Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberBLD08-01553
StatusFinaled
Name KELLEE SHARPLES
Site Address 413 S 8TH ST
Project Name 
Customer Number 
ePlanReviewNo
Description
**(Buns in the Oven)** Application for inspection to determine requirements for issuance of a Certificate of Occpancy for a 815 sq ft retail sales tenant space. NO NEW WORK IS AUTHORIZED UNDER THIS PERMIT. This tenant space was formerly occupied by "Drop a Stitch, LLC" there is not any information on this tenant space. Rmh
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Print Occupancy Form  7/29/2010 DONE
Permanent Occupancy  7/29/2010 DONE
DetailsTisha Gallop
First Notice 4/30/20104/20/2010 DONE
Permanent Occupancy  4/20/2010 DONE
DetailsBarbara Stitt
FIRE-Final Inspection3/26/20103/26/20103/26/2010APASS
DetailsForrest France
Correction item site verified for completion, fire life safety finaled. Notified structural inspector of project status change.
BLD-Final3/26/20103/26/20103/26/2010PPASS
DetailsDave Hannah
ok for perm occ
BLD-Final8/5/20088/6/20088/6/2008PPART
DetailsDave Hannah
kelly Phone #: ###-#### ok for temp occ ok for perm occ after fire gos perm
FIRE-Final Inspection8/5/20088/6/20088/6/2008APART
DetailsForrest France
Temporary occupancy approval okayed, final pending removal of the remainder of ceiling tiles above the stairs.
BLD-Final7/31/20088/1/20088/1/2008PFAIL
DetailsJim Storey
kelly Phone #: ###-#### remove ceilling tile over stairs to expose sidewall head.
FIRE-Final Inspection7/31/20088/1/20088/1/2008AFAIL
DetailsForrest France
Lacking fire sprinkler coverage at the stairway area between the upper and lower levels-sprinkler head is missing or has been obstructed by the drop ceiling. See item number 8 under general requirements listed on the permit notes regarding fire sprinklers. Notified the tenant that any modifications necessary must be performed by a licensed fire sprinkler contractor with a project related fire permit.
Meeting  8/1/2008 DONE
Special site visit by S.Rogers. Sufficient ceiling tiles have been removed for adequate coverage of the bulk sprinkler piping feeding the basement, by the sidewall head above the suspended ceiling level. A sprinkler permit application was received this afternoon; not reviewed. Approval was granted for temp occy without issued paper work, other than a notation on the permit card, per agreement by D. Hanneman and B Chatterton. For final approval, the two painted heads within the tenant space are to be replaced and all ceiling tiles over the stairs permanently removed or an additional sprinkler head extended to protect below the suspended ceiling, and final inspection approval by Fire of the sprinkler permit and building permit and final signoff by Building inspector.
Issue PAID IN FULL permit  7/18/2008 DONE
DetailsTisha Gallop
Plan assigned to (R_H)7/17/2008 7/17/2008 PASS
DetailsRon Hill
7/17/2008 09:54:23 RMH - activity updated through activity BLDA022 from case BLD08-01553.
Case Summary (BLD)  7/17/2008 DONE
1st review completed  7/17/2008 DONE
PLANS/APPL TAKEN TO FRONT DESK  7/17/2008 DONE
Print Occupancy Form  7/17/2008 DONE
DetailsCathy Brown
Telephone call  7/17/2008 DONE
DetailsCathy Brown
lft vm for kellee sharples ###-#### that permt is ready to be picked up
Permit Ready to Issue  7/17/2008 DONE
DetailsCathy Brown
Application received 7/16/20087/16/2008 DONE
DetailsDarla L Downs