Third Notice | | 6/10/2010 | 7/9/2010 | | DONE |
|
|
|
|
Third Notice | | 5/15/2010 | 5/27/2010 | | DONE |
|
|
|
faxed
|
Second Notice | | 5/6/2010 | 5/10/2010 | | DONE |
|
|
|
|
First Notice | | 4/19/2010 | 4/26/2010 | | DONE |
|
|
|
|
Permanent Occupancy UNPAID FEE | | | 4/9/2010 | | DONE |
|
|
|
|
FIRE-Final Inspection | 4/7/2010 | 4/7/2010 | 4/7/2010 | A | PASS |
Forrest France
|
|
|
Correction notice item finished, fire life safety final approved.
|
BLD-Other | 4/7/2010 | 4/7/2010 | 4/7/2010 | A | DONE |
Forrest France
|
|
|
On site functional testing of the relocated automatic fire door completed satisfactory and within allowable closure rates per NFPA 80.
|
BLD-Final | 4/7/2010 | 4/7/2010 | 4/7/2010 | A | PASS |
Jim Storey
|
|
|
final ok card not avalable to sign.
|
BLD-Other | 4/7/2010 | 4/7/2010 | 4/7/2010 | A | PASS |
Jim Storey
|
|
|
fire door actuation test.
|
BLD-Conference | 4/6/2010 | 4/6/2010 | 4/6/2010 | A | PASS |
Jim Storey
|
|
|
|
BLD-Conference | 4/5/2010 | 4/6/2010 | 4/6/2010 | P | CANC |
Jim Storey
|
|
|
|
FIRE-Final Inspection | 3/26/2010 | 3/26/2010 | 3/26/2010 | A | PART |
Forrest France
|
|
|
ref. NFPA 80 regarding min. and max closure rate for the relocated fire door- (6"/sec. - 24"/sec.).
|
BLD-Final | 3/25/2010 | 3/25/2010 | 3/25/2010 | P | PART |
Jim Storey
|
|
|
mike Phone #: ###-#### ti ok to occupnance work on fire shudder in progress. temp isued.
|
FIRE-Final Inspection | 3/24/2010 | 3/25/2010 | 3/25/2010 | A | PART |
Forrest France
|
|
|
Fire life safety inspection completed satisfactory, noted corrections finished within the tenant space. Final pending completion and testing of the relocated automatic fire door at the exterior canopy per scope of pemit work.
|
FIRE-Conference | 3/24/2010 | 3/24/2010 | 3/24/2010 | P | DONE |
Forrest France
|
|
|
On site visit regarding fire life safety inspection items including exit signs, EM lights, door hardware, etc.
|
BLD-Conference | 3/24/2010 | 3/24/2010 | 3/24/2010 | A | PASS |
Jim Storey
|
|
|
door being relocated
|
BLD-Conference | 3/22/2010 | 3/22/2010 | 3/22/2010 | A | PASS |
Jim Storey
|
|
|
reviewed relocation of 2 hr fire shudder for compliant applacation to protect canopy opening.
|
BLD-Framing/Rough-in | 3/16/2010 | 3/17/2010 | 3/17/2010 | A | PASS |
Jim Storey
|
|
|
mike Phone #: ###-####
|
Telephone call | | | 3/16/2010 | | DONE |
|
|
|
t/c w pat at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 3/16/2010 | | DONE |
|
|
|
|
Issue PAID IN FULL permit | | | 3/16/2010 | | DONE |
Tisha Gallop
|
|
|
|
Plan assigned to (CJW) | 2/24/2010 | | 3/15/2010 | | PASS |
Carl Westfall
|
|
|
3/15/2010 13:34:50 CJW - activity updated through activity BLDA022 from case BLD10-00368.
|
Routing - PLAN CHECK | 3/4/2010 | | 3/15/2010 | | PASS |
Carl Westfall
|
|
|
Drawings approved after the resubmittal review.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/15/2010 | | DONE |
|
|
|
|
Print Occupancy Form | | | 3/15/2010 | | DONE |
|
|
|
|
Plan resubmittals received | | | 3/12/2010 | | |
|
|
|
received 2 copies of sheet A1.0 sent to Carl W
|
Plan resubmittals received | | | 3/10/2010 | | DONE |
|
|
|
received 1 response letter,and 2 copies of sheet A1.1 sent to Carl W.
|
Plan resubmittals received | | | 3/5/2010 | | |
Tisha Gallop
|
|
|
received response letter and two copies of plan sheets A1.0, A1.1; taken to Carl Westfall
|
Routing - FIRE | 3/2/2010 | 3/2/2010 | 3/4/2010 | | PASS |
Scott Arellano
|
|
|
Attached IFC comments to plans
|
1st review completed | | | 3/4/2010 | | FAIL |
|
|
|
Failed Plan Check
|
Route to Impact Fee Review | 3/2/2010 | 3/5/2010 | 3/3/2010 | | PASS |
Cindy M. Gould
|
|
|
Tenant improvement no impact fees
|
Routing - PLAN CHECK | 2/25/2010 | | 3/2/2010 | | FAIL |
Carl Westfall
|
|
|
The IBC plan review was started on February 26, 2010 and finished on March 2, 2010. Revised drawings were required. See the plan review report.
|
Routing - PUBLIC WORKS | 2/24/2010 | | 2/25/2010 | | PASS |
Connie Baumgartner
|
|
|
|
Routing - Erosion and Sediment | | | 2/25/2010 | | PASS |
Steven Webb
|
|
|
ESC plan waiver is approved according to the attached conditions. ESC10-00154
|
Routing PW Sewer Rating | 2/25/2010 | | 2/25/2010 | | PASS |
Connie Baumgartner
|
|
|
|
Routing - Addressing | 2/24/2010 | | 2/24/2010 | | PASS |
April Wing
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 2/24/2010 | | DONE |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 2/24/2010 | | DONE |
|
|
|
|
Pending Assignment by JCB | 2/24/2010 | | 2/24/2010 | | DONE |
Jason Blais
|
|
|
|
Application received | | 2/23/2010 | 2/23/2010 | | DONE |
Alexandra L. DeYoung
|
|
|
|