Second Notice | | 7/24/2009 | 8/6/2009 | | DONE |
|
|
|
|
Second Notice | | 7/22/2009 | 8/6/2009 | | DONE |
|
|
|
|
First Notice | | 6/29/2009 | 7/22/2009 | | DONE |
|
|
|
sent by mail
|
BLD-Final | 6/29/2009 | 6/29/2009 | 6/29/2009 | P | CANC |
Mike Jordan
|
|
|
christine Phone #: ###-####. ok for perm occ.
|
FIRE-Final Inspection | 6/29/2009 | 6/29/2009 | 6/29/2009 | P | PASS |
Troy Cobbley
|
|
|
Life safety passed.
|
Permanent Occupancy | | | 6/29/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
|
Permanent Occupancy | | | 6/29/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
|
FIRE-Final Inspection | 6/25/2009 | 6/26/2009 | 6/26/2009 | P | FAIL |
Troy Cobbley
|
|
|
The project related fire alarm and fire sprinkler permits need finaled and two exit discharge lights on the east side did not work.
|
PubWorks Occupancy Approval | 6/23/2009 | 6/23/2009 | 6/23/2009 | | DONE |
Terry Records
|
|
|
Final grading and drainage approved.
|
Zoning Approval | 6/19/2009 | 6/22/2009 | 6/22/2009 | | PASS |
Josh Wilson
|
|
|
|
BLD-Framing/Rough-in | 6/9/2009 | 6/10/2009 | 6/10/2009 | A | PASS |
Mike Jordan
|
|
|
christine - ceiling grid Phone #: ###-####
|
BLD-Other | 5/15/2009 | 5/15/2009 | 5/15/2009 | P | PASS |
Mike Jordan
|
|
|
Chistine Phone #: ###-####. 1hr. const. for fire riser room.
|
BLD-Other | 5/13/2009 | 5/14/2009 | 5/14/2009 | A | CANC |
Mike Jordan
|
|
|
christine - 1 hr construction on a fire riser Phone #: ###-####
|
BLD-Energy code compliance | 5/11/2009 | 5/11/2009 | 5/11/2009 | P | PASS |
Mike Jordan
|
|
|
Christine Phone #: ###-####
|
BLD-Final | 5/7/2009 | 5/8/2009 | 5/8/2009 | A | CANC |
Mike Jordan
|
|
|
christine Phone #: ###-####
|
BLD-Framing/Rough-in | 5/8/2009 | 5/8/2009 | 5/8/2009 | A | PASS |
Mike Jordan
|
|
|
christine Phone #: ###-####
|
BLD-Framing/Rough-in | 4/28/2009 | 4/29/2009 | 4/29/2009 | A | NR |
Mike Jordan
|
|
|
Christine Phone #: ###-####. Needs ri. imsp. from other trades first.
|
BLD-Other | 3/31/2009 | 4/1/2009 | 4/1/2009 | A | PART |
Mike Jordan
|
|
|
Christine- roof nailing Phone #: ###-####. Nailing for roof ok.
|
BLD-Framing/Rough-in | 3/26/2009 | 3/26/2009 | 3/26/2009 | P | PART |
Mike Jordan
|
|
|
Shear Inspection -christine Phone #: ###-####. Exterior shear nailing only, ok. Also gave contactor c/n noting to resubmit mezzanine drawing and all applicable engineering showing use of bonus trusses in leiu of TJI and additional square footage.
|
BLD-Foundation | 3/2/2009 | 3/3/2009 | 3/3/2009 | A | PASS |
Mike Jordan
|
|
|
ian Phone #: ###-####. Perimeter stemwalls and pedestals on column pad footings. ok.
|
BLD-Footing | 3/2/2009 | 3/2/2009 | 3/2/2009 | P | PASS |
Mike Jordan
|
|
|
Ian Phone #: ###-####. Exterior column pad footings.
|
BLD-Footing | 2/25/2009 | 2/26/2009 | 2/26/2009 | P | PASS |
Mike Jordan
|
|
|
ian Phone #: ###-####. Perimeter footings ok.
|
Issue PAID IN FULL permit | | | 2/24/2009 | | DONE |
|
|
|
|
Telephone call | | | 2/18/2009 | | |
Alexandra L. DeYoung
|
|
|
LM for chad with Dave- permit ready, fees given, also need ACHD and RP
|
Permit Ready to Issue | | | 2/18/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
|
Plan assigned to (JCM) | 11/12/2008 | | 2/17/2009 | | PASS |
John Menard
|
|
|
2/17/2009 15:08:42 JCM - activity updated through activity BLDA022 from case BLD08-02395.
