DOC - Permit Expired | 8/3/2010 | 8/4/2010 | 8/4/2010 | A | PASS |
Tom Arcoraci
|
|
|
|
BLD-Aging Inspection | 8/3/2010 | 8/3/2010 | 8/3/2010 | | PART |
Tom Arcoraci
|
|
|
|
BLD-Aging Inspection | 6/1/2010 | 6/1/2010 | 6/3/2010 | | PART |
Tom Arcoraci
|
|
|
no inspection made
|
BLD-Aging Inspection | 4/1/2010 | 4/1/2010 | 4/1/2010 | | NR |
Tom Arcoraci
|
|
|
no inspections performed
|
Inspection Record Card- Bld | | | 12/31/2009 | | DONE |
Barbara Stitt
|
|
|
|
Permit Ready to Issue | | | 12/31/2009 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 12/31/2009 | | DONE |
Barbara Stitt
|
|
|
Called Doug Storey and told him that permit is ready & fees due///12-31-09 @ 1:50pm BAS
|
Issue PAID IN FULL permit | | | 12/31/2009 | | DONE |
Tisha Gallop
|
|
|
|
Routing - PLAN CHECK | 12/29/2009 | | 12/30/2009 | | PASS |
Tim L. Woodard
|
|
|
Approved w/conditions.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/30/2009 | | DONE |
Tim L. Woodard
|
|
|
|
Case Summary (BLD) | | | 12/30/2009 | | DONE |
Tim L. Woodard
|
|
|
|
Plan assigned to (TLW) | 12/7/2009 | | 12/30/2009 | | PASS |
Tim L. Woodard
|
|
|
12/30/2009 13:53:22 TLW - activity updated through activity BLDA022 from case BLD09-02160.
|
Routing - FIRE | 12/22/2009 | | 12/29/2009 | | PASS |
Scott Arellano
|
|
|
Attached updated IFC comments to plans. Fire sprinkler modifications are required. A seperate permit shall be obtained for this work. Final approval will be subject to satisfactory field inspection by the PDS Fire inspector.
|
Meeting | | | 12/28/2009 | | DONE |
Scott Arellano
|
|
|
Onsite meeting held with Karen (Representative from the property management company), Doug Storey (GC), Tim Frost (Fire Sprinkler Plans Examiner) and Mark Senteno (Fire Marshal) to discuss the existing fire sprinker system relative to the proposed HPS use by the new tenant. Modifications to the existing fire sprinkler system will be necessary to adequately protect the proposed High Piled storage use.
|
Telephone call | | | 12/22/2009 | | DONE |
Tim Frost
|
|
|
Phone Call with Bob Sommers Senior Engineer for Sherwin Williams
Explained the following to him:
- FM Data Sheet 8-30 requires a .30/3000 + 500 hose.
- IFC does not define roll carpet storage however, Rugs, foam backed is defined as a Class IV commodity.
- Class IV commodity defined in NFPA 13 for a rack up to 12' is Extra Hazard Group I which is a .30/2500 + 500 hose. Which corresponds to FM criteria.
- Since there is no exact criteria for roll carpet storage in the IFC I will apply IFC 102.7 and use FM Data Sheets.
- The existing system is calculated for a .20/1500 + 250 based upon a letter provided by Treasure Valley Fire Protection
- He asked what it was he needed to do. I said, Hire a fire protection contractor to evaluate the existing sprinkler system and determine what changes are required to achieve .30/3000 + 500 density.
Bob told me the following:
- The drawing is wrong it is not a warehouse even though the drawing is labeled 'Warehous Area" he says it is a store. Since it is a store he wants to treat it as Mercantile.
- The drawing is wrong there is no paint storage even though there is an elevation defining "Warehouse Paint Rack Elevation"
- The drawing is wrong there is no pallet rack even though the drawing indicates "Pallet Racks"
- The drawing is wrong the roll carpet storage will not exceed 12'
- The drawing is wrong there is no "Handstack Rack"
Conclusion:
There is no basis to detemine that this is a mercantile occupancy other then Bob saying "This is what we have always done in the past." Even if it was mercantile IFC: 903.2.6.1 would then pertain which sends you back to racks which sends you to .30/2500 + 500 hose
Follow Up:
I briefed Mark Senteno on the above phone conversation.
|
Routing - PLAN CHECK | 12/16/2009 | | 12/22/2009 | | PEND |
Tim L. Woodard
|
|
|
rerouted plans to fire. TLW
|
Plan resubmittals received | | | 12/22/2009 | | DONE |
Tim L. Woodard
|
|
|
Applicant submitted fire sprinkler analysis letter from Treasure Valley Sprinkler. TLW
|
Routing - FIRE | 12/14/2009 | | 12/16/2009 | | FAIL |
Scott Arellano
|
|
|
Faxed and emailed resubmittal items to applicant.
|
1st review completed | | | 12/16/2009 | | FAIL |
|
|
|
Failed Fire
|
Routing - PLAN CHECK | 12/7/2009 | | 12/14/2009 | | PASS |
Tim L. Woodard
|
|
|
Redlined Special Inspections Required on Bolting. TLW
|
Plans ACCEPTED BY PLAN TECH | | | 12/7/2009 | | DONE |
|
|
|
|
Application received | | 12/7/2009 | | | |
|
|
|
|