Permit Information
Permit NumberBLD09-01275
StatusFinaled
Name CONTRACTORS NORTHWEST
Site Address 130 N MILWAUKEE ST
Project NamePETSMART
Customer Number 
ePlanReviewNo
Description
(PETSMART TENANT IMPROVEMENT) This building is required to be fire sprinklered for building area increase. To construct interior tenant improvements within a new building shell for a pet store. This tenant space will be used for retail sales, pet salon, pet medical treatment, and pet boarding. The building shell was constructed under permit BLD09-01007. Work is to include interior nonbearing walls, interior doors, interior windows, 2 restrooms accessible to the disabled, suspended acoustical ceilings, millwork, and finishes. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. A separate permit is required for high-rack storage. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice 6/6/20106/23/2010 DONE
BLD-Final5/26/20105/27/20105/27/2010APASS
DetailsMike Jordan
ok for perm occ.
Permanent Occupancy UNPAID FEE  5/27/2010 DONE
FIRE-Final Inspection5/7/20105/10/20105/10/2010PPASS
DetailsTroy Cobbley
Life safety passed.
BLD-Final5/6/20105/7/20105/7/2010APASS
DetailsMike Jordan
Rod Phone #: ###-####. ok for temp. occ. Open plumbing permit should be stand alone permit. Needs to complete firecaulking at riser room and repair the doorhardware at the pet salon.
Zoning Approval5/7/20105/7/20105/7/2010 PASS
DetailsJosh Wilson
Temporary Occupancy UNPAID FEE  5/7/2010 DONE
FIRE-Final Inspection5/5/20105/6/20105/6/2010APART
DetailsTroy Cobbley
A temporary occupancy was given with Scott and Marks approval until the fire alarm permit for the new tamper switch on the anti-freeze loop has been finaled. The work has been scheduled for monday morning at 8:00am.
FIRE-Conference5/6/20105/6/20105/6/2010ADONE
DetailsTroy Cobbley
The property manager, Linda, contacted me about a temporary occupancy for this project until Monday due to SimpleGrinnell not being able to perform their work until that I deferred her to Mark Senteno for a decision.
FIRE-Final Inspection5/3/20105/4/20105/4/2010PFAIL
DetailsTroy Cobbley
The project related fire alarm permit needs to be finaled, verification of factory installed duct smoke detectors and the indicators installed on the main exit doors as discussed. The previous items have been corrected.
BLD-Final4/29/20104/30/20104/30/2010ANR
DetailsMike Jordan
rod Phone #: ###-####. Also spoke to contractor about shell and core permit.
FIRE-Final Inspection4/28/20104/29/20104/29/2010PFAIL
DetailsTroy Cobbley
The project related fire alarm permit needs to be finaled. Also indicators and stickers need to be installed at the two sets of double main entry doors. The exit discharge light on the northwest exit door did not function.
FIRE-Conference4/14/20104/14/20104/14/2010PDONE
DetailsTroy Cobbley
I spoke with the job superintendant for CNI Construction about the need for an additional fire alarm permit for the connection of the canopy anti-freeze system control valve into the existing fire alarm system located at 104 Milwaukee. This fire alarm work is not covered under the new PetsMart fire alarm system. I let him know that I could not sign off on the building until this additional permit has atleast been submitted for review. He said he would let the associated parties know.
BLD-Other4/7/20104/8/20104/8/2010APASS
DetailsMike Jordan
rob - ceiling grid Phone #: ###-####. Reinspected grid ceiling. grid as installed per cisca 0-2 ok. Received letter from CASCO (architect of record) noting that CISCA 0-2 system is approved to be installed in leiu of the CICSCA3-4. Will have letter scanned into project.
BLD-Conference4/5/20104/5/20104/5/2010PDONE
DetailsMike Jordan
Met on site with contractor to discuss ceiling grid issues. Will discuss with plan reviewer before proceeding further.
BLD-Framing/Rough-in3/31/20103/31/20103/31/2010PFAIL
DetailsMike Jordan
Ceiling grid inspection please-Rod- Phone #: ###-####. Installed grid not per plan.
BLD-Energy code compliance3/1/20103/2/20103/2/2010APASS
DetailsMike Jordan
Rod Phone #: ###-####
BLD-Framing/Rough-in2/25/20103/1/20103/1/2010APASS
DetailsMike Jordan
ROD Phone #: ###-####. All interior steel stud framed walls and backing for ada elements, no grid. Also spoke to rod about 1hr. consttruction requirements for fire riser room.
BLD-Aging Inspection2/24/20102/24/20102/24/2010 PASS
DetailsMike Jordan
work is in progress on interior steel stud walls. Visited job site last week. Should be ready for framing inspection by early next week as per contractor.
Issue PAID IN FULL permit  11/25/2009 DONE
Details
Print Occupancy Form  11/23/2009 DONE
Permit Ready to Issue  11/23/2009 DONE
DetailsBarbara Stitt
Telephone call  11/23/2009 DONE
DetailsBarbara Stitt
Called Mark Bender at ###-#### and left a voice message that permit is ready, fees due and need GC/RCE #///11-23-09 @ 12:05pm BAS
Plan assigned to (CJW)8/14/20098/14/200911/20/2009 PASS
DetailsCarl Westfall
11/20/2009 09:21:10 CJW - activity updated through activity BLDA022 from case BLD09-01275.
