Second Notice | | 7/24/2009 | 8/6/2009 | | DONE |
|
|
|
|
Second Notice | | 7/22/2009 | 8/6/2009 | | DONE |
|
|
|
|
First Notice | | 6/29/2009 | 7/24/2009 | | DONE |
|
|
|
sent by mail
|
First Notice | | 6/29/2009 | 7/22/2009 | | DONE |
|
|
|
|
Permanent Occupancy | | | 6/29/2009 | | DONE |
|
|
|
|
Permanent Occupancy | | | 6/29/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
|
PubWorks Occupancy Approval | 6/23/2009 | 6/23/2009 | 6/23/2009 | | DONE |
Terry Records
|
|
|
Final grading and drainage complete and approved
|
Zoning Approval | 6/19/2009 | 6/22/2009 | 6/22/2009 | | PASS |
Josh Wilson
|
|
|
|
BLD-Final | 6/1/2009 | 6/2/2009 | 6/2/2009 | P | PART |
Mike Jordan
|
|
|
christine Phone #: ###-####. ok for temp occ. Needs to install remaing glazing in doors, provide hc signs and complete firecaulking in riser room.
|
FIRE-Final Inspection | 6/1/2009 | 6/2/2009 | 6/2/2009 | A | PASS |
Troy Cobbley
|
|
|
Life Safety Passed
|
Temporary Occupancy | 6/2/2009 | 8/31/2009 | 6/2/2009 | | DONE |
Tisha Gallop
|
|
|
|
FIRE-Final Inspection | 6/1/2009 | 6/1/2009 | 6/1/2009 | P | FAIL |
Troy Cobbley
|
|
|
The northwest exit discharge light failed to operate.
|
Zoning Approval Temp | 5/28/2009 | 5/28/2009 | 5/28/2009 | | PASS |
Josh Wilson
|
|
|
Temp occ while Building B and remaining site improvements are completed.
|
BLD-Other | 5/20/2009 | 5/21/2009 | 5/21/2009 | A | PASS |
Mike Jordan
|
|
|
Christine- grid Phone #: ###-####. Grid ok.
|
BLD-Other | 5/19/2009 | 5/20/2009 | 5/20/2009 | P | FAIL |
Mike Jordan
|
|
|
Christine- grid Phone #: ###-####. Installed grid not per approved plan.
|
BLD-Framing/Rough-in | 4/24/2009 | 4/24/2009 | 4/24/2009 | P | PASS |
Mike Jordan
|
|
|
christine Phone #: ###-####. All issues resolved. Received engineering noting that 2x6 with double top plate is adequate for piont loads. Will have scanned into permit.
|
BLD-Energy code compliance | 4/24/2009 | 4/24/2009 | 4/24/2009 | P | PASS |
Mike Jordan
|
|
|
christine Phone #: ###-####
|
BLD-Framing/Rough-in | 4/22/2009 | 4/23/2009 | 4/23/2009 | A | PART |
Mike Jordan
|
|
|
christine Phone #: ###-####. Needs to add lateral bracing on bottom chords, provide letter from engineer regarding point loads on 2x6 walls. Also needs to provide tbh on truss eg1 and 2.
|
BLD-Framing/Rough-in | 4/22/2009 | 4/22/2009 | 4/22/2009 | P | PART |
Mike Jordan
|
|
|
christine Phone #: ###-####. ok to insul. exterior walls and one side only. Needs to provide new truss engineering and sprinkler ri insp.
|
BLD-Framing/Rough-in | 3/26/2009 | 3/26/2009 | 3/26/2009 | P | PART |
Mike Jordan
|
|
|
roof inspection-christine Phone #: ###-####. Nailing on roof diaphragm ok. Also gave contractor c/n noting to resubmit mezzanine drawings and all applicable engineering showing bonus truss in leiu of TJI and additional square footage added.
|
BLD-Framing/Rough-in | 3/20/2009 | 3/23/2009 | 3/23/2009 | A | PART |
Mike Jordan
|
|
|
building a only please--shear nail christine Phone #: ###-####. Shear nailing on exterior walls only. ok.
