Permit Information
Permit NumberBLD11-01031
StatusFinaled
Name CM COMPANY
Site Address 130 E MALLARD DR
Project NamePlaza Apartments
Customer Number 
ePlanReviewNo
Description
(PLAZA APARTMENTS – FLOOR JOIST HANGER REPAIRS) To repair a portion of the existing floor system due to floor joist hangers failing. PLAN MODIFICATION 1-17-12 – Modification submitted to include additional structural engineering onto this permit. Additional engineering includes: grid “M” beam replacement, grid “G” beam replacement, wood column repairs, wood joist replacement, and overhead walkway deck calculations. **TLW** Work to include: Removal of sheetrock and installation of new ledger support. Approved per engineered plans, plan review report, and structural calculations. PLAN MODIFICATION 1-17-12 – Modification submitted to include additional structural engineering onto this permit. Additional engineering includes: grid “M” beam replacement, grid “G” beam replacement, wood column repairs, wood joist replacement, and overhead walkway deck calculations. **TLW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Second Notice 5/3/20134/29/2013 DONE
First Notice3/29/20133/29/20134/23/2013 DONE
DetailsTom Arcoraci
Faxed 4-23-13
BLD-Other3/8/20133/29/20133/29/2013ADONE
DetailsTom Arcoraci
Follow up..Check status and maintenance
DOC - Permit Finaled3/29/20133/29/20133/29/2013PPASS
DetailsTom Arcoraci
BLD-Final3/29/20133/29/20133/29/2013PPASS
DetailsTom Arcoraci
Follow up..Check status and maintenance ok
Plan Reviewer's activity  3/7/2013 DONE
DetailsTim L. Woodard
A conference was held between Jason Blais, Jim Storey, and myself to evaluate Scott Soule's Final Structural Letter (Attached to this case) we will accept it with the understanding that Scott Soule's instructions of continual maintenance will be followed through with. If we come to find that maintenance is not be done and the issues begin to reappear we will reevaluate this decision and possibly pull the Certificate of Occupancy. TLW
Plan resubmittals received  2/6/2013 DONE
DetailsJason Blais
Received final letter from structural engineer. Letter attached to this case.
BLD-Conference10/31/201211/1/201211/1/2012APASS
DetailsJim Storey
ben ###-#### fire resiatave membrane complet and firestopping done / walkway skim coat in progress ok will be complet in aprox. 1 wk.
BLD-Conference10/31/201210/31/201210/31/2012PDEFR
DetailsTom Arcoraci
ben Phone #: ###-####
BLD-Other9/13/20129/14/20129/14/2012APASS
DetailsJim Storey
structural to cover basement ceiling, and planter repairs//Ben Mclenna Phone #: ###-#### framing and water mangment of planters tested and aproved for gyp aplacation of ceilling .
Plan Reviewer's activity  7/30/2012 DONE
DetailsJason Blais
Structural Engineer Progress Letter attached to this case.
BLD-Other7/17/20127/18/20127/18/2012PPASS
DetailsJim Storey
Status update? meet ben to review job progress. all post and beam const. complet per engineer of records oversite. membrane and diphram installed except for one area pending observation of joist uncovered that may need replaced. scott will be by the afternoon to make this discition.. walkways framed out and ready for membrane as son as the last colm. is stablaized. letter will be forthcomimg from scott upon completion fof all strucrual observation.
