BLD-Final | 4/21/2010 | 4/22/2010 | 4/22/2010 | A | PASS |
Mike Jordan
|
|
|
Kelly Phone #: ###-####. Ok for permanant occupancy.
|
Permanent Occupancy | | | 4/22/2010 | | DONE |
Tisha Gallop
|
|
|
|
FIRE-Final Inspection | 4/20/2010 | 4/21/2010 | 4/21/2010 | P | PASS |
Troy Cobbley
|
|
|
Life safety passed.
|
BLD-Final | 4/16/2010 | 4/19/2010 | 4/19/2010 | P | NR |
Mike Jordan
|
|
|
Kelly Phone #: ###-####. lIfe/safety failed.
|
FIRE-Final Inspection | 4/16/2010 | 4/19/2010 | 4/19/2010 | A | FAIL |
Troy Cobbley
|
|
|
Remove the manual locks from the doors as indicated in red on the city approved plans, mount the fire extinguishers as discussed and marked in red on the city approved plans and repair/replace and test the exit signs and emergency lights.
|
Issue PAID IN FULL permit | | | 4/16/2010 | | DONE |
Tisha Gallop
|
|
|
|
Plan assigned to (SRZ) | 4/15/2010 | 4/15/2010 | 4/15/2010 | | PASS |
Sam Zahorka
|
|
|
4/15/2010 11:58:26 SRZ - activity updated through activity BLDA022 from case BLD10-00801.
|
Plan assigned to (CDM) | 4/14/2010 | 4/14/2010 | 4/15/2010 | | DEFR |
Carl D Madsen
|
|
|
Deferred to SRZ
|
Routing - PLAN CHECK | 4/15/2010 | | 4/15/2010 | | PASS |
Sam Zahorka
|
|
|
|
Case Summary (BLD) | | | 4/15/2010 | | DONE |
Sam Zahorka
|
|
|
|
1st review completed | | | 4/15/2010 | | DONE |
Sam Zahorka
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/15/2010 | | DONE |
Sam Zahorka
|
|
|
|
Print Occupancy Form | | | 4/15/2010 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 4/15/2010 | | DONE |
|
|
|
|
Telephone call | | | 4/15/2010 | | DONE |
|
|
|
called Kelly Cromwell permit ready 4-15-10 pdf
|
Application received | | 4/14/2010 | | | |
|
|
|
|