Permit Information
Permit NumberBLD09-02032
StatusFinaled
Name MCALVAIN CIVIL CONSTRUCTORS INC
Site Address 1120 S HILTON ST
Project Name 
Customer Number 
ePlanReviewNo
Description
United Water - Hilton Street Well House - To demolish and remove an existing 435 square foot well house and construct a new 1,870 square foot, one story well house and a 41,000 gallon steel backwash water tank. The new well house will be constructed of concrete masonry exterior walls and wood trussed roof framing. This permit also includes related site improvements. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Color Key
Current location of plans being reviewed:  
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Second Notice 10/7/201010/4/2010 DONE
First Notice 9/17/20109/27/2010 DONE
PubWorks Occupancy Approval9/7/20109/7/20109/7/2010 DONE
DetailsTiffany Lowery
Permanent Occupancy  9/7/2010 DONE
BLD-Final8/31/20109/1/20109/1/2010APASS
DetailsTom Arcoraci
Travis Phone #: ###-####
FIRE-Final Inspection8/31/20108/31/20109/1/2010PPASS
DetailsTroy Cobbley
Life safety passed
BLD-Final8/26/20108/26/20108/26/2010PPART
DetailsTom Arcoraci
travis Phone #: ###-#### ok after fire sign off
FIRE-Final Inspection8/26/20108/26/20108/26/2010PFAIL
DetailsTroy Cobbley
An outside supply duct has been added to the unit. This new duct is connected to the hvac unit before the duct detector which would delute any smoke from within the compartment. This new ducting needs to be connected to the hvac unit after the duct smoke detector. No testing was performed.
FIRE-Final Inspection8/24/20108/24/20108/25/2010PFAIL
DetailsTroy Cobbley
The west hvac unit tested ok. The east hvac unit would not go into heat mode like it did the day before so that it could be tested.
BLD-Final8/24/20108/24/20108/24/2010PNR
DetailsTom Arcoraci
Kent Phone #: ###-####
FIRE-Final Inspection8/20/20108/23/20108/23/2010AFAIL
DetailsTroy Cobbley
The east side duct smoke detector did not shut down the hvac unit immediately when tested. The west side hvac unit would not turn on for the testing.
BLD-Final8/20/20108/23/20108/23/2010ANR
DetailsTom Arcoraci
travis Phone #: ###-####
BLD-Final7/23/20107/26/20107/26/2010PPART
DetailsTom Arcoraci
James Phone #: ###-#### needs fire sign off
FIRE-Final Inspection7/23/20107/26/20107/26/2010AFAIL
DetailsTroy Cobbley
Upon review of the city approved plans there are two duct smoke detectors shown on the Mechanical sheets and they are installed as well. These two detectors will be required to be tested with the required remote annunciators or have engineer approval to delete since the drawings show the units at only 1700 cfm. All other items are ok.
FIRE-Final Inspection7/22/20107/22/20107/22/2010PFAIL
DetailsTroy Cobbley
Provide city approved plans, provide address and fire extinguisher as discussed.
BLD-Final7/21/20107/22/20107/22/2010ANR
DetailsTom Arcoraci
call 30 min prior to meet//Travis Shelton Phone #: ###-####
Zoning Approval7/22/20107/22/20107/22/2010 DONE
DetailsCody Riddle
Print Occupancy Form  7/22/2010  
BLD-Aging Inspection6/22/20106/22/20106/22/2010 PASS
DetailsTom Arcoraci
BLD-Framing/Rough-in4/21/20104/22/20104/22/2010PPART
DetailsTom Arcoraci
shane Phone #: ###-#### check truss buckets for girder at next inspection
BLD-Foundation3/18/20103/19/20103/19/2010APASS
DetailsTom Arcoraci
Re-enforcing-rebar inspection Phone #: ###-#### strata on site
BLD-Footing3/18/20103/18/20103/18/2010PPASS
DetailsTom Arcoraci
Re-enforcing-rebar inspection Phone #: ###-#### strata on site
Plan assigned to (JCM)11/12/2009 1/20/2010 PASS
DetailsJohn Menard
1/20/2010 08:49:31 JCM - activity updated through activity BLDA022 from case BLD09-02032.
Routing - PLANNING Land Div1/20/2010 1/20/2010 PASS
DetailsDave Abo
Parcels have been combined into one. New Tax Parcel Number is R5128000175.