CHANGE STATUS TO (ISS)  5/4/2012 DONE
DetailsChristina Prado
Routing Off Site - STRUCTURAL5/1/2012 5/3/2012 PASS
DetailsTim L. Woodard
Routed to Engineer via: email as discussed with representive at out source agency. Resubmittals were 4 8 1/2 by 11 inch sheets of paper. TLW
Inspection Record Card- Bld  5/3/2012 DONE
DetailsChristina Prado
PLANS/APPL TAKEN TO FRONT DESK  5/3/2012 DONE
DetailsTim L. Woodard
Override - Parcel Holds  5/3/2012  
Permit Ready to Issue  5/3/2012 DONE
DetailsTisha Gallop
Telephone call  5/3/2012 DONE
DetailsTisha Gallop
called John Price and told him plan mod was ready and fees due
Plan assigned to (TLW)4/20/2012 5/3/2012 PASS
DetailsTim L. Woodard
Plan Modification submitted 4-20-12
Plan resubmittals received  5/1/2012  
DetailsTim L. Woodard
2 copies of response comments dated 4-30-12 from Scott Soule, 2 copies of structural calcs taken to Tim Woodards desk
Routing - PLAN CHECK4/20/2012 4/25/2012 FAIL
DetailsTim L. Woodard
Address corrections from engineer. TLW
Routing Off Site - STRUCTURAL4/23/2012 4/25/2012 FAIL
DetailsTim L. Woodard
Reviewed failed. Corrections forwarded to the engineer and Ben at Parklane. TLW
Telephone call  4/23/2012 DONE
DetailsTisha Gallop
called Action Couriers for pick up
Plan Modification Accepted  4/20/2012 DONE
DetailsBarbara Stitt
Plan modification accepted for the revised detail of beam repair on grid line M. 3 copies of sheets A2.0 & A10.0, 3 copies of structural calcs, and app were submitted with no change of value. Routed to Tim Woodard
Telephone call  4/5/2012 DONE
Called structural engineer for status on repairs. Repairs are progressing. Recent meeting occurred within the last two weeks between engineer and Parklane Management on status and remaining work to occur. A 4/5/12 email with details is attached to the case.
Plan Reviewer's activity  4/5/2012 DONE
Sent an email to Ken Howell to provide an updated timeline document for completion of the repairs. The beam/joists repair work is still occurring.
BLD-Other3/2/20123/2/20123/9/2012PPEND
DetailsBob Archibald
Reviewed project status with Jim S.
BLD-Conference3/5/20123/5/20123/5/2012PPART
DetailsJim Storey
meet engineer of record on site. review of glb and floor joist repair. to be revised as to conditions.
BLD-Other2/29/20123/1/20123/2/2012APART
DetailsJim Storey
insp for beam and planter//Ben Mclenna Phone #: ###-#### discused issues w/scott eng. will meet next wk.
Plan Reviewer's activity  2/7/2012 DONE
DetailsJason Blais
CM Company has indicated in an email beam repairs should be started within a couple of weeks. They have been instructed to proceed by Parklane Management and are in process of ordering the steel. Design submittal/details from the structural engineer will be submitted to the City within the next couple of days.
BLD-Other1/31/20122/3/20122/3/2012APASS
DetailsJim Storey
ben - columns for the walkways - please call 1/2 hr prior Phone #: ###-#### all colums but two are complet as well as ledger angle instaled g line beam and colums are part of the beam replacment as a plan mod that was discuvered at colum repair. contractor is having steel fab and matrial orded and will e-mail me with a time line as to when this will be ready to begin instaltion.
CHANGE STATUS TO (ISS)  1/20/2012 DONE
DetailsBarbara Stitt
(F) Reprint permit  1/20/2012 DONE
DetailsBarbara Stitt
PLANS/APPL TAKEN TO FRONT DESK  1/17/2012 DONE
DetailsTim L. Woodard
Case Summary (BLD)  1/17/2012 DONE
DetailsTim L. Woodard
Inspection Record Card- Bld  1/17/2012 DONE
Telephone call  1/17/2012 DONE
DetailsChristina Prado
Left message for John Price giving fees due and advising permit is ready to be issued
Override - Parcel Holds  1/17/2012  
Permit Ready to Issue  1/17/2012 DONE
DetailsChristina Prado
Plan assigned to (TLW)11/28/2011 1/17/2012 PASS
DetailsTim L. Woodard
Routing - PLAN CHECK11/28/2011 1/17/2012 PASS
DetailsTim L. Woodard
Approved with outsource engineering comments addressed. TLW
Plan resubmittals received  1/13/2012 DONE
DetailsTisha Gallop
received response and two copies of plan sheet A2.0; taken to Tim Woodard.
Routing Off Site - STRUCTURAL12/23/2011 1/5/2012 FAIL
DetailsTim L. Woodard
Sent Corrections to the architect. TLW
Telephone call  12/23/2011 DONE
DetailsTisha Gallop
called Action Couriers for pick up
Plan resubmittals received  12/23/2011 DONE
DetailsTisha Gallop
Plan modification resubmittals received; revised cert of value (added another $5,000 to original $5,000 added value when plan mod was initially submitted for total added value for plan mod $10,000), three copies of structural calcs and plan sheets A2.0, A10.0; taken to Tim Woodard.
