Permit Information
Permit NumberBLD08-02568
StatusFinaled
Name BENCHMARK CONSTRUCTION INC
Site Address 3630 N EAGLE RD
Project NameHome Fed Bank - Bald Cypress
Customer Number 
ePlanReviewNo
Description
Home Federal Bank - Bald Cypress Branch - To construct a new 4,700 square foot, one story, wood framed bank office building with covered drive-thru. This permit also included related site improvements. All construction per the approved plans and attached comment list. DRH08-00346 JCM
Contact Information
See Activities list for contact information
Color Key
Current location of plans being reviewed:  
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Case Summary (BLD)  8/9/2016 DONE
Routing PW Street Lights  5/7/2014 PASS
DetailsHank Alarcon
Called and faxed Steve Christensen on 12/29/2008 and advised him of correction required on street lighting plans.
Third Notice 11/15/200911/6/2009 DONE
Telephone call  11/6/2009 DONE
DetailsTisha Gallop
per phone call with Sean Matier/Benchmark const.; KMD final total $33,800 (all the mech. value), Paige final value is $27,000 (all the plm value), he doesn't know what value for Jim Russell Excavation because he had the contract for the all the site work and parking lot and not know what portion of that was just for the underground sewer/water lines.
Third Notice 10/31/200911/5/2009 DONE
Second Notice 9/28/200910/21/2009 DONE
DetailsBarbara Stitt
First Notice 9/1/20099/18/2009 DONE
PubWorks Occupancy Approval9/3/20099/3/20099/3/2009 DONE
DetailsTiffany Lowery
BLD-Final8/31/20099/1/20099/1/2009APASS
DetailsJim Sly
Shawn Phone #: ###-####
OK for Perm Occ.
Permanent Occupancy  9/1/2009 DONE
DetailsTisha Gallop
BLD-Final8/28/20098/31/20098/31/2009PNR
DetailsJim Sly
Shawn Phone #: ###-####
need P/W
FIRE-Final Inspection8/28/20098/31/20098/31/2009APASS
DetailsTroy Cobbley
life safety passed. The lights have been repaired.
BLD-Final8/27/20098/28/20098/28/2009PNR
DetailsJim Sly
Shawn Phone #: ###-####
Need Fire for Perm....P/W.....
FIRE-Final Inspection8/27/20098/28/20098/28/2009APART
DetailsTroy Cobbley
A temporary occupancy was being given with mark sentennos permission until the two missing emergency lights have been installed. All other items are passed. I waited while the sample tubes in the duct detector were installed correctly.
Zoning Approval8/28/20098/28/20098/28/2009 PASS
DetailsAndrea Tuning
BLD-Other8/18/20098/19/20098/18/2009APASS
DetailsJim Sly
shawn - ceiling grid Phone #: ###-####
Ceiling Grid Pass................Disregard previous framing Inspection....(ie...Eng to Ok double stud nai...........) Mistake.....
BLD-Framing/Rough-in8/17/20098/18/20098/18/2009APART
DetailsJim Sly
Shawn Phone #: ###-####
Shear panel nailing OK......Waiting for OK from Eng for attachment of double studs at panel ends.... (Pre mfg panels)
BLD-Energy code compliance7/29/20097/30/20097/30/2009APASS
DetailsJim Storey
Shawn Phone #: ###-#### roof made ok
BLD-Energy code compliance7/27/20097/28/20097/28/2009APART
DetailsJim Storey
shawn Phone #: ###-#### ok need recalc. for roof deck to meet r 30
BLD-Framing/Rough-in7/27/20097/28/20097/28/2009APASS
DetailsJim Storey
shawn Phone #: ###-#### drive thru roof nailling ok to cover
BLD-Framing/Rough-in7/24/20097/24/20097/24/2009PPASS
DetailsMike Jordan
Shawn if possible around 2 pm Phone #: ###-####. Interior and exterior framed walls and hardlids ok. All straps installed. Interior shear walls ok.
BLD-Framing/Rough-in7/21/20097/21/20097/21/2009PPART
DetailsMike Jordan
Shawn-if possible around 2 or 2:30 please Phone #: ###-####. Extrior shear nailing and nailing for roof diapragm. Also inspected and verified straps on exterior side of roof. Still needs to nstall straps for drag struts below.
BLD-Framing/Rough-in7/14/20097/14/20097/14/2009PPART
DetailsJim Sly
SHAWN Phone #: ###-####
Inspection of hold downs and fireblocking at (3) popped out walls........West wall toward Eagle Rd. OK to cover.
