
|
|
|
BLD-Aging Inspection | 4/15/2010 | 4/15/2010 | 4/19/2010 | | PEND |
Tony Young
|
|
|
|
BLD-Aging Inspection | 2/4/2010 | 2/9/2010 | 2/9/2010 | A | PASS |
Tony Young
|
|
|
ok to keep active
|
BLD-Framing/Rough-in | 5/22/2009 | 5/22/2009 | 5/22/2009 | P | PART |
Tony Young
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jessica Noland conf only
|
PubWorks Occupancy Approval | 5/22/2009 | 5/22/2009 | 5/22/2009 | | PASS |
Brian Murphy
|
|
|
ok for perm occupancy per BGM
|
BLD-Wall cover | 3/24/2009 | 3/25/2009 | 3/25/2009 | A | PART |
Mike Jordan
|
|
|
need ok to cover exterior (siding) Phone #: ###-#### Internet Inspection Request from: Jessica Noland. exteroir shear nailing ok.
|
BLD-Framing/Rough-in | 2/10/2009 | 2/11/2009 | 2/11/2009 | A | PART |
Tony Young
|
|
|
ben - ###-#### - party wall ok
|
Override - Parcel Holds | | | 2/10/2009 | | |
|
|
|
|
Override - Parcel Holds | | | 2/10/2009 | | |
|
|
|
|
Elevation Cert Rec'd-Final | | | 1/27/2009 | | DONE |
|
|
|
Received Elevation Certificate documenting compliance with Floodplain Ordinance. Okay to schedule framing inspection. Jim Wyllie / ###-####
|
BLD-Concrete | 10/9/2008 | 10/10/2008 | 10/10/2008 | A | PASS |
Tony Young
|
|
|
rebar inspection pouring concrete AM Phone #: ###-#### Internet Inspection Request from: Jessica Noland stem walls ok
|
BLD-Concrete | 9/26/2008 | 9/29/2008 | 9/29/2008 | P | PASS |
Tony Young
|
|
|
rebar inspection Phone #: ###-#### Internet Inspection Request from: Jessica Noland footings ok,, corners surveyed in
|
Override - Parcel Holds | | | 8/11/2008 | | |
|
|
|
|
Override - Parcel Holds | | | 8/11/2008 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 8/11/2008 | | DONE |
|
|
|
|
Telephone call | | | 8/8/2008 | | DONE |
|
|
|
left vm for curtis crystal at ###-#### - permit ready and fees given
|
Override - Parcel Holds | | | 8/8/2008 | | |
|
|
|
|
Override - Parcel Holds | | | 8/8/2008 | | |
|
|
|
|
Permit Ready to Issue | | | 8/8/2008 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 8/4/2008 | | 8/7/2008 | | PASS |
Sam Zahorka
|
|
|
|
Case Summary (BLD) | | | 8/7/2008 | | DONE |
Sam Zahorka
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/7/2008 | | DONE |
Sam Zahorka
|
|
|
|
Print Occupancy Form | | | 8/7/2008 | | DONE |
|
|
|
|
Plan assigned to (SRZ) | 4/24/2008 | | 8/7/2008 | | PASS |
Sam Zahorka
|
|
|
8/7/2008 11:46:33 SRZ - activity updated through activity BLDA022 from case BLD08-00228.
|
Route to Impact Fee Review | 8/4/2008 | 8/7/2008 | 8/4/2008 | | PASS |
Cindy M. Gould
|
|
|
Fees applied by LEG
|
Routing - FIRE | 8/4/2008 | 8/4/2008 | 8/4/2008 | | PASS |
Kenneth R Roule
|
|
|
See attached IFC fire plan review notes.
|
1st review completed | | | 8/4/2008 | | FAIL |
|
|
|
Public works, plan check and PW flood plain.
|
Routing - PLAN CHECK | 7/15/2008 | | 8/4/2008 | | FAIL |
Sam Zahorka
|
|
|
emailed correction to architect. Routed to Fire.
|
Plan resubmittals received | | | 8/4/2008 | | |
Sam Zahorka
|
|
|
Received transmittal, response letter and two copies of sheets A0.0, A0.1, A1.0, A1.1, A3.0, A3.1, A3.2, A5.0, A5.1, A5.2, A6.0, A6.1, A7.0, A7.2, A8.0, A8.1, A9.0, A10.0, S0.1, S4.01, S5.01, E2.1M; inserted by arch. rep. and taken back to Sam Zahorka
|
Case Summary (BLD) | | | 8/1/2008 | | DONE |
|
|
|
|
Plan resubmittals received | | | 7/15/2008 | | |
|
|
|
Received 6 copies of sheet A6.1 and inserted into plans by Modus Architects///7/15/08 @ 11:48am BAS
|
Routing - PUBLIC WORKS | 7/15/2008 | | 7/15/2008 | | PASS |
Louise Waldorf
|
|
|
|
Routing PW Flood Plain | 7/15/2008 | | 7/15/2008 | | PASS |
Jim Wyllie
|
|
|
|
Routing PW Flood Plain | 7/8/2008 | | 7/8/2008 | | FAIL |
Jim Wyllie
|
|
|
Show flood vents on building elevation. Jim Wyllie / ###-####
|
Routing PW Flood Plain | 6/19/2008 | | 6/23/2008 | | FAIL |
Jim Wyllie
|
|
|
Elevation Certificate shows attached garage below Base Flood Elevation without flood vents. Elevation Certificate needs to be modified to show placement of flood vents as per FEMA Technical Bulletin 1-93. Jim Wyllie / ###-####
|
Routing - PUBLIC WORKS | 6/19/2008 | | 6/23/2008 | | FAIL |
Louise Waldorf
|
|
|
Plans are so large that they are in office with Carl & Ben waiting re-submittals.
|
Routing - PLANNING | 6/19/2008 | | 6/19/2008 | | PASS |
Matthew A Halitsky
|
|
|
Routed to Public Works.
|
Plan resubmittals received | | | 6/12/2008 | | |
|
|
|
Received 6 copies of sheet A6.0 and A6.1 and taken to Matt Halitsky 6-12-08 @ 11:44am BAS
|
Plan resubmittals received | | | 6/9/2008 | | |
Tisha Gallop
|
|
|
Received two copies of sheet LS1.0; taken to Matt H. to insert into plans
|
Plan resubmittals received | | | 5/2/2008 | | |
Matthew A Halitsky
|
|
|
received "3" sets of plans with each sheet of A3.O, A3.1, A6.1, A1O.O--plans taken to Matt Halitsky
|
Pending Assignment by SRZ | 2/8/2008 | | 4/24/2008 | | DONE |
Marlene Southard
|
|
|
4/24/2008 11:15:26 MYS - activity updated through activity BLDA160 from case BLD08-00228.
|
Routing - PLANNING | 2/9/2008 | | 2/14/2008 | | FAIL |
Matthew A Halitsky
|
|
|
Drh 07-00466 Matt Halitsky; Cup07-00121 Susan Riggs
Conditions of DR approval not met. Email sent 2/13/2008.
Plans in my office.
|
Routing - Addressing | 2/8/2008 | | 2/8/2008 | | PASS |
Chris Pichardo
|
|
|
|
Application received | | | 2/8/2008 | | |
|
|
|
|