BLD-Final | 12/12/2011 | 12/13/2011 | 12/13/2011 | A | PASS |
Jim Storey
|
|
|
Late morning---Tommy Phone #: ###-####
|
FIRE-Final Inspection | 12/12/2011 | 12/13/2011 | 12/13/2011 | A | PASS |
Troy Cobbley
|
|
|
life safety passed
|
Permanent Occupancy | | | 12/13/2011 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 11/21/2011 | | DONE |
Sam Zahorka
|
|
|
Left message for Tommy Scott the general manager. Following up on requested field corrections by the fire and building inspectors prior to permanent certificate of occupancy issuance.
|
BLD-Final | 10/11/2011 | 10/13/2011 | 10/14/2011 | P | PART |
Jim Storey
|
|
|
Tommy Phone #: ###-#### ext 3022 temp for 2nd floor only co pending for exit sys compliance. not per plan.
|
Temporary Occupancy | 10/14/2011 | 1/12/2012 | 10/14/2011 | | DONE |
Christina Prado
|
|
|
|
FIRE-Final Inspection | 10/11/2011 | 10/13/2011 | 10/13/2011 | P | PART |
Troy Cobbley
|
|
|
A temporary occupancy for life safety is being given. Several lights are on back order for the west rink. Door swing on the west second floor corridor exit needs to be corrected. Provide stickers at the main exit doors, provide testing for the emergency lighting exiting across the roof. Provide signage at the breaker/ controller for the skating ring emergency lighting. The storage of the propane for the zambonie machines is being deferred to the fire dept.
|
Print Occupancy Form | | | 10/13/2011 | | DONE |
Barbara Stitt
|
|
|
|
BLD-Final | 10/5/2011 | 10/7/2011 | 10/12/2011 | A | CANC |
Jim Storey
|
|
|
Please call Sam prior to inspection Phone #: ###-####
|
FIRE-Final Inspection | 10/7/2011 | 10/11/2011 | 10/11/2011 | P | FAIL |
Troy Cobbley
|
|
|
Repair all of the inoperative exit signs/emergency lights, add emergency lights in locations as discussed, verify occupant load signs as discussed, remove the lock from the custodial closet door. The master switch on the ice rink emergency lighting is ok with Scott as long as a trained individual is stationed at this switch during functions.
|
FIRE-Final Inspection | 10/5/2011 | 10/6/2011 | 10/7/2011 | P | CANC |
Forrest France
|
|
|
Overbooked
|
Application received | | 10/5/2011 | 10/5/2011 | | DONE |
Barbara Stitt
|
|
|
|
Plan assigned to (SRZ) | 10/5/2011 | 10/5/2011 | 10/5/2011 | | PASS |
Sam Zahorka
|
|
|
|
Routing - PLAN CHECK | 10/5/2011 | | 10/5/2011 | | PASS |
Sam Zahorka
|
|
|
|
1st review completed | | | 10/5/2011 | | DONE |
Sam Zahorka
|
|
|
|
Case Summary (BLD) | | | 10/5/2011 | | DONE |
Sam Zahorka
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/5/2011 | | DONE |
Sam Zahorka
|
|
|
|
Issue & PRINT permit | | | 10/5/2011 | | DONE |
Barbara Stitt
|
|
|
|
Permit Ready to Issue | | | 10/5/2011 | | DONE |
|
|
|
|
First Notice | | 12/23/2011 | | | |
|
|
|
|