First Notice | | 9/12/2010 | 9/23/2010 | | DONE |
|
|
|
|
Print Occupancy Form | | | 9/2/2010 | | DONE |
|
|
|
|
Permanent Occupancy | | | 9/2/2010 | | DONE |
|
|
|
|
BLD-Final | 8/31/2010 | 9/1/2010 | 9/1/2010 | P | PASS |
Tom Arcoraci
|
|
|
Mike Phone #: ###-####
|
BLD-Final | 9/1/2010 | 9/1/2010 | 9/1/2010 | P | PASS |
Tom Arcoraci
|
|
|
Mike Phone #: ###-#### no stove installed at this time
|
FIRE-Final Inspection | 8/31/2010 | 9/1/2010 | 9/1/2010 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed
|
FIRE-Final Inspection | 8/30/2010 | 8/31/2010 | 8/31/2010 | A | CANC |
Troy Cobbley
|
|
|
Cancel per Mike
|
BLD-Final | 8/27/2010 | 8/30/2010 | 8/30/2010 | P | NR |
Tom Arcoraci
|
|
|
Mike Phone #: ###-####
|
FIRE-Final Inspection | 8/27/2010 | 8/30/2010 | 8/30/2010 | A | FAIL |
Troy Cobbley
|
|
|
Provide building address, mount fire extinguisher, provide automatic flush bolts for the inactive leaf of the double doors from the BreakRoom, remove the keyed hardware from one of the two main exit doors and provide with single action hardware. The door that is to remain keyed needs the sticker provided as discussed.
|
BLD-Energy code compliance | 7/28/2010 | 7/29/2010 | 7/29/2010 | A | PASS |
Tom Arcoraci
|
|
|
zack - please call when inspection is completed Phone #: ###-####
|
BLD-Framing/Rough-in | 7/28/2010 | 7/29/2010 | 7/29/2010 | A | PASS |
Tom Arcoraci
|
|
|
zack - please call when inspection is completed Phone #: ###-####
|
BLD-Framing/Rough-in | 7/26/2010 | 7/26/2010 | 7/26/2010 | P | PART |
Tom Arcoraci
|
|
|
zack - please call when you are finished Phone #: ###-#### correction notice posted
|
OVERRIDE | | | 7/14/2010 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 7/14/2010 | | DONE |
Tisha Gallop
|
|
|
|
Routing - PLAN CHECK | 6/24/2010 | | 7/14/2010 | | PASS |
Carl D Madsen
|
|
|
|
Print Occupancy Form | | | 7/14/2010 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 7/14/2010 | | DONE |
Tisha Gallop
|
|
|
|
Plan assigned to (CDM) | 6/23/2010 | 6/23/2010 | 7/13/2010 | | PASS |
Carl D Madsen
|
|
|
7/13/2010 14:06:29 CDM - activity updated through activity BLDA022 from case BLD10-01391.
|
Routing - PLANNING | 7/13/2010 | | 7/13/2010 | | PASS |
Josh Wilson
|
|
|
|
Routing - FIRE | | | 7/13/2010 | | PASS |
|
|
|
Verify in field CDM
|
1st review completed | | | 7/13/2010 | | FAIL |
|
|
|
Landing and step elevation required for ne doors. Called Robert Powell at Evans construction and requested elevation for the landing and step 7-12-10 cdm
|
Case Summary (BLD) | | | 7/13/2010 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/13/2010 | | |
|
|
|
|
Routing - PUBLIC WORKS | 6/23/2010 | | 6/24/2010 | | PASS |
Beverly Mountain
|
|
|
|
Routing - Addressing | 6/24/2010 | | 6/24/2010 | | PASS |
Terry Records
|
|
|
|
Application received | | 6/17/2010 | 6/23/2010 | | DONE |
Tisha Gallop
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 6/23/2010 | | DONE |
Tisha Gallop
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 6/23/2010 | | DONE |
Tisha Gallop
|
|
|
|
Intake Approval | | | 6/18/2010 | | FAIL |
|
|
|
Zoning certificate required see checklist 6-17-10 CDM
|