BLD-Conference7/9/20097/9/20097/9/2009PPASS
DetailsJim Sly
shaun Phone #: ###-####
Verified hold down at W. wall ....Electrical room......OK to cover.
BLD-Foundation6/22/20096/23/20096/23/2009APART
DetailsJim Sly
shawn - stem wall Phone #: ###-####
Wall OK pending MTI inspection, tests and approvals.
BLD-Foundation6/17/20096/18/20096/18/2009APART
DetailsJim Sly
shawn - late morning - pouring at 1 Phone #: ###-####
Rebar appears OK at footings except for an area for truck access to be completed later. MTI special insp on Compressive strength for concrete.
Issue PAID IN FULL permit  6/12/2009 DONE
DetailsTisha Gallop
Routing - PLAN CHECK6/10/2009 6/11/2009 PASS
DetailsJohn Menard
PLANS/APPL TAKEN TO FRONT DESK  6/11/2009 DONE
DetailsJohn Menard
Print Occupancy Form  6/11/2009 DONE
Details
Telephone call  6/11/2009 DONE
Details
left vm for steve christiansen at ###-#### - permit ready and fees given - also need ACHD receipt and RP name
Permit Ready to Issue  6/11/2009 DONE
Details
Plan assigned to (JCM)12/19/2008 6/11/2009 PASS
DetailsJohn Menard
6/11/2009 09:16:35 JCM - activity updated through activity BLDA022 from case BLD08-02568.
Routing - PUBLIC WORKS6/4/2009 6/10/2009 PASS
DetailsBeverly Hall
Routing PW Drainage  6/10/2009 FAIL
DetailsBrian Murphy
NEED REVISION TO DETAIL SHEET BRIAN MURPHY ###-####
Routing PW Drainage6/10/2009 6/10/2009 PASS
DetailsBrian Murphy
Routing - PLANNING6/10/2009 6/10/2009 FAIL
DetailsAndrea Tuning
Waiting for the applicant to submit a cross access agreement. ANT 6-10-09
Routing - PLAN CHECK6/10/2009 6/10/2009  
DetailsJohn Menard
Routing - PLANNING6/10/2009 6/10/2009 PASS
DetailsAndrea Tuning
Routing - PLAN CHECK4/1/2009 6/4/2009  
DetailsJohn Menard
Routing - PLANNING Land Div6/4/2009 6/4/2009 PASS
DetailsTodd Tucker
Subdivision has been recorded.
Routing - PUBLIC WORKS3/27/2009 4/1/2009 FAIL
DetailsConnie Baumgartner
Failed by Brian Murphy, contact at ###-#### for more information.
Routing PW Drainage3/27/2009 3/31/2009 FAIL
DetailsBrian Murphy
Need cross drainage access agreement Brian Murphy ###-####
Routing - PLAN CHECK3/26/2009 3/27/2009  
DetailsJohn Menard
Routing PW Street Lights3/27/2009 3/27/2009 PASS
DetailsHank Alarcon
Routing - FIRE3/23/2009 3/26/2009 PASS
DetailsScott Arellano
Attached updated IFC comments to plans
Routing - PLAN CHECK3/20/2009 3/23/2009  
DetailsJohn Menard
Routing - PLANNING3/23/2009 3/23/2009 FAIL
DetailsAndrea Tuning
Waiting for the applicant to submit a cross access agreement. ANT 3-23-09
Routing - PLAN CHECK3/23/2009 3/23/2009 PASS
DetailsJohn Menard
Plan Reviewer's activity  3/23/2009 PASS
DetailsJohn Menard
Reviewed and and approved structural and nonstructural plan revisions. JCM
Routing - PUBLIC WORKS3/16/2009 3/20/2009 FAIL
DetailsLouise Waldorf
Refer to site drainage
Routing - Erosion and Sediment3/13/2009 3/16/2009 PASS
DetailsSteven Webb
ESC plan approved with attached conditions. ESC08-01043
Plan resubmittals received  3/13/2009  
Received three copies of O & M manual, Drainage Report, ESC application and narrative, five copies of sheets C1.0, C1.1, C1.2, C1.3, C1.4, C1.5; inserted by arch. rep and taken back to ESC
Routing - PUBLIC WORKS3/6/2009 3/13/2009 FAIL
DetailsLouise Waldorf
Refer to site drainage
Routing PW Street Lights3/6/2009 3/9/2009 FAIL
DetailsHank Alarcon
Called E2CO Electrical Engineering Company ###-#### on 03/09/2009. Advised Jeff that plan did not meet ISPWC standards or City of Boise street lighting standards and to resubmit street light plans.
