Third Notice | | 3/15/2010 | 3/16/2010 | | DONE |
|
|
|
|
Second Notice | | 2/21/2010 | 3/10/2010 | | DONE |
|
|
|
|
First Notice | 2/2/2010 | 2/2/2010 | 2/11/2010 | | DONE |
Tom Arcoraci
|
|
|
|
BLD-Final | 2/1/2010 | 2/2/2010 | 2/2/2010 | A | PASS |
Tom Arcoraci
|
|
|
please call 20 min prior to meet you//###-#### Kelly
|
DOC - Permit Finaled | 2/2/2010 | 2/2/2010 | 2/2/2010 | P | PASS |
Tom Arcoraci
|
|
|
|
FIRE-Final Inspection | 2/1/2010 | 2/2/2010 | 2/2/2010 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed.
|
Issue PAID IN FULL permit | | | 2/1/2010 | | DONE |
Tisha Gallop
|
|
|
|
Plan assigned to (DRS) | 1/22/2010 | 1/22/2010 | 1/29/2010 | | PASS |
Dan Stuart
|
|
|
1/29/2010 11:04:42 DRS - activity updated through activity BLDA022 from case BLD10-00120.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/29/2010 | | PASS |
|
|
|
|
Inspection Record Card- Bld | | | 1/29/2010 | | DONE |
|
|
|
|
Telephone call | | | 1/29/2010 | | DONE |
|
|
|
left message w tim for kelly at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 1/29/2010 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 1/26/2010 | | 1/29/2010 | | PASS |
Dan Stuart
|
|
|
To permit desk to issue.
|
Plan resubmittals received | | | 1/27/2010 | | |
Tisha Gallop
|
|
|
received two copies of e-mail from Greg Patrick; letter from Treasure Valley Fire Protection, rack engineering detail, Project Start up For Special Inspection application, Bolt Inspection Report, Contractor Registration Declaration (same one as with application), and plan sheet MH-1; taken to Dan Stuart
|
Routing - FIRE | 1/25/2010 | | 1/26/2010 | | PASS |
Scott Arellano
|
|
|
These plans have NOT been approved for high piled storage. The class IV storage commodities shown on racks are not approved for heights above 12 feet. Final approval will be subject to satisfactory field inspection by the PDS Fire inspector.
|
1st review completed | | | 1/26/2010 | | FAIL |
Scott Arellano
|
|
|
Failed in Building review.
|
Routing - PLAN CHECK | 1/22/2010 | | 1/25/2010 | | FAIL |
Dan Stuart
|
|
|
Resubmittals required. Copy of plan review e-mailed to Debbie Gomez. Plans routed to fire code analyst for review.
|
Plan resubmittals requested | | | 1/25/2010 | | DONE |
|
|
|
Copy of plan review e-mailed to Debbie Gomez.
|
Application received | | 1/22/2010 | 1/22/2010 | | DONE |
Tisha Gallop
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 1/22/2010 | | DONE |
Tisha Gallop
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 1/22/2010 | | DONE |
Tisha Gallop
|
|
|
|