Permit Information
Permit NumberBLD08-01275
StatusFinaled
Name FIRST SERVICE GROUP
Site Address 6205 W FRANKLIN RD
Project NameSTEPPING STONE SPA
Customer Number 
ePlanReviewNo
Description
Stepping Stone Spa - To construct a new 3,590 square foot, two story, wood framed beauty salon and spa and related site improvements. This building will contain a hair cutting salon, a manicure area and beauty and message treatment areas. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice 8/5/20099/15/2009 DONE
DetailsTisha Gallop
being processed by DLD
Second Notice 7/24/20098/5/2009 DONE
First Notice 4/23/20097/24/2009 DONE
Permanent Occupancy  4/23/2009 DONE
Zoning Approval4/7/20094/7/20094/7/2009 DONE
DetailsAndrea Tuning
BLD-Final3/13/20093/13/20093/13/2009PPASS
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 3/13/2009 at 7:47:23 AM. Contact: ###-####. ok for perm when others are perm
Temporary Occupancy3/13/20096/11/20093/13/2009 DONE
DetailsTisha Gallop
Zoning Approval3/10/20093/10/20093/13/2009 DONE
DetailsAndrea Tuning
The applicant has not completed the landscaping, has added a concrete walkway on the west side of the building, has added two second story windows on the south elevation and eliminated on parking space from the site.
The applicant has provided a $5,000 bond to cover the modifications that would be needed to obtain a building that matches the approved building. With the bond, staff has allowed the applicant to have temporary occupancy for the next 90 days. This will allow the applicant time to modify the site and the building to match the approved drawings or obtain a modification to teh DR application (DRH07-00486 and DRH08-00147). ANT
FIRE-Final Inspection3/12/20093/12/20093/12/2009PPASS
DetailsTroy Cobbley
life safety passed
BLD-Final3/12/20093/12/20093/12/2009PPART
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 3/12/2009 at 9:36:06 AM. Contact: ###-####. needs hand rails
PubWorks Occupancy Approval3/13/20093/13/20093/11/2009 DONE
BLD-Other3/10/20093/10/20093/10/2009PPASS
DetailsTom Arcoraci
Blake- ceiling Phone #: ###-####
FIRE-Final Inspection3/10/20093/10/20093/10/2009PFAIL
DetailsTroy Cobbley
Mount the fire extinguisher on the lower level as discussed and tag both extinguishers. Provide approved single action hardware on the secondary (west) exit door. Per April in addressing the 6205 address will suffice.
BLD-Other2/20/20092/20/20092/20/2009PNR
DetailsTom Arcoraci
BLD-Framing/Rough-in2/18/20092/19/20092/19/2009PPART
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 2/18/2009 at 3:27:35 PM. Contact: ###-####. needs elec
BLD-Aging Inspection2/2/20092/2/20092/2/2009 PASS
DetailsTom Arcoraci
BLD-Energy code compliance12/2/200812/3/200812/3/2008APASS
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 12/2/2008 at 4:05:02 PM. Contact: ###-####.
BLD-Other12/2/200812/2/200812/2/2008PPASS
DetailsTom Arcoraci
BLD-Framing/Rough-in12/1/200812/1/200812/1/2008PPASS
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 12/1/2008 at 10:16:53 AM. Contact: ###-####.
BLD-Conference11/14/200811/14/200811/14/2008PPASS
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 11/14/2008 at 9:59:09 AM. Contact: ###-####.
BLD-Framing/Rough-in11/5/200811/6/200811/6/2008APART
DetailsTom Arcoraci
Scheduled by a contractor via Hello! on 11/5/2008 at 1:42:03 PM. Contact: ###-####. ok to insulate floor with no plumb or elec
BLD-Framing/Rough-in11/4/200811/5/200811/5/2008APART
DetailsMike Jordan
Scheduled by a contractor via Hello! on 11/4/2008 at 1:21:46 PM. Contact: ###-####. Nailing for roof sheating only.
BLD-Conference10/14/200810/14/200810/14/2008PDONE
DetailsMike Jordan
Issue with north wall on vertical exit enclosure. Wood penetration into 1hr wall. Noted to contractor to have architect draw new detail for repair and submit to plan review for approval.
BLD-Footing9/30/200810/1/200810/1/2008APART
DetailsMike Jordan
blake - rebar Phone #: ###-####. Stemwalls. Special insp. on site.
