Permit Information
Permit NumberBLD11-03007
StatusFinaled
Name SWANK-SAHLEIN F B & S L TRUST
Site Address 1875 S CENTURY WAY
Project NameWINGS CENTER
Customer Number 
ePlanReviewNo
Description
(WINGS CENTER) (Does NOT include Planet Kids or Pool) 7/10/12 Plan Modification - Modify scope of work by reducing area of wall demo below the new mezzanine area and modify structural support and framing materials for new mezzanine area; reduce size of open office area and increase size of sprinkler room and nap room; remove select exterior doors from service by removing door hardware, exit signs and securing in place; reduce glazing in wall between rooms 114 & 121 and add new glazing and door in wall between rooms 110 and Planet Kids; add new exit signs and add emergency lighting (3 new in Gym/Cheerleading area, 1 to room 121 at 2nd exit and 2 on mezzanine area - redlined on Sheet A2.2); add new 16' opening at office mezzanine area M102C; and provide two exits from Cheer Leading Area 102; change room use and layout for Room 121; and delete stove and range hood from break room 115A See Plan Modification Plan resubmittals received 10/30/12. drs Remodel of an existing daycare / assembly / activity center per approved plans. Work to include construction of new tube steel support columns, beams, floor framing & sheathing, wall framing, finishes, doors / hardware, main level observation areas, and expand the south end mezzanine adding 609 s.f. support area and 310 s.f. new mezzanine observation area. On the main level, a NAP room, offices, retail area, breakroom/kitchen for existing daycare (licensed for 70 maximum), add an accessible restroom on the main level and work on electrical, mechanical, plumbing and sprinkler system. NOTE: This building was constructed in Ada County in 1980, remodeld in 2002 in Ada County and annexed into Boise City on 1/8/02. The building is declared to be fully sprinklered for allowable area increase under Ada County permit. Note: Mezzanine area is not considered part of the floor area but is considered for determining the fire area per IBC. Existing kitchen shown for daycare has range for heating foods only. No cooking allowed. - drs
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Agreement of Future work12/14/201211/19/201311/26/2013 DONE
DetailsDan Stuart
Fire Upgrade Agreement attached to case.
11/26/13 Permits FIR12-00267 (sprinklers) and FIR12-00557 (alarms) have been obtained, work completed, work inspected and permits finaled out. Work outlined in upgrade agreement attached to this case completed.
Third Follow up  7/1/2013 DONE
DetailsTisha Gallop
Eireannach on hold to provide final values for Bld11-03007, Bld11-03020, Bld12-01216.
Third Notice 4/27/20136/3/2013 DONE
mailed to Eirannach
Third Notice 3/27/20134/22/2013 DONE
mailed to Eireannach LLC
Second Notice 3/1/20133/22/2013 DONE
First Notice 2/11/20132/19/2013 DONE
Override - Parcel Holds  2/1/2013  
Permanent Occupancy  2/1/2013 DONE
DetailsTisha Gallop
BLD-Final1/29/20131/29/20131/30/2013PCANC
DetailsTom Arcoraci
JOHN Phone #: ###-####
BLD-Final1/29/20131/30/20131/30/2013APASS
DetailsTom Arcoraci
ok for occ. no mech permit required
FIRE-Final Inspection1/29/20131/29/20131/29/2013PPASS
DetailsTroy Cobbley
Life safety passed
Override - Parcel Holds1/29/20131/1/19001/29/2013  
this is for a building final
BLD-Final1/25/20131/28/20131/28/2013ANR
DetailsTom Arcoraci
John Phone #: ###-####
FIRE-Final Inspection1/25/20131/28/20131/28/2013AFAIL
DetailsTroy Cobbley
Provide exit signs and emergency lights as shown on the city approved plans. Provide testing for all exit signs and emergency lights.
Override - Parcel Holds1/25/20131/1/19001/25/2013  
Not on this permit
Override - Parcel Holds1/25/20131/1/19001/25/2013  
not on this permit
Override - Parcel Holds  12/14/2012  
CHANGE STATUS TO (ISS)  12/11/2012 DONE
(F) Reprint permit  12/11/2012 DONE
Telephone call  12/4/2012 DONE
DetailsChristina Prado
Spoke to ward to verify constractor has been notified of upcoming expiration. Will check back 12-10-12 if it hasn't been picked up yet
Expiration Notice11/26/201212/17/201211/26/2012 DONE
DetailsChristina Prado
OVERRIDE  10/31/2012  
Plan assigned to (DRS)7/10/20127/10/201210/31/2012 PASS
DetailsDan Stuart
Wings Center
Routing - PLAN CHECK10/30/2012 10/31/2012 PASS
DetailsDan Stuart
Plan Mod resubmittals of 10/30/12 inserted into original plans in place of original sheets. Red line notes added to Sheet A2.1 & A2.2 and original permit & plan review modified based on changes, site observation and red line notes. To permit desk to issue.
