BLD-Final | 10/17/2011 | 10/18/2011 | 10/18/2011 | A | PASS |
Mike Jordan
|
|
|
Devin Phone #: ###-####. All issues were resolved. Ok for perm occ.
|
Permanent Occupancy | | | 10/18/2011 | | DONE |
Tisha Gallop
|
|
|
|
FIRE-Final Inspection | 10/17/2011 | 10/17/2011 | 10/17/2011 | P | PASS |
Troy Cobbley
|
|
|
life safety passed
|
BLD-Conference | 9/26/2011 | 9/27/2011 | 9/27/2011 | P | FAIL |
Mike Jordan
|
|
|
Call 30 min prior----Devin Phone #: ###-####. Resubmit plan for 2nd warehouse to match existing conditions, remove all tumbturns and provide lever type hardware at exterior doors.
|
BLD-Final | 9/26/2011 | 9/27/2011 | 9/27/2011 | A | CANC |
Mike Jordan
|
|
|
call 30 min notice//Devin Phone #: ###-####
|
FIRE-Final Inspection | 9/26/2011 | 9/26/2011 | 9/26/2011 | P | FAIL |
Troy Cobbley
|
|
|
Provide exit signs with battery backup in locations as marked on the plans, provide "Door to remain unlocked when building is occupied" sticker at the main exit door, provide single action hardware on the west front exit door and all of the other exterior exit doors and remove the deadbolts, provide missing covers for the electrical outlets and breaker boxes in the remote warehouse, provide 2A, 10BC fire extinguishers as discussed with current inspection tags and resubmit plans for the remote warehouse that matches the installed floor plan.
|
Issue PAID IN FULL permit | | | 9/26/2011 | | DONE |
Tisha Gallop
|
|
|
|
Plan assigned to (TLW) | 9/21/2011 | | 9/23/2011 | | PASS |
Tim L. Woodard
|
|
|
|
Routing - PLAN CHECK | 9/21/2011 | | 9/23/2011 | | PASS |
Tim L. Woodard
|
|
|
|
1st review completed | | | 9/23/2011 | | DONE |
Tim L. Woodard
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/23/2011 | | DONE |
Tim L. Woodard
|
|
|
|
Case Summary (BLD) | | | 9/23/2011 | | DONE |
Tim L. Woodard
|
|
|
|
Print Occupancy Form | | | 9/23/2011 | | DONE |
|
|
|
|
Telephone call | | | 9/23/2011 | | DONE |
|
|
|
t/c w devon - permit ready
|
Permit Ready to Issue | | | 9/23/2011 | | DONE |
|
|
|
|
Application received | | 9/21/2011 | 9/21/2011 | | DONE |
Tisha Gallop
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 9/21/2011 | | DONE |
Tisha Gallop
|
|
|
|