Permanent Occupancy | | | 8/25/2010 | | |
|
|
|
|
FIRE-Final Inspection | 8/28/2008 | 8/29/2008 | 8/29/2008 | A | PASS |
Troy Cobbley
|
|
|
Fire life safety completed. KR
|
BLD-Final | 8/29/2008 | 8/29/2008 | 8/29/2008 | P | PASS |
Jim Sly
|
|
|
Phone #: ###-#### OK for Perm Occ.
|
Temporary Occupancy UNPAID FEE | | | 8/29/2008 | | DONE |
Tisha Gallop
|
|
|
|
FIRE-Final Inspection | 8/25/2008 | 8/26/2008 | 8/26/2008 | A | CANC |
Troy Cobbley
|
|
|
Ken contacted Sergio and let him know that the fire life safety can not be completed until the project related FIR for the hood suppression system is completed and a FIR permit is aquired for the hood suppression interconnection with the existing facp.
|
BLD-Final | 8/25/2008 | 8/25/2008 | 8/25/2008 | A | CANC |
Jim Sly
|
|
|
|
FIRE-Final Inspection | 8/13/2008 | 8/14/2008 | 8/14/2008 | A | FAIL |
Troy Cobbley
|
|
|
Provide current certification for the hood suppression system ( currently the appliances will not fit under the hood and are too low), remove the dead bolt from the rear exit door and provide single action hardware as per the approved drawings, provide sprinkler protection in the areas where heads are missing and/or overspaced, replace the painted sprinkler heads, repair and test all exit signs and emergency lights and install additional signage as shown on drawing sheets A1.1 and E1, provide verification that the sprinkler system has had itsw annual inspection, provide fire extinguishers throughout the tenant as per the review comments, post the occupant load sign as per the review comments (193), remove dead bolts from the inactive leaf of the main exit/entrance door, provide verification that the hood suppression system is interconnected with the building fire alarm system.
|
(F) Reprint permit | | | 8/14/2008 | | |
|
|
|
|
Case Summary (BLD) | | | 8/14/2008 | | |
|
|
|
|
Meeting | | | 8/14/2008 | | DONE |
|
|
|
Walk-in meeting held with Reuben Pedraza, new tenant owner. Explained each of the fire inspection correction items to him, and how to go about resolving them. Also gave him an alternative design from Carl Westfall to install a keyed deadbolt at the base of each leaf of the double front doors, (inconjunction with the required signage for keyed locks, indicating both doors to remain unlocked when building is occupied), as an approved solution to the currently existing vertical deadbolts on the inactive leaf. I had to deny his request for a TOC while he got the sprinkler deficiencies corrected.
|
(F) Reprint permit | | | 5/28/2008 | | DONE |
|
|
|
|
BLD-Conference | 5/27/2008 | 5/27/2008 | 5/27/2008 | P | DONE |
Jim Sly
|
|
|
bill Phone #: ###-#### Met with Arch and owner.......Need all Req. permits....ie. Mech, Plumb, Electr...Obtain all Req. signatures for finals.
|
BLD-Conference | 5/23/2008 | 5/27/2008 | 5/27/2008 | A | CANC |
Jim Sly
|
|
|
bill - 10:30 at site Phone #: ###-####
|
Print Occupancy Form | | | 5/23/2008 | | DONE |
|
|
|
|
Print Occupancy Form | | | 4/22/2008 | | DONE |
|
|
|
|
Telephone call | | | 4/22/2008 | | DONE |
|
|
|
left vm for rocky towle at ###-#### - permit ready and fees given - also need gc name and rce#
|
Telephone call | | | 4/22/2008 | | DONE |
|
|
|
left message w chuck for ruben pedraza at ###-#### - left vm for rocky towle at ###-#### - permit ready and fees given - also need gc name and rce#
|
Permit Ready to Issue | | | 4/22/2008 | | DONE |
|
|
|
|
Issue PAID IN FULL permit | | | 4/22/2008 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 4/7/2008 | | 4/21/2008 | | PASS |
Carl Westfall
|
|
|
Drawings approved after the resubmittal review.
|
Plan assigned to (CJW) | 3/10/2008 | | 4/21/2008 | | PASS |
Carl Westfall
|
|
|
4/21/2008 16:14:11 CJW - activity updated through activity BLDA022 from case BLD08-00360.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/21/2008 | | DONE |
|
|
|
|
Plan resubmittals received | | | 4/17/2008 | | |
Carl Westfall
|
|
|
Recieved 1 response letter from Rocky Towle dated 4-14-08, A1.1, A2.0, A2.1 and taken to Carl Westfall's desk///4-17-08 @ 11:35am BAS
|
Plan resubmittals received | | | 4/11/2008 | | |
|
|
|
Received response letter and two copes of sheets COVER, A1.1, A2.0, A2.1, E1; taken to Carl Westfall
|
1st review completed | | | 4/7/2008 | | FAIL |
|
|
|
Failed Plan Check
|
Routing - FIRE | 4/2/2008 | | 4/7/2008 | | PASS |
Scott Arellano
|
|
|
Attached IFC comments to plans
|
Routing - PLAN CHECK | 3/18/2008 | | 4/2/2008 | | FAIL |
Carl Westfall
|
|
|
The IBC plan review was started on March 31, 2008 and was finished on April 2, 2008. Revised drawings were required. See the plan review report.
|
Routing - PLUMBING | 3/11/2008 | | 3/18/2008 | | PASS |
Bill VanDegrift
|
|
|
new fixtures and equipment on existing plumbing. backflow preventors with water discharge must be installed in an accessable location over a floor sink.
|
Routing - PUBLIC WORKS | 3/10/2008 | | 3/11/2008 | | PASS |
Beverly Hall
|
|
|
|
Routing PW Environmental | 3/11/2008 | | 3/11/2008 | | PASS |
Walt Baumgartner
|
|
|
existing grease trap from Asiago's operation.
|
Routing PW Sewer Rating | 3/11/2008 | | 3/11/2008 | | PASS |
Louise Waldorf
|
|
|
|
Pending Assignment by MYS | 2/28/2008 | | 3/10/2008 | | DONE |
Marlene Southard
|
|
|
3/10/2008 16:37:20 MYS - activity updated through activity BLDA172 from case BLD08-00360.
|
Application received | | | 2/28/2008 | | |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 2/28/2008 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 2/28/2008 | | DONE |
|
|
|
|