Plan resubmittals received  12/5/2011 DONE
DetailsJason Blais
Received annual inspection memo from structural engineer. Also received timeline to complete repairs from Parklane Management. These documents are attached to this case.
Plan Modification Accepted  11/28/2011 DONE
DetailsChristina Prado
PLAN MOD ACCEPTED** Received three sets of sheets A2.0 & A10.0 as well as three copies of structural calcs and applications. Plans routed to Tim Woodard for additional review
Meeting  11/17/2011 DONE
DetailsJason Blais
On site meeting. Attending were city staff Jason Blais, Tim Woodard, Bob Archibald, and Jim Storey meeting Doug Bolen (Parklane Management), Scott Soule (structural engineer). This meeting was for progress/repair updates and to meet the structural engineer annual inspection requirement. Structural engineer will be providing an annual inspection memo of progress and no imminent hazard status to the City. Doug Bolen will be providing a document to the City outlining the proposed repairs and timeline to complete. Structural engineer has indicated he is making frequent trips to the site for investigation, evaluation and inspection of items under repair. As more concealed areas are uncovered, the structure is evaluated for adequacy or needed repairs. A Plan Modification application, updated plans/details and structural calculations for repair work not included on previously approved plans need to be provided at once.
Plan Reviewer's activity  11/8/2011 DONE
DetailsJason Blais
Informed Doug Bolen to provide a Plan Modification application, plans and structural calculations to plans examiner Tim Woodard for review. Also requested a timeline proposal to complete the repairs.
Plan Reviewer's activity  11/4/2011 DONE
DetailsJason Blais
Received an updated engineering analysis letter and supporting structural calculations for repairs via email.
Telephone call  11/1/2011 DONE
DetailsJason Blais
Doug Bolen of Parklane Mgmt. will be emailing a progress/status report on repairs to the building by the end of today.
Telephone call  11/1/2011 DONE
DetailsJason Blais
Called structural engineer and left message for him to call be back on status of structural repairs to the building.
Telephone call  9/30/2011 DONE
DetailsJason Blais
Called Doug Bolen of Parklane Management. Doug stated he is having delays from his design structural engineer. I called and left a message with the design structural engineer for a status check. Sent an email to both stating this needs to be addressed immediately. Still have not received a final repair report.
BLD-Conference8/19/20118/19/20118/22/2011PPASS
DetailsJim Storey
400 pm apointment
Telephone call  8/9/2011 DONE
DetailsJason Blais
Talked with Scott Soule of Core Engineering. He is actively working on the evaluation of structural issues in this building. He reiterated there is no imminent danger but definitely issues needing repair or reinforcement. Scott is on track to provide the City with a final report/proposal on structural fixes to this building by the end of August 2011.
Issue PAID IN FULL permit  6/8/2011 DONE
DetailsTisha Gallop
Plan assigned to (TLW)5/13/2011 6/7/2011 PASS
DetailsTim L. Woodard
Routing - PLAN CHECK6/7/2011 6/7/2011 PASS
DetailsTim L. Woodard
Approved with removing a portion of the scope of work and email sent to Jason Blais and Myself. TLW
PLANS/APPL TAKEN TO FRONT DESK  6/7/2011 DONE
DetailsTim L. Woodard
Case Summary (BLD)  6/7/2011 DONE
DetailsTim L. Woodard
Inspection Record Card- Bld  6/7/2011 DONE
Permit Ready to Issue  6/7/2011 DONE
DetailsBarbara Stitt
Permit Ready to Issue  6/7/2011 DONE
DetailsBarbara Stitt
Telephone call  6/7/2011 DONE
DetailsBarbara Stitt
Called John and told him that permit is ready, fees due and that we need GC information on 6-7-11//BAS
Routing - PLAN CHECK5/13/2011 6/2/2011 FAIL
DetailsTim L. Woodard
Refer to plan review report. TLW
1st review completed  6/2/2011  
DetailsTim L. Woodard
Application received 5/13/20115/13/2011 DONE
DetailsTisha Gallop
Plans ACCEPTED BY PLAN TECH  5/13/2011 DONE
DetailsTisha Gallop
Recd Pcfee & Taken To Pln CK  5/13/2011 DONE
DetailsTisha Gallop
BLD-Final2/7/20132/7/2013 P 
DetailsJim Storey
ben Phone #: ###-####