Third Notice | | 1/3/2010 | 1/13/2010 | | DONE |
|
|
|
|
Second Notice | | 12/4/2009 | 12/29/2009 | | DONE |
|
|
|
|
First Notice | 11/13/2009 | 11/13/2009 | 11/25/2009 | | DONE |
Mike Jordan
|
|
|
|
BLD-Final | 11/12/2009 | 11/13/2009 | 11/13/2009 | P | PASS |
Mike Jordan
|
|
|
JD Phone #: ###-####
|
DOC - Permit Finaled | 11/13/2009 | 11/13/2009 | 11/13/2009 | P | PASS |
Mike Jordan
|
|
|
Final ok.
|
FIRE-Final Inspection | 11/13/2009 | 11/13/2009 | 11/13/2009 | P | PASS |
Troy Cobbley
|
|
|
Life safety passed.
|
FIRE-Final Inspection | 11/12/2009 | 11/13/2009 | 11/13/2009 | A | FAIL |
Troy Cobbley
|
|
|
The fire alarm db readings passed. All other items passed except the exit signs have been wired up to the light switches which is incorrect.
|
Telephone call | | | 11/2/2009 | | DONE |
|
|
|
Regarding notification: Had a conversation with JD of Hamilton. He wanted to know if notification would be required in the new lab/nacropsy area being built. I let him know that based on the information he gave me regarding the room use (no public access), and based on the case history, that audibility requirements would need to be met, but not visual. I told him as long as the minimum dB requirements of 2007 NFPA 72 were met in the room from the existing devices, that no new devices would be required. I stated, however, that if the audibility requirements were not met, then a notification device would be required and a separate permit obtained.
|
BLD-Framing/Rough-in | 9/24/2009 | 9/28/2009 | 9/28/2009 | A | PASS |
Mike Jordan
|
|
|
JD Phone #: ###-####. ok to rock. All framing issues resolved. Approved lans on site.
|
BLD-Framing/Rough-in | 9/23/2009 | 9/24/2009 | 9/24/2009 | P | FAIL |
Mike Jordan
|
|
|
JD Phone #: ###-####. Provide approved set of plans. Install stud shoes and straps were plumbing pipes penetrate. c/n issued.
|
Issue PAID IN FULL permit | | | 7/2/2009 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 7/1/2009 | | DONE |
|
|
|
|
Telephone call | | | 7/1/2009 | | DONE |
|
|
|
t/c w maryann hamilton at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 7/1/2009 | | DONE |
|
|
|
|
Routing - Addressing | 6/25/2009 | | 7/1/2009 | | PASS |
April Wing
|
|
|
|
Routing - PLAN CHECK | 6/26/2009 | | 6/30/2009 | | FAIL |
Carl D Madsen
|
|
|
Clarification is required on the actual limits of the USDA tenant space. E-Mailed the Agent representative (Hamilton Builders) Called George Graves with USDA and left a message requesting information on the tenant space and called ABC drafting and Design and left a message requesting information about the tenant space. 6-30-09 CDM
|
Routing - FIRE | | | 6/30/2009 | | PASS |
|
|
|
Field Verify CDM
|
1st review completed | | | 6/30/2009 | | FAIL |
|
|
|
|
Routing - PLAN CHECK | 6/30/2009 | | 6/30/2009 | | PASS |
Carl D Madsen
|
|
|
|
Case Summary (BLD) | | | 6/30/2009 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/30/2009 | | |
|
|
|
|
Plan assigned to (CDM) | | | 6/30/2009 | | PASS |
Carl D Madsen
|
|
|
6/30/2009 16:31:34 CDM - activity updated through activity BLDA022 from case BLD09-00869.
|
Routing - PUBLIC WORKS | | | 6/26/2009 | | PASS |
Beverly Hall
|
|
|
|
Routing PW Environmental | 6/26/2009 | | 6/26/2009 | | PASS |
Walt Baumgartner
|
|
|
USDA Wildlife Lab. Disposal of lab chemicals, particularly tissue preservatives, cannot be discharged to sanitary sewer except by express authorization by Pretreatment. ###-#### for more informtion. Any hazardous waste must be handled in accordance with applicable regulations.
|
Plans ACCEPTED BY PLAN TECH | | | 6/24/2009 | | |
Alexandra L. DeYoung
|
|
|
|
Application received | | 6/4/2009 | | | FAIL |
|
|
|
This permit in being changed to a level 3 TI. The space is approximately 39,000 square feet with the work confined to approximately 270 square feet. He did not have architectural stamp or dimensioned plans.
|