Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberBLD09-00068
StatusFinaled
Name RADIX CONSTRUCTION INC
Site Address 9632 W EMERALD ST STE B
Project NameWestpark Station-Soffit Repair
Customer Number 
ePlanReviewNo
Description
(WEST PARK STATION - SHELL & CORE - In front of Seimen's Technologies) Permit is to repair 102 square feet of damaged soffit in the canopy in front of Seimen's Technologies. Approval per approved plans on file. Work to include: demolition of existing soffit and installation of new soffit per cut-sheet attached to plans. This building is not fire sprinklered.**TLW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Second Notice BLD3/4/20093/4/20093/6/2009 DONE
DetailsAlexandra L. DeYoung
First Notice has not been responded to.
First Notice2/19/20092/19/20093/4/2009 DONE
DetailsTom Arcoraci
BLD-Final2/18/20092/19/20092/19/2009APASS
DetailsTom Arcoraci
jon Phone #: ###-####
DOC - Permit Finaled2/19/20092/19/20092/19/2009PPASS
DetailsTom Arcoraci
BLD-Final2/17/20092/17/20092/17/2009PNR
DetailsJim Sly
jon Phone #: ###-####
BLD-Framing/Rough-in2/2/20092/3/20092/3/2009APASS
DetailsMike Jordan
john Phone #: ###-####
Issue PAID IN FULL permit  2/2/2009 DONE
DetailsBarbara Stitt
Inspection Record Card- Bld  1/27/2009 DONE
Permit Ready to Issue  1/27/2009 DONE
Plan assigned to (TLW)1/22/2009 1/26/2009 PASS
DetailsTim L. Woodard
1/26/2009 16:58:07 TLW - activity updated through activity BLDA022 from case BLD09-00068.
Plan Reviewer's activity  1/26/2009 DONE
DetailsTim L. Woodard
Talked with applicant Jon Engelund he indicated he would change osb to exterior gypsum. Issued Plans accordingly. TLW
Routing - PLAN CHECK1/26/2009 1/26/2009 PASS
DetailsTim L. Woodard
PLANS/APPL TAKEN TO FRONT DESK  1/26/2009 DONE
Case Summary (BLD)  1/26/2009 DONE
Routing - PLAN CHECK1/22/2009 1/22/2009 FAIL
DetailsTim L. Woodard
Soffit Repair only. TLW
Cut-sheet showed use of OSB. Due to this being a type IIN it is required non-combustable materials.
1st review completed  1/22/2009 FAIL
DetailsTim L. Woodard
Plans ACCEPTED BY PLAN TECH  1/22/2009 DONE
DetailsBarbara Stitt
Application received 1/21/20091/21/2009 DONE
DetailsBarbara Stitt
Recd Pcfee & Taken To Pln CK  1/21/2009 DONE
DetailsBarbara Stitt