Routing - PLAN CHECK1/20/2010 1/20/2010 PASS
DetailsJohn Menard
PLANS/APPL TAKEN TO FRONT DESK  1/20/2010 DONE
DetailsJohn Menard
Print Occupancy Form  1/20/2010 DONE
Permit Ready to Issue  1/20/2010 DONE
Issue PAID IN FULL permit  1/20/2010 DONE
Plan resubmittals received  1/11/2010  
DetailsJohn Menard
rec'd notice of buildable parcel for combining lots/parcel; taken to John M
Routing PW Environmental12/18/2009 12/18/2009 PASS
DetailsWalt Baumgartner
Approved - resubmittal sheets show secondary containment around sodium hypochlorite tank
Plan resubmittals received  12/18/2009 DONE
received transmittal letter and 2 sheets of P-102 - taken to john menard
Routing - PUBLIC WORKS12/18/2009 12/18/2009 PASS
DetailsBeverly Hall
Routing PW Drainage12/10/2009 12/17/2009 PASS
DetailsBrian Murphy
Plan resubmittals received  12/16/2009  
DetailsTisha Gallop
received transmittal, response letter, plan check corrections, ES Report about Skylights, two copies of sheets A1, A1.1, C-102; inserted by arch. rep. and taken back to Brian Murphy
Plan resubmittals received  12/15/2009  
DetailsTisha Gallop
received one copy of response letter and structural calculations, three copies of plan sheets C-502, A4; inserted by eng. rep.and taken back to Public Works.
Routing - PLAN CHECK12/2/2009 12/10/2009  
DetailsJohn Menard
Plan resubmittals received  12/9/2009  
DetailsTisha Gallop
received two copies of transmittal, O & M Manual, Drainage calcs, plan sheets C-101, C-102, C-501; inserted by eng. rep. and taken back to John Menard
Routing - FIRE11/25/200911/25/200912/2/2009 PASS
DetailsScott Arellano
Attached IFC comments to plans
1st review completed  12/2/2009 FAIL
Failed Public Works, Structural, Plumbing, Planning, Plan Check
Route to Impact Fee Review11/25/200912/1/200911/27/2009 PASS
DetailsCindy M. Gould
Plan resubmittals requested  11/25/2009 DONE
DetailsJohn Menard
E-mailed architect a copy of the plan review requesting revisions. JCM
Routing - PLAN CHECK11/24/2009 11/25/2009 FAIL
DetailsJohn Menard
Routing - PLANNING11/23/2009 11/24/2009 PASS
DetailsJoshua Johnson
Routing - PLUMBING11/23/2009 11/23/2009 PASS
DetailsBill VanDegrift
no plumbing
Routing Off Site - STRUCTURAL11/12/2009 11/23/2009 FAIL
DetailsJohn Menard
called Action Couriers for pick up - Received comment list from consulting structural engineer requesting revisions. JCM
Routing - Erosion and Sediment  11/23/2009 PASS
DetailsSteven Webb
ESC plan is approved along with the permit attached conditions. Certified RP required prior to start of work. Inform Boise City with the name of RP at ###-####. ESC09-00724
Plan resubmittals requested  11/23/2009 DONE
DetailsJohn Menard
E-mailed the engineer a copy of the structural comments requesting revisions. JCM
Routing - PUBLIC WORKS11/12/2009 11/20/2009 FAIL
DetailsConnie Baumgartner
Routing PW Drainage11/16/2009 11/20/2009 FAIL
DetailsBrian Murphy
O and M incomplete. BRIAN MURPHY ###-####
Routing - Addressing11/16/2009 11/16/2009 PASS
DetailsApril Wing
Routing - PLANNING Land Div11/12/2009 11/12/2009 FAIL
DetailsDave Abo
Applicant owns two parcels. Marty Santoya stated that the existing building would be torn down and a new structure would be buillt to replace it. The new building is one foot from the property line. Prior to issuing building permit, the two parcels must be combined. Called Nathaniel Runyan, JUB on 11/12/09
Plans ACCEPTED BY PLAN TECH  11/12/2009 DONE
Ok per John M for new construction
Pending Assignment by JCM11/12/2009 11/12/2009 BLDA
DetailsJohn Menard
11/12/2009 11:57:43 JCM - activity updated through activity BLDA166 from case BLD09-02032.
Application received 11/12/2009   
Routing - PUBLIC WORKS12/10/2009   FAIL
DetailsBeverly Hall
See Environmental notes.
Routing PW Environmental12/17/2009   FAIL
DetailsWalt Baumgartner
Must resubmit plan showing wall around hypochloride tank. Called JUB 12/17/09.
Routing - PLAN CHECK12/18/2009    
DetailsJohn Menard