Third Notice | | 6/26/2012 | 6/21/2012 | | DONE |
|
|
|
|
Second Notice | | 6/16/2012 | 6/21/2012 | | DONE |
|
|
|
|
First Notice | | 5/24/2012 | 6/6/2012 | | DONE |
|
|
|
|
Permanent Occupancy | | | 5/14/2012 | | DONE |
Tisha Gallop
|
|
|
|
FIRE-Final Inspection | 5/10/2012 | 5/11/2012 | 5/11/2012 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed
|
BLD-Final | 5/11/2012 | 5/11/2012 | 5/11/2012 | P | PASS |
Tom Arcoraci
|
|
|
nate Phone #: ###-####
|
BLD-Final | 4/18/2012 | 4/19/2012 | 4/19/2012 | A | DONE |
Tom Arcoraci
|
|
|
Nate Phone #: ###-####
|
Temporary Occupancy | 4/19/2012 | 7/18/2012 | 4/19/2012 | | DONE |
Tisha Gallop
|
|
|
|
BLD-Final | 4/18/2012 | 4/18/2012 | 4/18/2012 | P | PASS |
Tom Arcoraci
|
|
|
Nate Phone #: ###-#### ok for temp occ
|
FIRE-Final Inspection | 4/16/2012 | 4/17/2012 | 4/17/2012 | A | PART |
Troy Cobbley
|
|
|
A temporary is being given for the fire life safety inspection until the bollards and parking lot is finished. This is per Romeo Gervais.
|
FIRE-Conference | 4/16/2012 | 4/16/2012 | 4/16/2012 | P | DONE |
Troy Cobbley
|
|
|
Met Darren and went over the signage requirement for fire dept access. I also noted that a 5,000 or 6,000 gallon carbon dioxide tank that had not been shown on the plans is now installed along the north property line. I contacted scott arellano and he was ok with the installation of the tank and no additional submittal were to be required. Darren also asked about the bollards at the north side tanks. I deferred him to the fire chief since their installation does not match IFC 318.
|
BLD-Final | 4/12/2012 | 4/12/2012 | 4/13/2012 | P | NR |
Tom Arcoraci
|
|
|
|
FIRE-Final Inspection | 4/10/2012 | 4/12/2012 | 4/12/2012 | P | FAIL |
Troy Cobbley
|
|
|
(1) The vehicle protection "bollards", required per the IFC do not meet section 312.2, 1, 2 and 5 for spacing between posts, filled with concrete or 3'-0" clearance from the propane tank. (2) The LOX tank has not been installed to verify the 5'-0" clearance from the property line. (3) Provide fire dept access signage per review note #8 (4) Finish mounting the fire extinguishers. (5) Provide the missing exits signs and repair the exit discharge and interior emergency lights. (6) Mount and test the fire sprinkler exterior alarm bell (7) The fire alarm system manual pull station is mounted too high and needs to be lowered. (8) United Water has not turned on the water supply for the fire sprinkler system therefore the forward flush could not be performed or any alarms for flow tested. (9) Repair the 6" sprinkler hanger at the top of the dry pipe system that has been disconnected. There may be other items added to the list once actual testing can be performed. Per the drawings and the electrical contractor the electrical service is less than the 1,200 ampers therefore panic hardware is not required on the electrical room.
|
BLD-Final | 4/10/2012 | 4/12/2012 | 4/12/2012 | A | NR |
Tom Arcoraci
|
|
|
nate Phone #: ###-####
|
BLD-Other | 3/14/2012 | 3/15/2012 | 3/15/2012 | A | PASS |
Tom Arcoraci
|
|
|
Grid ceiling -- Darrin Phone #: ###-####
|
BLD-Footing | 2/9/2012 | 2/10/2012 | 2/10/2012 | A | PASS |
Tom Arcoraci
|
|
|
darrin - concrete pour at 10:00 Phone #: ###-####
|
BLD-Conference | 2/1/2012 | 2/1/2012 | 2/1/2012 | P | PASS |
Tom Arcoraci
|
|
|
eng says 2500 psi min ok for tank slab
|
CHANGE STATUS TO (ISS) | | | 1/31/2012 | | DONE |
Tisha Gallop
|
|
|
paid and picked up approved plan mod
|
Plan assigned to (SRZ) | 1/11/2012 | 1/11/2012 | 1/27/2012 | | DONE |
Sam Zahorka
|
|
|
1st review completed for plan mod. Failed Fire review
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/27/2012 | | DONE |
Sam Zahorka
|
|
|
|
Print Occupancy Form | | | 1/27/2012 | | DONE |
|
|
|
|
Telephone call | | | 1/27/2012 | | DONE |
Christina Prado
|
|
|
called and gave Jim fees due and advised plan mod is ready for pick up
|
Permit Ready to Issue | | | 1/27/2012 | | DONE |
Christina Prado
|
|
|
|
Routing - PLAN CHECK | 1/13/2012 | | 1/26/2012 | | PEND |
Sam Zahorka
|
|
|
Received resubmittals for Fire Review. Routed to Fire plan review.
|
Routing - FIRE | 1/26/2012 | | 1/26/2012 | | PASS |
Tim Frost
|
|
|
|
Plan resubmittals received | | | 1/25/2012 | | |
|
|
|
Received 1 copy of cover transmittal, 1 copy of letter to Tim Frost from Justin Wall dated 1-25-12, 2 copies of sheets A-0.1, S-1.1 and taken to Sam Zahorka's desk
|
Telephone call | | | 1/23/2012 | | DONE |
|
|
|
Emailed the following to Justin Wall
Per our phone conversation of today. The drawings need to annotated to say 6000 Gal and a dimension indication 5'-0" minimum from the propertly line.
