Case Summary (BLD) | | | 1/12/2016 | | DONE |
|
|
|
|
Letter of compliance | | | 5/7/2009 | | DONE |
Tisha Gallop
|
|
|
|
DOC - Permit Finaled | | | 5/7/2009 | | DONE |
Tisha Gallop
|
|
|
|
BLD-Final | 5/4/2009 | 5/4/2009 | 5/4/2009 | P | PASS |
Jim Storey
|
|
|
Scheduled by a contractor via Hello! on 5/4/2009 at 8:17:01 AM. Contact: ###-####.
|
FIRE-Final Inspection | 5/4/2009 | 5/4/2009 | 5/4/2009 | P | PASS |
Forrest France
|
|
|
Correction notice items verified for compliance, vanilla fire life safety passed.
|
FIRE-Final Inspection | 4/22/2009 | 4/22/2009 | 4/22/2009 | A | FAIL |
Forrest France
|
|
|
Existing office area at the vanilla TI is lacking sufficient fire sprinkler coverage and proper spacing per NFPA 13. Items include an office missing protection, overspacing at the entry lobby, two rooms with min./max. spacing issues. Fire sprinkler system modifications will require a separate permit- see project description and item #8 on the general notes on approved plan set.
|
BLD-Final | 4/22/2009 | 4/22/2009 | 4/22/2009 | A | PASS |
Jim Storey
|
|
|
Dan Phone #: ###-####
|
Issue PAID IN FULL permit | | | 3/18/2009 | | DONE |
Tisha Gallop
|
|
|
|
(F) Reprint permit | | | 3/18/2009 | | DONE |
|
|
|
|
Routing - FIRE | | | 2/24/2009 | | PASS |
Scott Arellano
|
|
|
|
Telephone call | | | 2/24/2009 | | DONE |
|
|
|
t/c w joe thompson at ###-#### - permit ready - also need gc name and rce#
|
Permit Ready to Issue | | | 2/24/2009 | | DONE |
|
|
|
|
Plan assigned to (TLW) | 2/10/2009 | | 2/23/2009 | | PASS |
Tim L. Woodard
|
|
|
2/23/2009 14:57:29 TLW - activity updated through activity BLDA022 from case BLD09-00156.
|
Routing - FIRE | 2/20/2009 | | 2/23/2009 | | FAIL |
Scott Arellano
|
|
|
Faxed and emailed resubmittal items to architect.
|
Routing - PLAN CHECK | 2/23/2009 | | 2/23/2009 | | PASS |
Tim L. Woodard
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/23/2009 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 2/23/2009 | | DONE |
|
|
|
|
Case Summary (BLD) | | | 2/20/2009 | | DONE |
Tim L. Woodard
|
|
|
|
1st review completed | | | 2/20/2009 | | FAIL |
|
|
|
Failed Fire
|
Routing - PLAN CHECK | 2/20/2009 | | 2/20/2009 | | PASS |
Tim L. Woodard
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 2/10/2009 | | DONE |
Tisha Gallop
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 2/10/2009 | | DONE |
Tisha Gallop
|
|
|
|
Application received | | 2/10/2009 | | | |
|
|
|
|