Second Notice | | 8/23/2010 | 8/19/2010 | | DONE |
|
|
|
|
First Notice | | 8/8/2010 | 8/13/2010 | | DONE |
|
|
|
|
BLD-Final | 7/28/2010 | 7/29/2010 | 7/29/2010 | A | PASS |
Jim Sly
|
|
|
Junior Phone #: ###-#### OK for Perm Occ.
|
Permanent Occupancy UNPAID FEE | | | 7/29/2010 | | DONE |
Tisha Gallop
|
|
|
|
FIRE-Final Inspection | 7/28/2010 | 7/29/2010 | 7/28/2010 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed.
|
FIRE-Final Inspection | 7/26/2010 | 7/26/2010 | 7/26/2010 | P | CANC |
Troy Cobbley
|
|
|
Wrong permit called in.
|
BLD-Final | 7/21/2010 | 7/22/2010 | 7/22/2010 | P | CANC |
Mike Jordan
|
|
|
dennis Phone #: ###-#### Inspection cancelled from web by: Barbara Stitt
|
FIRE-Final Inspection | 7/21/2010 | 7/22/2010 | 7/22/2010 | A | FAIL |
Troy Cobbley
|
|
|
Repair/test all of the exit signs and emergency lights, provide exit sign leading into room 102 per the plans, remove the manual flush bolts at the double doors to room 102, remove the manual deadbolts/steel bars and provide approved single action hardware on all three of the rear exit doors, remove the keyed hardware and provide approved single action hardware on the north/front exit door or remove hardware completely.
|
Issue PAID IN FULL permit | | | 7/13/2010 | | DONE |
Tisha Gallop
|
|
|
|
Print Occupancy Form | | | 7/9/2010 | | DONE |
|
|
|
|
Telephone call | | | 7/9/2010 | | DONE |
|
|
|
left vm for jeff at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 7/9/2010 | | DONE |
|
|
|
|
Plan assigned to (CDM) | 6/30/2010 | 6/30/2010 | 7/8/2010 | | DONE |
Carl D Madsen
|
|
|
|
Routing - PLAN CHECK | 7/7/2010 | | 7/8/2010 | | PASS |
Carl D Madsen
|
|
|
|
Routing - FIRE | | | 7/8/2010 | | PASS |
|
|
|
Verify in field CDM
|
1st review completed | | | 7/8/2010 | | DONE |
|
|
|
|
Case Summary (BLD) | | | 7/8/2010 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/8/2010 | | |
|
|
|
|
Routing - PUBLIC WORKS | 6/30/2010 | | 7/7/2010 | | PASS |
Beverly Mountain
|
|
|
|
Routing PW Sewer Rating | 7/6/2010 | | 7/6/2010 | | PASS |
Connie Baumgartner
|
|
|
|
Routing - Addressing | 7/2/2010 | | 7/2/2010 | | PASS |
April Wing
|
|
|
|
Application received | | 6/23/2010 | 6/30/2010 | | DONE |
Tisha Gallop
|
|
|
need signature page of application, plan check fee paid and Design Profesional info on form #304.
|
Plans ACCEPTED BY PLAN TECH | | | 6/30/2010 | | DONE |
Tisha Gallop
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 6/30/2010 | | DONE |
Tisha Gallop
|
|
|
|
Intake Approval | | | 6/30/2010 | | PASS |
Tisha Gallop
|
|
|
|
Telephone call | | | 6/29/2010 | | DONE |
Tisha Gallop
|
|
|
Called Jeff Likes about incomplete application and plan check fee, he said still waiting. Notified him plans would not be reviewed until the above was done.
|