Permit Information
Permit NumberBLD11-00044
StatusFinaled
Name ENVISION 360 INC
Site Address 5982 E MILLET DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Permit for the construction of a new 4,537 sq. ft., two story (first story 2,882 sq. ft., second story 1,655 sq. ft.) single family dwelling with 4 bedrooms, 3 1/2 bathrooms, approximately 260 sq. ft. of covered patio area and a 1006 sq. ft. attached garage per the approved plans. This structure is located in WUI zone B abutting undeveloped area an requires a class A roof and noncombustible exterior siding materials. A letter from the applicant’s geotechnical engineer indicating that the footing sub-grade is acceptable must be approved by Public Works prior to scheduling a footing inspection. Call Terry Records at 384-3946. A-1 zoning and setbacks per planning. CDM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final8/12/20118/15/20118/15/2011APASS
DetailsDave Hannah
Chad Phone #: ###-####
DOC - Permit Finaled8/15/20118/15/20118/15/2011PPASS
DetailsDave Hannah
BLD-Grading Inspection8/12/20118/12/20118/12/2011ADONE
DetailsTerry Records
Final grading and drainage approved.
BLD-Energy code compliance4/22/20114/22/20114/22/2011PPASS
DetailsJim Storey
BLD-Energy code compliance4/21/20114/22/20114/22/2011ADEFR
DetailsJim Storey
chad Phone #: ###-####
BLD-Framing/Rough-in4/20/20114/20/20114/21/2011PPART
DetailsDave Hannah
CHAD (CONF ,SHEER & RI) With ENG 4 PM Phone #: ###-#### ok to cover ext shear was renailed and is per city approved plans framing ok all but for one hold down on se wall right of fire place needs to be instaled framing contractor builder and the builders engineer all on site for this inspection. engineer ok stru changes made and was ok with framing energy star inspector also on site walking project . Troy with boise city mec inspection also on site has several items said it was ok to insulate but dont cover until he signs off so ok to insulate.
BLD-Framing/Rough-in4/15/20114/15/20114/15/2011PFAIL
DetailsDave Hannah
CHAD Phone #: ###-#### shear nailing on ext not per plan do not cover
BLD-Footing3/9/20113/9/20113/9/2011PPASS
DetailsDave Hannah
BLD-Footing3/7/20113/8/20113/8/2011ANR
DetailsDave Hannah
BILL Phone #: ###-#### footings and site are very muddy contractor will wait for site to dry out so they dont have to remove bar to clean out
BLD-Footing3/4/20113/4/20113/7/2011PCANC
DetailsDave Hannah
aaron Phone #: ###-####
PubWorks Subgrade Approval3/4/20113/4/20113/4/2011 DONE
DetailsTerry Records
Footing subgrade approved by the geotechnical engineer
BLD-Footing3/2/20113/3/20113/3/2011PCANC
DetailsDave Hannah
BILL Phone #: ###-####
Issue PAID IN FULL permit  2/8/2011 DONE
Issue PAID IN FULL permit  2/8/2011 DONE
Plan assigned to (CDM)1/13/20111/13/20112/1/2011 DONE
DetailsCarl D Madsen
Routing - PLAN CHECK2/1/2011 2/1/2011 PASS
DetailsCarl D Madsen
Case Summary (BLD)  2/1/2011 DONE
PLANS/APPL TAKEN TO FRONT DESK  2/1/2011  
Inspection Record Card- Bld  2/1/2011 DONE
Permit Ready to Issue  2/1/2011 DONE
Telephone call  2/1/2011 DONE
2-1-11 called Chad permit ready and fee given ///dld
Routing - MECHANICAL1/13/2011 1/31/2011 PASS
DetailsTroy James
1. Need components construction data.
2. Need Right J worksheet for the entire house.
3. Wrong method used on design info./use simplified.
4. Need static pressure for heating equipment.
5. Need expanded performance data.
6. Furnace location for second floor? If in attic, the btu load is to low.
7. Air conditioner location for upstairs furnace?
8. AED assessment not required for plan review.
9. This is not a complete review due to missing information.

Routing - PLAN CHECK1/24/2011 1/30/2011 FAIL
DetailsCarl D Madsen
2009 Res-Check and additional engineers stamp is required.
Sent E-Mail to Chad at Envision Homes 1-30-11 CDM
1st review completed  1/30/2011 FAIL
Current Res-Check required and additional engineers stamp is required as well as mechanical sign off. CDM
Routing - FIRE  1/24/2011 PASS
DetailsScott Arellano
No comments attached.
Routing - Erosion and Sediment1/19/2011 1/20/2011 PASS
DetailsSteven Webb
ESC plan is approved according to the ESC plan and ESC permit conditions. ESC11-00020
Route to Impact Fee Review1/10/20111/13/20111/19/2011 PASS
DetailsCindy M. Gould
Routing - PLANNING1/13/2011 1/13/2011 PASS
DetailsCody Riddle
Construction subject to standards of the WUI Valley zone.
Routing - PUBLIC WORKS  1/13/2011 PASS
DetailsConnie Baumgartner
Routing - Addressing1/11/2011 1/13/2011 PASS
DetailsTerry Records
Routing PW Grading-Hillside1/11/2011 1/13/2011 PASS
DetailsTerry Records
Approved as category 1 by CFH10-00030
Recd Pcfee & Taken To Pln CK  1/11/2011 DONE
DetailsBarbara Stitt
Intake Approval  1/10/2011 PASS
DetailsBarbara Stitt
Application received 1/7/20111/7/2011 DONE
DetailsBarbara Stitt
Plans ACCEPTED BY PLAN TECH  1/7/2011 DONE
DetailsBarbara Stitt
Routing - PLAN CHECK     
DetailsCarl D Madsen
Carl Madsen