Routing - PLUMBING11/19/2009 11/20/2009 PASS
DetailsBill VanDegrift
move WF-1 downstream of R.P..
Routing - PLAN CHECK11/20/2009 11/20/2009 DONE
DetailsCarl Westfall
Took drawings to the permits desk.
PLANS/APPL TAKEN TO FRONT DESK  11/20/2009 DONE
Routing - FIRE11/16/2009 11/19/2009 PASS
DetailsScott Arellano
Attached updated IFC comments to plans
Routing - PLAN CHECK11/19/2009 11/19/2009  
Sent back to Plumbing
Plan resubmittals received  11/19/2009 DONE
DetailsTisha Gallop
received response to comments and two copies of plan sheets P1.1, P1.2, P2.0, P3.0, P3.1; taken to Carl Westfall
Routing - PLUMBING11/13/2009 11/16/2009 FAIL
DetailsBill VanDegrift
still need all water in the treatment area, pet isolation, bathing, kennel areas,isolated with a R.P. hot and clod. Hot water can not recirculate from the pretected system to the unprotected system.
Routing - PLAN CHECK9/29/2009 11/13/2009 PASS
DetailsCarl Westfall
Drawings approved after resubmittal review.
Plan resubmittals received  11/12/2009  
DetailsCarl Westfall
received cover letter, 2 sets of A0.1, A1.0, A2.2, A6.0, A6.1, A8.0, A8.1, A8.4 - taken to carl westfall
Routing - PUBLIC WORKS10/6/2009 10/7/2009 PASS
DetailsBeverly Hall
Routing PW Environmental10/6/2009 10/7/2009 PASS
DetailsWalt Baumgartner
reviewed - West Boise Sewer Dist.
Routing - FIRE9/28/2009 9/29/2009 FAIL
DetailsScott Arellano
Emailed and faxed updated review comments to architect (William Bandle).
Routing - PLUMBING9/25/2009 9/28/2009  
Routing - PLAN CHECK9/10/2009 9/25/2009 FAIL
DetailsCarl Westfall
Completed the 2nd plan review. Sent E-mail to the Architect listing the corrections needed.
Plan resubmittals received  9/21/2009  
DetailsCarl Westfall
Rec'd by mail response letter, door hardware info, and two copies of sheets; f1.0; a0.1; a2.0; a2.1; a2.2; a2.3; a3.0; a5.0; a6.0; a6.1; a6.2; a8.0; a8.1; a8.4; a9.0; a12.0; p0.1; p1.0; p1.1; p1.2; p2.0; p2.1; p3.0; p3.1; e0.1; e1.0- taken to Carl W.
Routing - PLANNING9/9/2009 9/10/2009 PASS
DetailsJosh Wilson
1st review completed  9/10/2009 FAIL
Failed Plumbing, Plan Check, Fire
Routing - PLAN CHECK9/8/2009 9/9/2009  
Sent to Planning
Routing - FIRE9/1/20099/1/20099/8/2009 FAIL
DetailsScott Arellano
Faxed and emailed resubmittal items to architect.
Route to Impact Fee Review9/1/20099/4/20099/2/2009 PASS
DetailsCindy M. Gould
Tenant improvement no impact fees
Routing - PLAN CHECK8/21/2009 9/1/2009 FAIL
DetailsCarl Westfall
The IBC plan review was started on August 24, 2009 and was finished on September 1, 2009. Revised drawings were required. See the plan review report.
Routing - PLUMBING8/17/2009 8/21/2009 FAIL
DetailsBill VanDegrift
all water to fixtures in the treatment area must be protected by a reduced pressure zone backflow preventer (RP) located outside the treatment area. all water to the pet isolation, bathing, kennel areas must be protected by an r.p.. wp-1 will require an r.p. upstream.
Routing - PUBLIC WORKS8/14/2009 8/17/2009 PASS
DetailsBeverly Hall
Routing PW Sewer Rating8/17/2009 8/17/2009 PASS
DetailsConnie Baumgartner
Routing PW Environmental8/17/2009 8/17/2009 PASS
DetailsWalt Baumgartner
Any silver bearing wastewater from xray room must be pretreated prior to discharge to District sewer system. Call ###-#### for guidance.
Routing - Addressing8/14/2009 8/14/2009 PASS
DetailsApril Wing
Pending Assignment by JCB8/11/2009 8/14/2009 DONE
DetailsDarla L Downs
Assigned to Carl Westfall
Intake Approval  8/11/2009 PASS
Conducted follow-up plan intake meeting. Allowed project to be submitted for permit.
Application received 7/29/20097/29/2009 DONE
DetailsBarbara Stitt
Intake Approval  7/29/2009 FAIL
NEED: 1) United Water fire flow; 2) Need Ceiling notes & details for CISCA 0-2; 3) Fire pump / riser room & construction details & door to exterior; 4) Automatic lighting control shutoff for tenant space > 5,000sq. ft.; 5) Heating & Cooling load calcs.