Print Statement | | | 12/29/2011 | | DONE |
|
|
|
|
FIRE-Final Inspection | 8/26/2011 | 8/29/2011 | 8/31/2011 | A | PASS |
Forrest France
|
|
|
Fire life safety passed final inspection.
|
BLD-Final | 8/29/2011 | 8/30/2011 | 8/30/2011 | A | PASS |
Jim Sly
|
|
|
Wes Smith Phone #: ###-####
|
DOC - Permit Finaled | 8/30/2011 | 8/30/2011 | 8/30/2011 | P | PASS |
Jim Sly
|
|
|
|
BLD-Final | 8/25/2011 | 8/26/2011 | 8/29/2011 | P | CANC |
Jim Sly
|
|
|
wes - ###-####
|
FIRE-Final Inspection | 8/25/2011 | 8/26/2011 | 8/26/2011 | A | DEFR |
Forrest France
|
|
|
|
Override - Parcel Holds | | | 8/25/2011 | | |
|
|
|
|
Override - Parcel Holds | | | 8/25/2011 | | |
|
|
|
|
Override - Parcel Holds | | | 8/25/2011 | | |
|
|
|
|
Override - Parcel Holds | | | 8/25/2011 | | |
|
|
|
|
FIRE-Sprinkler Rough-in | 6/3/2011 | 6/6/2011 | 6/6/2011 | A | PART |
Forrest France
|
|
|
Preliminary overhead inspection for fire sprinkler work at the new server room double interlock preaction system. Discussed plan review schedule, hydrostatic testing, heat at the riser room, seismic issues, as-builts for field mods, system impairments, cover inspections, etc.
|
FIRE-Conference | 6/3/2011 | 6/3/2011 | 6/3/2011 | A | DONE |
Forrest France
|
|
|
Regarding project related fire sprinkler work.
|
BLD-Framing/Rough-in | 5/6/2011 | 5/6/2011 | 5/6/2011 | P | PASS |
Jim Sly
|
|
|
WES Phone #: ###-####
|
Issue PAID IN FULL permit | | | 4/20/2011 | | DONE |
Tisha Gallop
|
|
|
|
Plan assigned to (SRZ) | 3/23/2011 | 3/23/2011 | 4/15/2011 | | PASS |
Sam Zahorka
|
|
|
|
Routing - PLAN CHECK | 4/13/2011 | | 4/15/2011 | | PASS |
Sam Zahorka
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/15/2011 | | DONE |
Sam Zahorka
|
|
|
|
Inspection Record Card- Bld | | | 4/15/2011 | | DONE |
|
|
|
|
Telephone call | | | 4/15/2011 | | DONE |
|
|
|
left vm for john - permit ready and fees given
|
Permit Ready to Issue | | | 4/15/2011 | | DONE |
|
|
|
|
Routing - FIRE | 4/11/2011 | | 4/13/2011 | | PASS |
Scott Arellano
|
|
|
Attached IFC comments to plans
|
1st review completed | | | 4/13/2011 | | PASS |
|
|
|
|
Case Summary (BLD) | | | 4/11/2011 | | DONE |
Sam Zahorka
|
|
|
|
Routing - PLAN CHECK | 4/1/2011 | | 4/11/2011 | | PASS |
Sam Zahorka
|
|
|
Sam Zahorka
|
Routing - PLANNING | 3/31/2011 | | 4/1/2011 | | PASS |
Josh Wilson
|
|
|
DRH10-308 Josh Wilson
|
Routing - MECHANICAL | 3/28/2011 | | 3/31/2011 | | PASS |
Troy James
|
|
|
|
Routing - PLUMBING | 3/25/2011 | | 3/28/2011 | | PASS |
Bill VanDegrift
|
|
|
traps required on sumps
|
Routing - Erosion and Sediment | 3/25/2011 | | 3/25/2011 | | PASS |
Steven Webb
|
|
|
ESC plan waiver is approved according to the ESC permit conditions. ESC11-00151
|
Routing - PUBLIC WORKS | | | 3/25/2011 | | PASS |
|
|
|
|
Routing PW Sewer Rating | 3/25/2011 | | 3/25/2011 | | PASS |
Connie Baumgartner
|
|
|
|
Routing PW Environmental | 3/25/2011 | | 3/25/2011 | | PASS |
Walt Baumgartner
|
|
|
Facility operates under sewer discharge permit issued by PW. Plans reviewed by Pretreament Group. OK
|
Routing - Addressing | 3/24/2011 | | 3/24/2011 | | PASS |
Terry Records
|
|
|
|
Application received | | 3/23/2011 | 3/23/2011 | | DONE |
Tisha Gallop
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 3/23/2011 | | DONE |
Tisha Gallop
|
|
|
per Ron Hill assign to SRZ and this routing.
|
Recd Pcfee & Taken To Pln CK | | | 3/23/2011 | | DONE |
Tisha Gallop
|
|
|
|