|
FIRE-Conference | 3/17/2009 | 3/17/2009 | 3/17/2009 | P | DONE |
Troy Cobbley
|
|
|
I spoke to Brian Johnson with Shilo Automatic Sprinkler about the sizing of the piping from the FDC to the floating main. I gave my interpretation of NFPA 13-8.17.2 but defered him to Tim Frost. The entry is being made under this permit due to the overhead sprinkler permit not being issued at this time.
|
BLD-Foundation | 3/3/2009 | 3/4/2009 | 3/4/2009 | A | PASS |
Mike Jordan
|
|
|
Ian Phone #: ###-####. Stemwall for dumpster enclosure ok.
|
BLD-Foundation | 3/2/2009 | 3/3/2009 | 3/3/2009 | A | PASS |
Mike Jordan
|
|
|
ian Phone #: ###-####. Perimeter stemwalls and column pad pdestals. ok.
|
BLD-Footing | 2/27/2009 | 2/27/2009 | 2/27/2009 | P | PASS |
Mike Jordan
|
|
|
Ian Phone #: ###-####. Perimeter footings and column pad footings ok.
|
BLD-Footing | 2/27/2009 | 2/27/2009 | 2/27/2009 | P | CANC |
Mike Jordan
|
|
|
ian Phone #: ###-####
|
BLD-Footing | 2/25/2009 | 2/26/2009 | 2/26/2009 | P | NR |
Mike Jordan
|
|
|
ian Phone #: ###-####. Contractor will reschedule insp.
|
Issue PAID IN FULL permit | | | 2/24/2009 | | DONE |
|
|
|
|
Telephone call | | | 2/18/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
LM for chad with Dave- permit ready, fees given, also need ACHD and RP
|
Permit Ready to Issue | | | 2/18/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
|
Plan assigned to (JCM) | 11/12/2008 | | 2/17/2009 | | PASS |
John Menard
|
|
|
2/17/2009 15:07:54 JCM - activity updated through activity BLDA022 from case BLD08-02393.
|
Routing - PLAN CHECK | 1/30/2009 | | 2/17/2009 | | PASS |
John Menard
|
|
|
|
Plan resubmittals received | | | 2/17/2009 | | |
John Menard
|
|
|
Received transmittal and two copies of pages A2.1, A2.3; inserted by Architect and taken back to John Menard
|
Plan Reviewer's activity | | | 2/17/2009 | | PASS |
John Menard
|
|
|
Reviewed and approved final revised plans with red lined notes and attached plan review clarification notes. JCM
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/17/2009 | | DONE |
John Menard
|
|
|
|
Print Occupancy Form | | | 2/17/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
|
Routing - FIRE | 1/29/2009 | | 1/30/2009 | | PASS |
Scott Arellano
|
|
|
Attached updated IFC comments to plans.
|
Plan resubmittals requested | | | 1/29/2009 | | DONE |
John Menard
|
|
|
E-mailed the architect requesting additional revisions. JCM
|
Plan Reviewer's activity | | | 1/29/2009 | | PASS |
John Menard
|
|
|
Reviewed and approved structural revisions. JCM
|
Plan resubmittals received | | | 1/28/2009 | | |
John Menard
|
|
|
Rec'd four copies of sheets- S0.1, S1.1, S3.1, S5.1, FP1.0, A2.1, A2.3, & A9.1 and four copies of structural calcs- inserted by architect- taken to John M
|
Routing - PLUMBING | 12/12/2008 | | 12/12/2008 | | PASS |
Bill VanDegrift
|
|
|
per plans and 2003 upc
|
Routing - PUBLIC WORKS | 12/10/2008 | | 12/12/2008 | | PASS |
Beverly Hall
|
|
|
|
Routing PW Sewer Design | 11/14/2008 | | 12/11/2008 | | PASS |
Jon R. Gunnerson
|
|
|
Connect onto existing 6-inch service provided.
