First Notice | | 3/8/2012 | 3/30/2012 | | DONE |
|
|
|
|
BLD-Final | 2/27/2012 | 2/27/2012 | 2/27/2012 | P | PASS |
Mike Jordan
|
|
|
Junior Phone #: ###-####. ok for perm occ.
|
Permanent Occupancy | | | 2/27/2012 | | |
Barbara Stitt
|
|
|
|
Temporary Occupancy | 2/17/2012 | 5/17/2012 | 2/17/2012 | | DONE |
Jason Blais
|
|
|
|
BLD-Aging Inspection | 1/23/2012 | 1/23/2012 | 1/25/2012 | | DONE |
Mike Jordan
|
|
|
Spoke to Junior with HCD, he noted that rated glazing should be here by the end of Jan 2012.
|
BLD-Final | 11/21/2011 | 11/22/2011 | 11/22/2011 | A | PART |
Mike Jordan
|
|
|
Please call 30 min before thanks Phone #: ###-#### >> Inspection requested via web by Les Seal. Ok for temp occ. only. Will be ok for perm occ. once plumbing is perm. and firerated glazing is installed in place of temp. 1hr. wall.
|
Temporary Occupancy | 11/22/2011 | 2/20/2012 | 11/22/2011 | | DONE |
Barbara Stitt
|
|
|
|
BLD-Final | 11/21/2011 | 11/21/2011 | 11/21/2011 | P | NR |
Mike Jordan
|
|
|
junior Phone #: ###-####
|
FIRE-Final Inspection | 11/21/2011 | 11/21/2011 | 11/21/2011 | P | PASS |
Troy Cobbley
|
|
|
life safety passed.
|
BLD-Conference | 11/18/2011 | 11/18/2011 | 11/18/2011 | P | DONE |
Mike Jordan
|
|
|
junior Phone #: ###-####
|
FIRE-Conference | 11/17/2011 | 11/17/2011 | 11/17/2011 | P | DONE |
Troy Cobbley
|
|
|
For a final on this project we need to test the smoke alarms, exit signs/emergency lights, and verify hardware.
|
BLD-Final | 11/14/2011 | 11/14/2011 | 11/14/2011 | P | CANC |
Mike Jordan
|
|
|
Please call junior 30 min before Phone #: ###-#### >> Inspection requested via web by Les Seal. Cancelled by contractor via phone call.
|
FIRE-Conference | 11/14/2011 | 11/14/2011 | 11/14/2011 | A | DONE |
Troy Cobbley
|
|
|
I went over life safety notes with JR.
|
BLD-Framing/Rough-in | 11/1/2011 | 11/1/2011 | 11/1/2011 | P | PASS |
Mike Jordan
|
|
|
junior - late afternoon please Phone #: ###-####. double layer 5/8 type x at canopy lid ok.
|
BLD-Wall cover | 11/1/2011 | 11/1/2011 | 11/1/2011 | A | PASS |
Mike Jordan
|
|
|
Phone #: ###-#### >> Inspection requested via web by Les Seal. Structural beam in canopy wrap with 5/8 type x rock, 2 layers ok.
|
BLD-Wall cover | 10/24/2011 | 10/25/2011 | 10/25/2011 | A | PASS |
Mike Jordan
|
|
|
Please call junior 30 min before thanks Phone #: ###-#### >> Inspection requested via web by Les Seal
|
BLD-Conference | 10/24/2011 | 10/25/2011 | 10/25/2011 | A | DONE |
Mike Jordan
|
|
|
Please call junior 30 min before thanks Phone #: ###-#### >> Inspection requested via web by Les Seal. Conferance on canopy protection.
|
BLD-Framing/Rough-in | 10/19/2011 | 10/20/2011 | 10/20/2011 | A | PASS |
Jim Storey
|
|
|
Dennis-dry wall inspection Phone #: ###-#### gyp ok/ col rapped and ok to continue 2nd layer on north side. roof framing ok to cover glb still needs 48" gyp wrap and 2x4 removed from 2 hr wall penatrations will need fire stopped.
|
Issue PAID IN FULL permit | | | 10/19/2011 | | DONE |
Barbara Stitt
|
|
|
|
Routing - PLAN CHECK | 10/14/2011 | | 10/18/2011 | | PASS |
Dan Stuart
|
|
|
Attached plan review comments and redlined notes on plans from all reviewing agencies are part of the reviewed approved plan and require compliance. Plans to permit desk to issue.
|
Plan Reviewer's activity | | | 10/18/2011 | | DONE |
|
|
|
Letter of explanation from architect concerning temporary 1-hour wall to north of 2-hr fire wall until 3/4 hour rated glazing and frames arrive for installation. A temporary occupancy is allowed when all required work is completed and temporary 1-hour wall is in place. Final C.O. to be issued after rated glazing is installed and approved by inspection.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/18/2011 | | PASS |
Dan Stuart
|
|
|
|
Print Occupancy Form | | | 10/18/2011 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/18/2011 | | DONE |
Tisha Gallop
|
|
|
|
Telephone call | | | 10/18/2011 | | DONE |
Tisha Gallop
|
|
|
called Jeff and left message w/Dave that permit is ready, fees, and need GC/RCE/form.