BLD-Foundation9/25/20089/26/20089/26/2008PPART
DetailsMike Jordan
blake note:rebar Phone #: ###-####. Perimeter footings. Special insp. on site.
Override - People Holds  9/23/2008  
Issue PAID IN FULL permit  9/23/2008  
OVERRIDE  9/22/2008  
OVERRIDE  9/22/2008  
Print Occupancy Form  9/22/2008 DONE
Details
Telephone call  9/22/2008 DONE
Details
left vm for james murray at ###-#### - permit ready and fees given - also need ACHD receipt
Override - People Holds  9/22/2008  
Permit Ready to Issue  9/22/2008 DONE
Details
Plan resubmittals requested  9/19/2008 DONE
DetailsJohn Menard
E-mailed the architect a letter requesting additional structural revisions. JCM
Plan resubmittals received  9/19/2008 DONE
Received 1 response, 2 structural calcs, and 2 copies if sheet s2.1 inserted by Nate from CSHQA and plans returned to John M.
PLANS/APPL TAKEN TO FRONT DESK  9/19/2008 DONE
DetailsJohn Menard
Routing - PLAN CHECK9/12/2008 9/19/2008 PASS
DetailsJohn Menard
Plan assigned to (JCM)6/10/2008 9/19/2008 PASS
DetailsJohn Menard
9/19/2008 16:27:06 JCM - activity updated through activity BLDA022 from case BLD08-01275.
Plan resubmittals received  9/12/2008  
DetailsBarbara Stitt
Received 1 response letter dated 9-12-08 to John Menard from James Murray, and 2 copies of the following sheets-A2.1, A2.3, A10.1, S2.1, M0.2, M2.1, M4.1, M5.1, P2.1, P2.2, E1.0, E2.0 and inserted into plans then returned to John's desk///9-12-08 BAS
Routing PW Drainage9/12/2008 9/12/2008 PASS
DetailsBrian Murphy
Routing - PUBLIC WORKS9/5/2008 9/12/2008 PASS
DetailsBeverly Hall
Plan resubmittals requested  9/5/2008 DONE
DetailsJohn Menard
E-mailed the architect a copy of a letter requesting additional revisions. JCM
Routing - PLAN CHECK9/2/2008 9/5/2008 FAIL
DetailsJohn Menard
Routing - MECHANICAL8/25/2008 9/2/2008 PASS
DetailsTroy James





Plan resubmittals received  8/28/2008  
received letter of response from cshqa & "3" sets of structural calcs.(10 pages each) & "3" sets of plans with each sheet A2.1, A2.3, A6.1, A10.1, S1.1, S2.1, S3.1, M2.1, P2.1, & P2.2, --took plans to plumbing box & e-mailed troy james
Routing - PLUMBING8/20/2008 8/25/2008 PASS
DetailsBill VanDegrift
per plans and 2003 upc
Routing Off Site - STRUCTURAL8/19/2008 8/22/2008 PASS
DetailsJohn Menard
Received letter from consulting structural engineer approving the revised structural plans and calculations. JCM
Plan resubmittals received  8/20/2008  
DetailsJohn Menard
Received three copies of Structural Calculations; inserted into plans by LEG; taken back to John Menard
Plan resubmittals requested  8/20/2008 DONE
DetailsJohn Menard
E-mailed the architect requesting additional revisions. JCM
Routing - PLAN CHECK7/31/2008 8/20/2008 FAIL
DetailsJohn Menard
Plan resubmittals received  8/19/2008 DONE
received 1 response , 3 copies of sheets G0.1,A2.1,A2.3,A4.1,A6.1,A8.1,A10.1,S1.1,S2.1,S3.1,M0.1,M0.2,M2.1,M4.1,M5.1,MPS,P0.1,P2.1,P2.2,E1.0,E2.0 plans inserted by Ryan from CSHQA and plans taken back to John M.
Route to Impact Fee Review7/30/20088/4/20087/31/2008 PASS
DetailsCindy M. Gould
Routing - FIRE7/30/20087/30/20087/31/2008 PASS
DetailsScott Arellano
See IFC fire review comments attached.
1st review completed  7/31/2008 FAIL
Failed, PW, PW drainage,Plan check, off site structual, Mechanical and plan check.
