Second Notice BLD | 11/7/2008 | 11/7/2008 | 11/25/2008 | | DONE |
Cathy Brown
|
|
|
First Notice has not been responded to.
|
First Notice | | 10/16/2008 | 11/7/2008 | | DONE |
|
|
|
|
Permanent Occupancy | | | 10/16/2008 | | DONE |
Tisha Gallop
|
|
|
|
BLD-Final | 10/6/2008 | 10/7/2008 | 10/7/2008 | P | PASS |
Jim Sly
|
|
|
troy Phone #: ###-#### OK for Perm Occ.
|
FIRE-Final Inspection | 10/6/2008 | 10/7/2008 | 10/7/2008 | A | PASS |
Troy Cobbley
|
|
|
Corrections made per Troys last inspection.KR
|
BLD-Final | 10/6/2008 | 10/7/2008 | 10/6/2008 | A | CANC |
Jim Sly
|
|
|
troy Phone #: ###-#### Inspection cancelled from web by: Patricia Smith
|
FIRE-Final Inspection | 10/6/2008 | 10/6/2008 | 10/6/2008 | P | FAIL |
Troy Cobbley
|
|
|
Provide approved single action hardware on all of the office doors. Provide a racking permit for the racks over 8' or reduce the height of the racks as discussed. Move the stored items on the floor from infront of the exit doors.
|
BLD-Final | 10/3/2008 | 10/6/2008 | 10/6/2008 | A | NR |
Jim Sly
|
|
|
TROY NOTE: 1813 N WILDWOOD Phone #: ###-#### Need fire final
|
BLD-Framing/Rough-in | 9/18/2008 | 9/19/2008 | 9/19/2008 | A | PASS |
Jim Sly
|
|
|
troy - please call 1 hr prior so he can meet you there - will be coming from middleton Phone #: ###-####
|
Issue PAID IN FULL permit | | | 9/17/2008 | | DONE |
|
|
|
|
Plan assigned to (R_H) | 9/4/2008 | 9/4/2008 | 9/15/2008 | | PASS |
Ron Hill
|
|
|
9/15/2008 12:46:02 RMH - activity updated through activity BLDA022 from case BLD08-01910.
|
Routing - PLAN CHECK | 9/5/2008 | | 9/15/2008 | | PASS |
Ron Hill
|
|
|
|
Case Summary (BLD) | | | 9/15/2008 | | DONE |
|
|
|
|
Routing - FIRE | | | 9/15/2008 | | PASS |
|
|
|
|
1st review completed | | | 9/15/2008 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/15/2008 | | DONE |
|
|
|
|
Print Occupancy Form | | | 9/15/2008 | | DONE |
|
|
|
|
Telephone call | | | 9/15/2008 | | DONE |
|
|
|
left vm for elizabeth cooper - permit ready and fees given - also need gc name and rce#
|
Permit Ready to Issue | | | 9/15/2008 | | DONE |
|
|
|
|
Application received | | 9/4/2008 | 9/5/2008 | | DONE |
Barbara Stitt
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 9/4/2008 | | DONE |
Alexandra L. DeYoung
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 9/4/2008 | | DONE |
Alexandra L. DeYoung
|
|
|
|