|
Routing PW Drainage | 12/10/2008 | | 12/10/2008 | | PASS |
Terry Records
|
|
|
|
Routing - PLAN CHECK | 12/8/2008 | | 12/10/2008 | | |
|
|
|
|
Routing - FIRE | 12/3/2008 | 12/3/2008 | 12/8/2008 | | FAIL |
Scott Arellano
|
|
|
Faxed and emailed resubmittal items to architect.
|
1st review completed | | | 12/8/2008 | | FAIL |
|
|
|
Failed PW, Plan Check, Fire
|
Plan resubmittals received | | | 12/4/2008 | | |
Barbara Stitt
|
|
|
Received 9 sets of sheets C2, C3, C4, C5, C6 were inserted into plans BLD08-02293, and BLD08-02295 and sheets C2 & C3 into BLD08-02292 by architects office and returned to desks taken from 12-4-08 BAS
|
Route to Impact Fee Review | 12/3/2008 | 12/8/2008 | 12/3/2008 | | PASS |
Cindy M. Gould
|
|
|
|
Routing - PLAN CHECK | 12/3/2008 | | 12/3/2008 | | FAIL |
John Menard
|
|
|
|
Routing - PLANNING | 11/20/2008 | | 12/3/2008 | | PASS |
Sue Cummings
|
|
|
CAR07-00070 & CUP07-00177
|
Plan resubmittals requested | | | 12/2/2008 | | DONE |
John Menard
|
|
|
E-mailed the architect a copy of the plan review requesting revisions. JCM
|
Plan resubmittals requested | | | 11/25/2008 | | DONE |
John Menard
|
|
|
E-mailed the architect a copy of the structural plan review comment requesting revisions. JCM
|
Routing Off Site - STRUCTURAL | 11/12/2008 | | 11/25/2008 | | FAIL |
John Menard
|
|
|
Called Action Couriers for pick up -Received comment list from consulting structural engineer requesting revisions. JCM
|
Routing - PLANNING | 11/20/2008 | | 11/20/2008 | | PASS |
Josh Wilson
|
|
|
DRH07-00597-Josh Wilson PASS
CUP07-00177- Sue Cummings
|
Routing - PLUMBING | 11/18/2008 | | 11/20/2008 | | FAIL |
Bill VanDegrift
|
|
|
need to pass sewer design prior to plumbing review acceptance.
|
Routing - Erosion and Sediment | 11/17/2008 | | 11/18/2008 | | PASS |
Steven Webb
|
|
|
ESC plan approved with attached conditions. ESC08-00979
|
Routing PW Solid Waste | 11/17/2008 | | 11/17/2008 | | PASS |
Peter J. McCullough
|
|
|
|
Routing PW Drainage | 11/17/2008 | | 11/17/2008 | | FAIL |
Brian Murphy
|
|
|
grading plan failed
|
Routing PW Street Lights | | | 11/17/2008 | | PASS |
Hank Alarcon
|
|
|
|
Routing - PUBLIC WORKS | 11/14/2008 | | 11/17/2008 | | FAIL |
Louise Waldorf
|
|
|
Refer to Sewer Design - Jon Gunnerson and Drainage - Terry Records.
|
Routing - PLANNING Land Div | 11/12/2008 | | 11/14/2008 | | PASS |
Todd Tucker
|
|
|
property has not changed since it was annexed into the city.
|
Routing PW Sewer Rating | 11/14/2008 | | 11/14/2008 | | PASS |
Connie Baumgartner
|
|
|
|
Application received | | 11/10/2008 | 11/12/2008 | | DONE |
Barbara Stitt
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 11/12/2008 | | DONE |
Barbara Stitt
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 11/12/2008 | | DONE |
Barbara Stitt
|
|
|
|
Routing PW Sewer Design | 12/10/2008 | | | | |
Jon R. Gunnerson
|
|
|
|
Routing - PLAN CHECK | 12/12/2008 | | | | |
|
|
|
|