Routing - PLAN CHECK6/30/2008 7/30/2008 FAIL
DetailsJohn Menard
Plan resubmittals requested  7/30/2008 DONE
DetailsJohn Menard
E-mailed the architect a copy of the plan review requesting revisions. JCM
Routing - MECHANICAL6/24/2008 6/30/2008 FAIL
DetailsTroy James
1. Boise City interpretation to the Ventilation requirements for nail salons per IMC Table 403.3, footnote b, states that there shall be no recirculation of air in the space. The intent of the IMC is that the exhaust system shall be at point of use. Please revise plans to show the exhaust system to manicure station. Diffuser at ceiling above does not meet intent of code.
2. Please show on plans revised ventilation calculations and make up air design.
3. Provide section view on plans of exhaust system at manicure station.
4. Please revise notes 10 and 13 sheet M2.1. State the fresh air shall be installed downstream of smoke detector. This is a common problem in the field. The contractor does not allow enough return duct plenum for this to be done correctly. Please show on detail sheet M5.1 the correct location of fresh air and smoke detector. Please note the smoke detectors are not required by code.

Routing - PLAN CHECK6/19/2008 6/24/2008  
DetailsJohn Menard
John Menard
6/24/08 Routed to Troy for mechanical review.
Routing - PLANNING6/19/2008 6/19/2008 PASS
DetailsAndrea Tuning
Approved per DRH08-00147. A copy of the license agrement from teh irrigation district has been included in the DR file. Andrea;

CUP07-00162 Diane P. A portion of the building encroaches into the irrigation easement. It appears that a lic. agreement was required prior to issuance of construction permits....please confirm before passing.

The required agreement was provided and placed in the CUP file prior to issuance. CER
Routing - PLUMBING6/18/2008 6/19/2008 FAIL
DetailsBill VanDegrift
provide fixture schedule, include all fixtures. show location of backflow preventers for the pedicure stations. show detail of waste connections for the pedicure and manicure stations. verify expansion tank sizing, st-5 is too small.
Routing - Erosion and Sediment6/13/2008 6/18/2008 PASS
DetailsClint A Smith
ESC plan approved with attached conditions. ESC08-00516
Plan resubmittals requested  6/18/2008 DONE
DetailsJohn Menard
E-mailed the architect a copy of structural comment list requesting revisions. JCM
Plan resubmittals received  6/17/2008  
DetailsBarbara Stitt
Received 1 cover transmittal, 2 O & m manuals, 2 copies of sheets C1.4 & C1.5 and inserted into plans by Jeff With CSHQA//taken back to ESC inbox/6-17-08 @ 9:39am BAS
Routing Off Site - STRUCTURAL6/10/2008 6/16/2008 FAIL
DetailsJohn Menard
Received comment list from consulting structural engineer requesting revisions. JCM
Routing - PUBLIC WORKS6/10/2008 6/13/2008 FAIL
DetailsLouise Waldorf
Routing PW Drainage6/11/2008 6/13/2008 FAIL
DetailsBrian Murphy
GRADING 2 FEET NEAR PROPERTY LINE, MONITORING WELL ON PLAN. BRIAN MURPHY ###-####
Routing PW Street Lights  6/13/2008 PASS
DetailsBill Colson
Routing PW Sewer Rating6/13/2008 6/13/2008 PASS
DetailsLouise Waldorf
Routing PW Solid Waste6/13/2008 6/13/2008 PASS
DetailsPeter J. McCullough
Pass with condition that no dumpsters are permitted on the property (only commercial and residential cans).
Peter McCullough, ###-####
Pending Assignment by MYS6/10/2008 6/10/2008 DONE
DetailsJohn Menard
6/10/2008 10:06:11 JCM - activity updated through activity BLDA166 from case BLD08-01275.
Routing - PLANNING Land Div6/10/2008 6/10/2008 PASS
DetailsJoan Johnson
Plans ACCEPTED BY PLAN TECH  6/10/2008 DONE
DetailsTisha Gallop
Recd Pcfee & Taken To Pln CK  6/10/2008 DONE
DetailsTisha Gallop
Plan routing begun/NEW & ADDTN  6/10/2008 DONE
DetailsTisha Gallop
Telephone call  6/10/2008 DONE
DetailsTisha Gallop
called Action Couriers for pick up
Routing - Addressing6/10/2008 6/10/2008 PASS
DetailsApril Wing
Application received 6/10/2008   
DetailsTisha Gallop