In regards to the 1000 Gal propane tank.
The tank is required to be at least 10' from the property line and 25' from any other propane tank over 125 gal. (Ref: IFC: Table 3804.3 footnote f)
The propane tank must be protected from damage since it is located in a parking area. (Ref: 3807.4) See Section 312 excerpt (below) for protection requirements.
__________________________________
SECTION 312
VEHICLE IMPACT PROTECTION
312.1 General.
Vehicle impact protection required by this code shall be provided by posts that comply with Section 312.2 or by other approved physical barriers that comply with Section 312.3
312.2 Posts.
Guard posts shall comply with all of the following requirements:
1. Constructed of steel not less than 4 inches (102 mm) in diameter and concrete filled.
2. Spaced not more than 4 feet (1219 mm) between posts on center.
3. Set not less than 3 feet (914 mm) deep in a concrete footing of not less than a 15-inch (381 mm) diameter.
4. Set with the top of the posts not less than 3 feet (914 mm) above ground.
5. Located not less than 3 feet (914 mm) from the protected object.
312.3 Other barriers.
Physical barriers shall be a minimum of 36 inches (914 mm) in height and shall resist a force of 12,000 pounds (53 375 N) applied 36 inches (914 mm) above the adjacent ground surface.
__________________________________
|
Plan assigned to (SRZ) | 1/11/2012 | 1/11/2012 | 1/17/2012 | | FAIL |
Sam Zahorka
|
|
|
Plan Modification. Pending Statement of Special Inspection and Fire to PASS.
|
Telephone call | | | 1/17/2012 | | DONE |
Sam Zahorka
|
|
|
Left message with the architect Justin Wall. Plan modification submittal failed Fire plan review. I did receive the Statement of Special Inspection application. Permit issuance pending Fire plan review to pass.
|
Plan Reviewer's activity | | | 1/17/2012 | | DONE |
|
|
|
Emailed copy of Fire Review to jwall@grboise.com
|
Routing - FIRE | 1/12/2012 | | 1/13/2012 | | FAIL |
Tim Frost
|
|
|
|
1st review completed | | | 1/13/2012 | | FAIL |
|
|
|
Failed - Fire
|
Routing - PLAN CHECK | 1/11/2012 | | 1/12/2012 | | FAIL |
Sam Zahorka
|
|
|
Statement of special inspections required prior to plan mod issuance.
|
Case Summary (BLD) | | | 1/12/2012 | | DONE |
Sam Zahorka
|
|
|
|
Routing - PLANNING | 1/11/2012 | | 1/11/2012 | | PASS |
Andrea Tuning
|
|
|
CZC12-00002 Andrea
|
Plan Modification Accepted | | | 1/10/2012 | | DONE |
Tisha Gallop
|
|
|
Plan Modification accepted for Bld11-01192 (Oxarc Inc) to Replace the existing metal siding with new metal siding onall sides of building. Replace existing exterior concrete pad with new pad for large tanks. Replace existing concrete steps at main entrance with pre-engineered metal stairs. Install bollards at existing overhead door locations. Install concrete screen enclosure for propane tanks. Submitted on plan sheets CVR, A0.1, A1.1, A3.1, A3.3, S1.1, revised cert of value and structural calculations. Reference CZC12-00002. Routed to Sam Zahorka.
|
Issue PAID IN FULL permit | | | 9/14/2011 | | DONE |
Barbara Stitt
|
|
|
|
Print Occupancy Form | | | 9/14/2011 | | DONE |
Barbara Stitt
|
|
|
|
Issue PAID IN FULL permit | | | 9/14/2011 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 8/19/2011 | | DONE |
Christina Prado
|
|
|
Called and left a message for Peter giving fees due and ACHD Requirement prior to issuance of permit
|
Permit Ready to Issue | | | 8/19/2011 | | DONE |
Christina Prado
|
|
|
|
Routing - FIRE | 8/12/2011 | | 8/18/2011 | | PASS |
Tim Frost
|
|
|
Please, see attached review
|
Routing - PLAN CHECK | 8/18/2011 | | 8/18/2011 | | PASS |
Sam Zahorka
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/18/2011 | | DONE |
Sam Zahorka
|
|
|
|
Print Occupancy Form | | | 8/18/2011 | | DONE |
|
|
|
|
Plan assigned to (SRZ) | 6/2/2011 | | 8/18/2011 | | PASS |
Sam Zahorka
|
|
|
1st review completed. Pending Corrections.
|
Routing - PLAN CHECK | 7/29/2011 | | 8/12/2011 | | PEND |
Sam Zahorka
|
|
|
|
Plan resubmittals received | | | 8/10/2011 | | DONE |
|
|
|
received 1 letter of transmittal, 1 comments,and 2 copies of sheets A-0.1,A-1.1 sent to Sam Z.
|
Plan Reviewer's activity | | | 8/2/2011 | | DONE |
|
|
|
Sent the following email to Justin Wall in response to his email with questions.