|
Plan assigned to (DRS) | 8/12/2011 | | 10/18/2011 | | PASS |
Dan Stuart
|
|
|
|
Plan resubmittals received | | | 10/14/2011 | | DONE |
|
|
|
10-14-11 received 1 transmittal1 response,and 2 copies of sheets G1.1,G1.2,G1.3,A1.1,A1.2 sent to Dan S.
|
Plan resubmittals received | | | 10/7/2011 | | |
|
|
|
Received 1 cover transmitall, 1 copy of letter to Dan Stuart dated 10-7-11 from Jeff Likes, 1 copy of Alternate Request dated 10-7-11, 1 copy calcs, 2 copies of sheets G1.1, G1.2, G1.3, A1.1, A1.2, A1.3 and taken to Dan Stuart
|
Meeting | | | 9/27/2011 | | DONE |
|
|
|
Met with strcural inspector Mike jordan to review the plans for the 2-hour fire wall being created as the north wall of the new tenant, Kim's Kare-A-Lot Childcare, to clarify requirements and suggest a pre-constrcution conference with the contractor to verify code requirements for this scope of work as part of the tenant improvement to establish a certificate of occupancy.
|
Telephone call | | | 9/27/2011 | | DONE |
|
|
|
Talked W/ Jeff Likes to review e-mail of plan changes to verify needed information had been provided on plans. jeff brining in resubmittals this afternoon.
|
Case Summary (BLD) | | | 9/27/2011 | | |
|
|
|
|
Routing - PLAN CHECK | 9/13/2011 | | 9/26/2011 | | FAIL |
Dan Stuart
|
|
|
Plan resubmittals of 9/23/11 did not indicate corrections needed as reviewed on 9/9/11 in meeting W Jeff Likes and Dan Stuart. Resubmittals requested.
|
Plan resubmittals requested | | | 9/26/2011 | | DONE |
|
|
|
Called Jeff Likes and reviewed items remaining to be corrected or clarified on the plans.
|
Plan resubmittals received | | | 9/23/2011 | | DONE |
Christina Prado
|
|
|
Received three full new sets of plans G1.1, G1.2, G1.3, A1.1 and A1.2. Plans given to Dan Stuart for review
|
Telephone call | | | 9/20/2011 | | DONE |
|
|
|
Called Jeff Likes to review code items needing corrected or to be shown on plan resubmittals. 2hr fire wall labeling, 2-hour continuous through the frame walls above the CMU into canopy and back wall, change note on plans to indicate support wall and glazing along line of store front needs to be 1-hour / 3/4 hour glazing 10' on each side of fire wall (depth of the canopy overhang. Detail for protection of 2 hour fire wall on interior side of tenant spaces (wrapp bottom of truss' & up side to deck at minimum 4 feet.
|
Routing - FIRE | 9/8/2011 | 9/8/2011 | 9/13/2011 | | PASS |
Scott Arellano
|
|
|
Attached IFC comments to plans. Seerate Fire Sprinkler and Fire Alarm permits are required.
|
1st review completed | | | 9/13/2011 | | FAIL |
|
|
|
Failed Plan Check
|
Meeting | | | 9/9/2011 | | DONE |
|
|
|
Jeff and I met in conf. room #1. I brought the submitted plans I had marked up with concerns that did not allow the completion of the plans review. Jeff brought a copy of the plans that we could mark up and sketch on for use in providing new plan sheets.
|
Route to Impact Fee Review | 9/8/2011 | 9/13/2011 | 9/8/2011 | | PASS |
Cindy M. Gould
|
|
|
Tenant improvement no impact fees
|
Plan Reviewer's activity | | | 9/8/2011 | | DONE |
|
|
|
Set up meeting with architect to review plans and missing data to show method of providing code compliance for this project. Plans to incomplete to provide detailed plan review. Copy of cursory plan review notes e-mailed to architect so he can prepare for meeting at 8:30 AM on 9/9/11.
|
Routing - PLAN CHECK | 8/15/2011 | | 9/8/2011 | | FAIL |
Dan Stuart
|
|
|
Plans & details are incomplete. Contacted Jeff Likes and set up appointment to sit down with him and review plans for requirements. We are meeting at 8:30 AM Friday 9/9/11.
|
Plan resubmittals requested | | | 9/8/2011 | | DONE |
|
|
|
|
Routing - PUBLIC WORKS | 8/15/2011 | | 8/15/2011 | | PASS |
Beverly Mountain
|
|
|
|
Routing - PLANNING | 8/15/2011 | | 8/15/2011 | | PASS |
David Moser
|
|
|
David Moser - CUP11-00035
|
Plan resubmittals received | | | 8/15/2011 | | DONE |
Jason Blais
|
|
|
Received CDHD Child Care Plan Review & Approval form.
|
Routing - Addressing | 8/15/2011 | | 8/15/2011 | | PASS |
Terry Records
|
|
|
|
Pending Assignment by JCB | 8/12/2011 | | 8/12/2011 | | DONE |
Jason Blais
|
|
|
|
Application received | | 8/11/2011 | 8/11/2011 | | DONE |
Barbara Stitt
|
|
|
|
Intake Approval | | | 8/11/2011 | | PASS |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 8/11/2011 | | DONE |
Barbara Stitt
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 8/11/2011 | | DONE |
Barbara Stitt
|
|
|
|