Third Notice | | 10/14/2011 | 10/18/2011 | | DONE |
|
|
|
|
Third Notice | | 8/30/2011 | 9/29/2011 | | DONE |
|
|
|
mailed to GC
|
Second Notice | | 8/12/2011 | 8/25/2011 | | DONE |
Christina Prado
|
|
|
Mailed 8-25-2011
|
First Notice | | 7/21/2011 | 8/2/2011 | | DONE |
|
|
|
|
Permanent Occupancy | | | 7/11/2011 | | DONE |
Christina Prado
|
|
|
|
BLD-Final | 7/6/2011 | 7/7/2011 | 7/7/2011 | A | PASS |
Tom Arcoraci
|
|
|
Jeff Phone #: ###-####
|
FIRE-Final Inspection | 7/6/2011 | 7/6/2011 | 7/6/2011 | P | PASS |
Forrest France
|
|
|
Noted correction items finished. Life safety passed.
|
FIRE-Final Inspection | 6/20/2011 | 6/21/2011 | 6/21/2011 | P | FAIL |
Forrest France
|
|
|
Need to provide approved hardware at three doors, missing one exit sign per plan, two exit signs are not functional on battery backup, main door needs "door to remain..." signage, missing fire extinguisher posted with current tag. Discussed permit documents, plan review, approved drawings, and code conditions with tenant rep.
|
FIRE-Conference | 3/21/2011 | 3/21/2011 | 3/21/2011 | P | DONE |
Forrest France
|
|
|
Discussion with tenant on site regarding trade permit inspections, project approvals, fire life safety items, etc.
|
BLD-Framing/Rough-in | 3/15/2011 | 3/15/2011 | 3/15/2011 | P | PASS |
Tom Arcoraci
|
|
|
###-####
|
Issue & PRINT permit | | | 2/11/2011 | | DONE |
Christina Prado
|
|
|
meant to select Issue & Print paid in full permit
|
Plan assigned to (CDM) | 1/11/2011 | 1/11/2011 | 1/24/2011 | | DONE |
Carl D Madsen
|
|
|
|
Routing - PLAN CHECK | 1/24/2011 | | 1/24/2011 | | PASS |
Carl D Madsen
|
|
|
|
Case Summary (BLD) | | | 1/24/2011 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/24/2011 | | |
|
|
|
|
Print Occupancy Form | | | 1/24/2011 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 1/24/2011 | | DONE |
Tisha Gallop
|
|
|
|
Telephone call | | | 1/24/2011 | | DONE |
Tisha Gallop
|
|
|
called Rob Thronton and told him permit is ready, fees and need GC/RCE
|
Plan resubmittals received | | | 1/21/2011 | | DONE |
Tisha Gallop
|
|
|
received transmittal, response and two copies of plan sheets G-001, A-101, A-102; taken to Carl Madsen
|
Routing - PLAN CHECK | 1/11/2011 | | 1/20/2011 | | FAIL |
Carl D Madsen
|
|
|
Sent E-Mail to Rob Thornton 1-20-10
|
Routing - FIRE | | | 1/20/2011 | | PASS |
|
|
|
Verify in field CDM
|
1st review completed | | | 1/20/2011 | | FAIL |
|
|
|
|
Application received | | 1/11/2011 | 1/11/2011 | | DONE |
Tisha Gallop
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 1/11/2011 | | DONE |
Tisha Gallop
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 1/11/2011 | | DONE |
Tisha Gallop
|
|
|
|