Permit Information
Permit NumberBLD08-01426
StatusFinaled
Name HCD INC
Site Address 6886 W STATE STREET
Project NameRadiant Nails
Customer Number 
ePlanReviewNo
Description
**Radiant Nails** To remodel an existing 1229 sq ft tenant space for new salon. Work to include, installation of new HVAC system, new plumbing installations and miscellaneous related interior improvements. This building is NOT fire sprinklered. Refer to BLD98-02117 for original shell building permit. RMH
Contact Information
See Activities list for contact information
Color Key
Current location of plans being reviewed:  
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice 2/28/20103/4/2010 DONE
Second Notice 2/20/20102/23/2010 DONE
First Notice 2/7/20102/10/2010 DONE
Permanent Occupancy  1/28/2010 DONE
DetailsTisha Gallop
BLD-Final1/27/20101/27/20101/27/2010APASS
DetailsTony Young
Kim Phone #: ###-####
ok for perm c of o
BLD-Final1/21/20101/25/20101/27/2010PPART
DetailsTony Young
Kim Phone #: ###-####
need f/l/s
FIRE-Final Inspection1/21/20101/25/20101/25/2010APASS
DetailsTroy Cobbley
Life safety passed.
BLD-Final1/15/20101/19/20101/22/2010PNR
DetailsTony Young
Kim Phone #: ###-####
FIRE-Final Inspection1/22/20101/22/20101/22/2010PCANC
DetailsTroy Cobbley
kim phone ###-####. Not ready for inspection. Has been rescheduled for Monday.
FIRE-Final Inspection1/15/20101/19/20101/19/2010AFAIL
DetailsTroy Cobbley
Repair the exit sign located over the main exit. Provide exit discharge lighting as shown on the approved plans at both the front and rear exits. I tried to verify the exit discharge requirement since the occupant load was only 12 but Ron Hill was unavailable so I contacted DC Engineering and spoke to Johnathan. He stated that he thought the exit discharge lighting was required.
BLD-Conference12/23/200912/31/20091/6/2010APEND
DetailsTony Young
status check,, still needs mech permit,, 411 is on top of this
BLD-Conference12/15/200912/23/200912/23/2009AFAIL
DetailsTony Young
check status,, still need mechanical permit
called 411,, she is on top of it
BLD-Conference12/2/200912/15/200912/15/2009APEND
DetailsTony Young
check on status
progress being made
BLD-Conference11/24/200911/27/200912/2/2009PPART
DetailsTony Young
check on status
wip on getting permits/ inspections
BLD-Conference11/24/200911/24/200911/24/2009PFAIL
DetailsTony Young
met w/ 411,, there has been mechanical and plumbing done w/out permits,, t/w landlord,, she said she would get things in order
BLD-Conference11/16/200911/16/200911/16/2009PPART
DetailsTony Young
on site conf w/ tenant,, called landlord, Christy,, ###-####, she will call for inspections
BLD-Aging Inspection3/9/20093/9/20093/10/2009 PEND
DetailsTony Young
BLD-Aging Inspection12/10/200812/10/200812/10/2008 PEND
DetailsTony Young
Issue PAID IN FULL permit  9/10/2008  
Plan assigned to (R_H)6/27/2008 8/20/2008 PASS
DetailsRon Hill
8/20/2008 07:30:37 RMH - activity updated through activity BLDA022 from case BLD08-01426.
Routing - PLAN CHECK8/19/2008 8/20/2008 PASS
DetailsRon Hill
1st review completed  8/20/2008 DONE
PLANS/APPL TAKEN TO FRONT DESK  8/20/2008 DONE
Print Occupancy Form  8/20/2008 DONE
Details
Telephone call  8/20/2008 DONE
Details
t/c w billy strite at ###-#### - permit ready and fees given - also need gc name and rce#
Permit Ready to Issue  8/20/2008 DONE
Details
Routing - PLAN CHECK8/18/2008 8/19/2008 PASS
DetailsRon Hill
Routed to fire......
Routing - FIRE8/19/2008 8/19/2008 PASS
DetailsKenneth R Roule
See attached IFC fire plan review notes.
1st review completed  8/19/2008 FAIL
Failed Mechanical, Plumbing and Plan check
Case Summary (BLD)  8/18/2008 DONE
Routing - PUBLIC WORKS8/18/2008 8/18/2008 PASS
DetailsConnie Baumgartner
Routing PW Sewer Rating8/18/2008 8/18/2008 PASS
DetailsConnie Baumgartner
Routing - PLAN CHECK7/3/2008 8/18/2008 PASS
DetailsRon Hill
Plan resubmittals received  8/8/2008  
DetailsRon Hill
received transmittal, response letter, and two copies of sheets A1.1, M1.0, P1.0; taken to Ron Hill
Routing - PLAN CHECK7/31/2008 8/4/2008 FAIL
DetailsRon Hill
Faxed requirements to the architect... needed service sink and drinking fountain.
Routing - MECHANICAL7/24/2008 7/31/2008 PASS
DetailsTroy James
Routing - PLUMBING7/28/2008 7/28/2008 PASS
DetailsBill VanDegrift
per resubmitted plans dated 7/23/08 and 2003 upc
Plan resubmittals received  7/24/2008 DONE
DetailsRon Hill
Received transmittal, response letter, and three copes of sheets E0.0, E0.1, E1.0, E1.1, E2.0, M0.0, M0.1, M1.0, P0.0, P1.0; taken to Ron Hill
Routing - PLUMBING6/27/2008 7/2/2008 FAIL
DetailsBill VanDegrift
pumped discharge from pedicure chairs must discharge to a floor sink. floor sink must not be in the toilet room. S-1 waste must be piped to the sanitary sewer by gravity or discharge to the required floor sink. can not tie to the pumped discharge. install BFP-1 and 2 over required floor sink.
Routing - PUBLIC WORKS6/27/2008 6/27/2008 PASS
DetailsBeverly Hall
Routing PW Sewer Rating6/27/2008 6/27/2008 PASS
DetailsLouise Waldorf
Application received 6/26/2008   
Routing - MECHANICAL7/2/2008   FAIL
1. Ventilation requirements for nail salons per IMC Table 403.3, footnote b, states that there shall be no recirculation of air in the space. The intent of the IMC is that the exhaust system shall be at point of service. Please revise plans to show the exhaust system design to each manicure station.
2. Please show on plans, exhaust to exterior per chapter 5 IMC, for product conveying exhaust systems termination requirements.
3. Please show on plans ventilation calculations and make up air design for the exhaust system at manicure stations.
4. Provide section view on plans of exhaust system design at manicure stations.
5. Show on plans ventilation requirements per Table 403.3 for outside air design of 25 cfm per person.