Permit Information
Permit NumberBLD09-02291
StatusFinaled
Name BIGHORN GROUP PREOFESSIONAL SERVICE
Site Address 500 E BAYBROOK CT
Project Namesupervalu
Customer Number 
ePlanReviewNo
Description
*( supervalu )* FPP permit Wall const. of aprox. 43 ln ft to create two rooms and two phone rooms on the first floor grid lines f/g to 2/4.Removal of selected doors and frames as well as finshes as noted on the plans.Walls will be nonconbustable partitions. minor ele work to be permited.
In code editions prior to the 1997 UBC stair enclosures were allowed to exit into corridors as long as the corridor doors were protected as required for a stair enclosure. (one-hour rated, 450 degree temperature rated in this case.) In code editions prior to the 1982 UBC stair enclosures were allowed to be one-hour rated in buildings 4 stories or less in height regardless of the Type of Construction.
Adjacent suites on the first floor will be required to provide one-hour, 450 degree temperature rated doors, where required in corridor on future permits. This building is NOT fire sprinklered, alarm modifcations will requirea permit from the fire planreview dept. 301
Contact Information
See Activities list for contact information
Color Key
Current location of plans being reviewed:  
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice5/28/20105/28/20106/1/2010 DONE
DetailsJim Storey
This permit finaled on the web by Craig Brown
BLD-Final5/26/20105/28/20105/28/2010APASS
DetailsJim Storey
Jim; Forest recently completed the life safety final for this Buidling- Riverview. I''d like to combine with another final at the main Supervalu Bldg. Please let me know atime Friday that works in your schedule so I can be ther.
Thanks Craig Inspection requested from web by: Craig Brown Phone #: ###-####
DOC - Permit Finaled5/28/20105/28/20105/28/2010PPASS
DetailsJim Storey
FIRE-Final Inspection5/19/20105/19/20105/20/2010PPASS
DetailsForrest France
Correction items finished, fire life safety finaled.
FIRE-Final Inspection5/14/20105/17/20105/17/2010PFAIL
DetailsTroy Cobbley
I called and left message on Craig's voice mail on the way and call when I arrived at the site. I asked for him with the security lady at the front deck but did not make contact. I noted that the exit sensor at the main exit has been disabled with a sign posted that says you must use your badge to exit the facility. No inspection was performed.
FIRE-Final Inspection4/16/20104/16/20104/16/2010AFAIL
DetailsForrest France
Access control doors are not in compliance with the functional aspects of item #3 per IFC 1008.1.3.4- Push to exit button must interrupt power for 30 sec. upon activation.
FIRE-Alarm Testing4/15/20104/15/20104/15/2010APART
DetailsForrest France
Relays at access control mag locks at both the south and west exits tested satisfactory for compliance with IFC 2006 sec. 1008.1.3.4 item #4.
FIRE-Final Inspection3/23/20103/23/20103/23/2010APART
DetailsForrest France
Final pending fire alarm permit work for relays at the main entry/exit door mag locks to release upon alarm per IFC requirements.
FIRE-Conference2/24/20102/24/20102/24/2010PDONE
DetailsForrest France
Regarding IFC 2006 sec. 1008.1.3.4 criteria for access controlled egress doors items #1 thru 6.
BLD-Wall cover1/28/20101/28/20101/28/2010PPASS
DetailsJim Storey
rated wall and above ceilling ok/ ok to cover framing.
BLD-Conference1/25/20101/25/20101/25/2010PPART
DetailsJim Storey
need to maintane rated loby wall above ceilling/ ok to rock rated infil. pending trades
Issue PAID IN FULL permit  1/19/2010 DONE
DetailsTisha Gallop
Route to Impact Fee Review12/29/20091/4/201012/29/2009 PASS
DetailsCindy M. Gould
Tenant improvement no impact fees
Plan assigned to (301)12/29/200912/29/200912/29/2009 PASS
DetailsJim Storey
12/29/2009 13:10:26 301 - activity updated through activity BLDA022 from case BLD09-02291.
Routing - FIRE12/29/200912/29/200912/29/2009 PASS
DetailsScott Arellano
PLANS/APPL TAKEN TO FRONT DESK  12/29/2009 DONE
Inspection Record Card- Bld  12/29/2009 DONE
Intake Approval  12/29/2009 PASS
1st review completed  12/29/2009 PASS
Routing - PLAN CHECK12/29/2009 12/29/2009 PASS
DetailsJim Storey
Inspection Record Card- Bld  12/29/2009 DONE
Telephone call  12/29/2009 DONE
Details
t/c w chris at ###-#### - permit ready and fees given
Permit Ready to Issue  12/29/2009 DONE
Details
Plans ACCEPTED BY PLAN TECH  12/28/2009 DONE
Application received 12/28/2009   
Routing - PLAN CHECK12/28/2009   PASS
DetailsJim Storey
sent to impact fee