Routing - PLUMBING3/2/2009 3/5/2009 PASS
DetailsBill VanDegrift
per plans and 2003 upc
Routing - PLAN CHECK1/14/2009 3/2/2009  
DetailsJohn Menard
Plan resubmittals received  3/2/2009 DONE
received 4 responses & 4 copies of sheets C1.3,A1.1,A5.5,A6.1,S2.0,S3.1,E1.0,E3.2 insreted by Steve Christansen from LCA architects. taken back to John M.
Route to Impact Fee Review1/12/20091/15/20091/14/2009 PASS
DetailsCindy M. Gould
Routing - FIRE1/12/20091/12/20091/14/2009 FAIL
DetailsScott Arellano
Faxed and emailed resubmittal items to architect.
Application received 12/18/20081/14/2009 DONE
DetailsBarbara Stitt
1st review completed  1/14/2009 FAIL
Failed PW, ESC, Structural, Plumbing, Planning, Plan Check, Fire
Plan resubmittals requested  1/13/2009 DONE
DetailsJohn Menard
E-mailed the architect a copy of the plan review requesting revisions. JCM
Routing - PLAN CHECK1/7/2009 1/12/2009 FAIL
DetailsJohn Menard
Plan resubmittals requested  1/12/2009 DONE
DetailsJohn Menard
E-mailed the architect a copy of the plan review requesting revisions. JCM
Routing - PLANNING1/6/2009 1/7/2009 FAIL
DetailsAndrea Tuning
The applicant has not provided the cross access agreement that was required with the DR application.

ANT 1-7-09
Routing - Erosion and Sediment1/5/2009 1/6/2009 FAIL
DetailsSteven Webb
ESC plan does not meet requirements per BMC 8-17. Faxed ESC checklist to PD. Re-submittal is required.
Routing - PUBLIC WORKS12/23/2008 1/5/2009 FAIL
DetailsLouise Waldorf
Refer to street lighting and site drainage
Routing PW Solid Waste1/2/2009 1/5/2009 PASS
DetailsPeter J. McCullough
Routing PW Sewer Rating  1/5/2009 PASS
DetailsLouise Waldorf
Routing PW Drainage  1/2/2009 FAIL
DetailsBrian Murphy
CROSS DRAINAGE ACCESS AGREEMENT 18 INCHES OF ASTM SAND LENGTH AND WIDTH OF SAND FILTERS. BRIAN MURPHY ###-####
Routing PW Sewer Design12/23/2008 12/29/2008 PASS
DetailsJon R. Gunnerson
Connect onto 4-inch sanitary sewer service to be constructed under DRI-1479 FirstChurch Commercial Subdivision.
Plan resubmittals requested  12/23/2008 DONE
DetailsJohn Menard
E-mailed the architect a copy of the structural review requesting revisions. JCM
Routing - PLANNING Land Div12/19/2008 12/23/2008 FAIL
DetailsTodd Tucker
The Final Plat has not been recorded yet. As such, DO NOT issue the Building Permit until the Final Plat has been recorded with the Ada County Recorders Office.
Routing Off Site - STRUCTURAL12/19/2008 12/23/2008 FAIL
DetailsJohn Menard
Called Action Couriers for pick up - Received comment list from consulting structural engineer requesting revisions. JCM
Pending Assignment by JCM12/19/2008 12/19/2008 BLDA
DetailsJohn Menard
12/19/2008 08:27:55 JCM - activity updated through activity BLDA166 from case BLD08-02568.
Plans ACCEPTED BY PLAN TECH  12/18/2008 DONE
DetailsDarla L Downs
Plan routing begun/NEW & ADDTN  12/18/2008 DONE
Routing - PLUMBING1/6/2009 1/6/2008 FAIL
DetailsBill VanDegrift
min. grade on the 3" roof drain and overflow will be 1/4" per foot. provide a site plan showing exterior rain water piping from the building to the point of disposal.
Routing PW Drainage3/9/2009   FAIL
DetailsBrian Murphy
NO new revisions. Need crosss access agreement
Routing PW Drainage3/20/2009   FAIL
NEED CROSS DRAINAGE ACCESSS AGREEMENT