|
Routing - PLAN CHECK | 12/12/2008 | | 2/17/2009 | | PASS |
John Menard
|
|
|
|
Plan resubmittals received | | | 2/17/2009 | | |
John Menard
|
|
|
Received transmittal and two copies of pages A2.2, A2.4; inserted by Architect and taken back to John Menard
|
Plan Reviewer's activity | | | 2/17/2009 | | PASS |
John Menard
|
|
|
Reviewed and approved final revised plans with red lined notes and attached plan review clarification notes. JCM
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/17/2009 | | DONE |
John Menard
|
|
|
|
Print Occupancy Form | | | 2/17/2009 | | DONE |
Alexandra L. DeYoung
|
|
|
|
Plan Reviewer's activity | | | 1/29/2009 | | PASS |
John Menard
|
|
|
Reviewed and approved structural revisions. JCM
|
Plan resubmittals requested | | | 1/29/2009 | | DONE |
John Menard
|
|
|
E-mailed the architect requesting additional revisions. JCM
|
Plan resubmittals received | | | 1/28/2009 | | |
John Menard
|
|
|
Rec'd four copies of sheets S0.1, S1.2, S3.2, S5.1, A2.2, A2.4, A9.2 and four copies of structural calcs- inserted by architect- taken to John M
|
Routing - PUBLIC WORKS | 12/10/2008 | | 12/12/2008 | | PASS |
Beverly Hall
|
|
|
|
Routing - PLUMBING | 12/12/2008 | | 12/12/2008 | | PASS |
Bill VanDegrift
|
|
|
per plans and 2003 upc
|
Routing PW Sewer Design | 11/14/2008 | | 12/11/2008 | | PASS |
Jon R. Gunnerson
|
|
|
Connect onto existing 6-inch service provided.
|
Routing PW Drainage | 12/10/2008 | | 12/10/2008 | | PASS |
Terry Records
|
|
|
|
Routing - PLAN CHECK | 12/8/2008 | | 12/10/2008 | | |
John Menard
|
|
|
|
Routing - FIRE | 12/3/2008 | 12/3/2008 | 12/8/2008 | | PASS |
Scott Arellano
|
|
|
Attached IFC comments to plans
|
1st review completed | | | 12/8/2008 | | FAIL |
|
|
|
Failed PW, Plumbing, Plan Check
|
Plan resubmittals received | | | 12/4/2008 | | |
Barbara Stitt
|
|
|
Received 9 sets of sheets C2, C3, C4, C5, C6 were inserted into plans BLD08-02293, and BLD08-02295 and sheets C2 & C3 into BLD08-02292 by architects office and returned to desks taken from 12-4-08 BAS
|
Route to Impact Fee Review | 12/3/2008 | 12/8/2008 | 12/3/2008 | | PASS |
Cindy M. Gould
|
|
|
|
Routing - PLAN CHECK | 12/3/2008 | | 12/3/2008 | | FAIL |
John Menard
|
|
|
|
Plan resubmittals requested | | | 12/2/2008 | | DONE |
John Menard
|
|
|
E-mailed the architect a copy of the plan review requesting revisions. JCM
|
Plan resubmittals requested | | | 11/25/2008 | | DONE |
John Menard
|
|
|
E-mailed the architect a copy of the structural plan review comment requesting revisions. JCM
|
Routing Off Site - STRUCTURAL | 11/12/2008 | | 11/21/2008 | | FAIL |
John Menard
|
|
|
Called Action Couriers for pick up - Received commen list from consulting structural engineer requesting revisions. JCM
|
Routing - PLANNING | 11/20/2008 | | 11/20/2008 | | PASS |
Josh Wilson
|
|
|
drh 07-00597 Josh W. PASS DR
cup07-00177 Sue H.
|
Routing - PLUMBING | 11/18/2008 | | 11/20/2008 | | FAIL |
Bill VanDegrift
|
|
|
need to pass sewer design prior to plumbing acceptance.
|
Routing - Erosion and Sediment | 11/17/2008 | | 11/18/2008 | | PASS |
Steven Webb
|
|
|
ESC plan approved with attached conditions. ESC08-00981
|
Routing - PUBLIC WORKS | 11/14/2008 | | 11/17/2008 | | FAIL |
Connie Baumgartner
|
|
|
Refer to Sewer Design - Jon Gunnerson & Drainage - Terry Records.
|
Routing PW Solid Waste | 11/17/2008 | | 11/17/2008 | | PASS |
Peter J. McCullough
|
|
|
|
Routing PW Drainage | 11/17/2008 | | 11/17/2008 | | FAIL |
Brian Murphy
|
|
|
Grading permit failed
|
Routing PW Street Lights | | | 11/17/2008 | | PASS |
Hank Alarcon
|
|
|
|
Routing PW Sewer Rating | 11/14/2008 | | 11/14/2008 | | PASS |
Connie Baumgartner
|
|
|
|
Routing - PLANNING Land Div | 11/12/2008 | | 11/14/2008 | | PASS |
Todd Tucker
|
|
|
Parcel has not changed since it was annexed into the city.
|
Plans ACCEPTED BY PLAN TECH | | | 11/12/2008 | | |
Darla L Downs
|
|
|
|
Plan routing begun/NEW & ADDTN | | | 11/12/2008 | | |
Darla L Downs
|
|
|
|
Pending Assignment by JCM | 11/12/2008 | | 11/12/2008 | | BLDA |
John Menard
|
|
|
11/12/2008 11:32:02 JCM - activity updated through activity BLDA166 from case BLD08-02395.
|
Application received | | 11/10/2008 | | | |
|
|
|
|
Application received | | 11/10/2008 | | | |
|
|
|
|
Routing PW Sewer Design | 12/10/2008 | | | | |
Jon R. Gunnerson
|
|
|
|