Case Summary (BLD) | | | 8/21/2008 | | |
|
|
|
|
Second Notice BLD | 4/23/2008 | 4/23/2008 | 4/25/2008 | | DONE |
Cathy Brown
|
|
|
First Notice has not been responded to.
|
First Notice | | 3/20/2008 | 4/23/2008 | | DONE |
|
|
|
|
BLD-Final | 3/19/2008 | 3/20/2008 | 3/20/2008 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Final | 3/18/2008 | 3/20/2008 | 3/20/2008 | A | PASS |
Tom Arcoraci
|
|
|
3:30 IF POSSIBLE--MARK-CALL 1ST BEFORE INSP Phone #: ###-####
|
FIRE-Final Inspection | 3/18/2008 | 3/19/2008 | 3/20/2008 | P | PASS |
Troy Cobbley
|
|
|
Life safety complete. KR
|
Permanent Occupancy | | | 3/20/2008 | | DONE |
|
|
|
|
BLD-Final | 3/6/2008 | 3/7/2008 | 3/7/2008 | P | NR |
Tom Arcoraci
|
|
|
Mark Phone #: ###-####
|
FIRE-Final Inspection | 3/6/2008 | 3/7/2008 | 3/7/2008 | A | FAIL |
Troy Cobbley
|
|
|
Repair the emergency light in the west outdoor area. Provide verification that the south exit doors exit sign has battery backup. The nozzles for the hood suppression system need to be aligned with the appliances. The correct nozzles need to be supplied for the appliances. The appliances need to be positioned no closer than 6" to the inside edge of the hood. These are problems at both hoods.
|
Issue PAID IN FULL permit | | | 3/6/2008 | | DONE |
|
|
|
|
Application received | | | 3/5/2008 | | |
|
|
|
|
Pending Assignment by MYS | 3/5/2008 | | 3/5/2008 | | DONE |
Ron Hill
|
|
|
3/5/2008 09:56:57 RMH - activity updated through activity BLDA175 from case BLD08-00396.
|
Plan assigned to (R_H) | 3/5/2008 | | 3/5/2008 | | PASS |
Ron Hill
|
|
|
3/5/2008 09:58:13 RMH - activity updated through activity BLDA022 from case BLD08-00396.
|
Routing - PLAN CHECK | 3/5/2008 | | 3/5/2008 | | PASS |
Ron Hill
|
|
|
|
Case Summary (BLD) | | | 3/5/2008 | | DONE |
|
|
|
|
1st review completed | | | 3/5/2008 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/5/2008 | | DONE |
|
|
|
|
Print Occupancy Form | | | 3/5/2008 | | DONE |
|
|
|
|
Telephone call | | | 3/5/2008 | | DONE |
|
|
|
tlk to mark casterson ###-#### that permit and fees are ready to be picked up 4:50 pm
|
Permit Ready to Issue | | | 3/5/2008 | | DONE |
|
|
|
|