Hi Justin,
I failed to mention in my previous review that you are only allowed 4 control areas (inside). I thought you would the move the storage into the parking lot as previously discussed. Please, keep in mind that you already have at least one control area in the gas filling room. Therefore, you could have 3 more control areas on the covered dock. The 3 control areas must be separated by fire barriers per IFC 2703.8.3 and have floors that comply with 2703.8.3.4. It is very hard to point out all of the pertinent code sections. I would suggest that you get a FPE involved with the project to help you with the design. All of the IFC and IBC of course applies. However, you may want to pay specific attention to chapters 27, 35 and 40 of the IFC.
|
Plan Reviewer's activity | | | 7/29/2011 | | DONE |
|
|
|
Emailed review to RP
|
Routing - PUBLIC WORKS | 7/28/2011 | | 7/29/2011 | | PASS |
Connie Baumgartner
|
|
|
Additional drinking fountain added.
|
Routing - FIRE | 7/29/2011 | | 7/29/2011 | | FAIL |
Tim Frost
|
|
|
Email review to RP
|
Case Summary (BLD) | | | 7/28/2011 | | DONE |
Sam Zahorka
|
|
|
|
Routing - PLAN CHECK | 6/30/2011 | | 7/28/2011 | | PEND |
Sam Zahorka
|
|
|
Pending Fire to pass and Public Works.
|
Plan resubmittals received | | | 7/26/2011 | | DONE |
|
|
|
7-26-11 received 1 letter of transmittal,1 comments,and 2 copies of sheet A1.1 sent to Sam Z.
|
Plan resubmittals received | | | 7/26/2011 | | DONE |
|
|
|
7-25-11 received 1 letter of transmittal,1 comment,1 response,and 2 copies of sheets CVR,A-1.1,A-6.1,P-2.0,E-2.0L,E-3.2 taken to Sam Z
|
Plan Reviewer's activity | | | 7/12/2011 | | DONE |
|
|
|
Emailed review to Justin Wall jwall@grboise.com
|
1st review completed | | | 6/30/2011 | | DONE |
|
|
|
Failed - Plan Check, Fire
|
Routing - FIRE | 6/27/2011 | | 6/30/2011 | | FAIL |
Tim Frost
|
|
|
Please, see attached review.
|
Case Summary (BLD) | | | 6/27/2011 | | DONE |
Sam Zahorka
|
|
|
|
Routing - PLAN CHECK | 6/9/2011 | | 6/27/2011 | | FAIL |
Sam Zahorka
|
|
|
Pending Fire reviews evaluation of proposed hazardous material storage.
|
Plan Reviewer's activity | | | 6/16/2011 | | DONE |
Jason Blais
|
|
|
ACHD has indicated they would like to see this project for review. Applicant required to submit plans to ACHD for evaluation. Sarah Schafer communicated this to Allison of Glancey Rockwell. Written verification from ACHD will need to be provided prior to permit issuance.
|
Routing - Design Review | 6/8/2011 | | 6/9/2011 | | PASS |
Sarah Schafer
|
|
|
Ok per CZC11-00132. Retail showroom is less than 25% of floor area and allowed as accessory use to primary allowed use.
|
Routing - PLUMBING | 6/6/2011 | | 6/8/2011 | | PASS |
Bill VanDegrift
|
|
|
Per plans and 2003 UPC.
|
Routing - Erosion and Sediment | 6/3/2011 | | 6/6/2011 | | PASS |
Steven Webb
|
|
|
ESC plan is approved according to the ESC Blueprint and ESC Permit conditions. ESC11-00333
|
Routing PW Sewer Rating | 6/3/2011 | | 6/3/2011 | | PASS |
Connie Baumgartner
|
|
|
|
Routing - PUBLIC WORKS | 6/2/2011 | | 6/3/2011 | | PASS |
Connie Baumgartner
|
|
|
|
Pending Assignment by JCB | 6/1/2011 | | 6/2/2011 | | DONE |
Jason Blais
|
|
|
|
Routing - Addressing | 6/2/2011 | | 6/2/2011 | | PASS |
Terry Records
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 6/1/2011 | | DONE |
Christina Prado
|
|
|
|
Intake Approval | | | 6/1/2011 | | PASS |
Carl D Madsen
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 6/1/2011 | | DONE |
Christina Prado
|
|
|
|
Application received | | 6/1/2011 | | | |
|
|
|
|