Routing - FIRE10/31/2012 10/31/2012 PASS
Details
Took plan mods of 10/31/12 to Scott Arellano and reviewed changes and where I had transfered the red lines for required fire extinguishers per Sheet S2.1 dated 2/3/2012 and S2.2 dated 3/3/12. Okay - no further review required.
PLANS/APPL TAKEN TO FRONT DESK  10/31/2012 PASS
Print Occupancy Form  10/31/2012 DONE
DetailsTisha Gallop
Telephone call  10/31/2012 DONE
DetailsChristina Prado
Called John to advise plan mod is ready and gave fees due
Override - Parcel Holds  10/31/2012  
Permit Ready to Issue  10/31/2012 DONE
DetailsChristina Prado
Plan resubmittals received  10/30/2012 DONE
DetailsChristina Prado
Received two sets of plans marked A2.1; Gave to Dan Stuart for review
Plan resubmittals received  10/24/2012 DONE
DetailsTisha Gallop
received two copies of plan sheets A2.1, A2.2, A2.3; put on Dan Stuarts desk
Routing - PLAN CHECK9/24/2012 10/8/2012 FAIL
DetailsDan Stuart
Visit to job site with structural inspector Tom Arcoraci and contractor John McCarthy revealed as-built conditions do not match original reviewed and permited plans and do not comply with code requirements for doors and landings and possible additional requirments for some areas based on actual uses which would increase occupant loads, exiting, door hardware, exit signage and emergency lighting, etc. Architect needs to walk the project site and provide correctly labeled plans for all use areas and address code compliance for doors, landings, hardware, exiting, exit signage and emergency lighting. Other code items may be dicovered once the corrected plans are provided for review.
BLD-Conference10/4/201210/5/201210/5/2012APASS
DetailsTom Arcoraci
Meeting  10/5/2012 DONE
DetailsDan Stuart
Tom Arcoraci and I, met John McCarthy, contractor, at job site to walk through the building to compare existing conditions and area uses with the most recent submitted plan modifications dated 9/24/12 as John had stated he was ready for a final inspection. It was discovered that changes had been made to the uses of several areas of the building that could effect occupant loads and exiting requirements; modifications at doors and landings on each side of doors do not comply with current code because of added flooring materials having been added to the activities areas; relocation of northeast corner observation area to the mezzanine level; questions on exit signage, emergency lighting and door hardware concerns and questions on the dyacare use areas and occupant load; and the kitchen areaclaimed to be existing in the SW corner area is not per the reviewed plans. John McCarthy took notes. The architect needs to get with the owner and contractor and to provide corrected plans showing all actual uses proposed and area of building where located, occupant loads, door hardware, door landings, door headroom, exit signage and emergency lighting, etc. for review and permiting.
BLD-Conference10/4/201210/4/201210/4/2012ACANC
DetailsTom Arcoraci
Override - Parcel Holds  10/4/2012  
Plan resubmittals received  9/24/2012  
resub for plan mod; received two copies of supplemental structural calcs and plan sheets A2.1, A2.2, A2.3; taken to Dan Stuart.
Routing - PLAN CHECK7/10/2012 8/2/2012 FAIL
DetailsDan Stuart
Resubmittals required. Copies of plan review to owner, contractor and architect. Copies also e-mailed to fire and structural inspectors.
Plan resubmittals requested  8/2/2012 DONE
Copies of plan review to owner, contractor and architect.
Plan Reviewer's activity  8/2/2012 DONE
DetailsDan Stuart
Copy of plan review report e-mailed to fire and structural inspectors.
Plan Modification Accepted  7/10/2012 DONE
Rec'd plan mod for reduction of foundation work since the design team found a soil report that showed 3500 psf bearing; modified nap room, office area, & daycare bathrooms; remoced some exit door to avoid some pull station upgrades; reduction of beam sizes by changing the span - two copies of sheets A2.1 & A2.2. Taken to Dan S
BLD-Wall cover6/15/20126/15/20126/15/2012PPART
DetailsTom Arcoraci
New Office area - electrical inspection is scheduled for a pm inspection as well. just two walls - north west corner of building Phone #: ###-#### >> Inspection requested via web by John McCarthy
BLD-Framing/Rough-in6/5/20126/5/20126/5/2012APASS
DetailsTom Arcoraci
Framing rough in for cover of new beam at spectator 101 [old front office location] Phone #: ###-#### >> Inspection requested via web by John McCarthy wip ok as built drawing required
BLD-Framing/Rough-in5/22/20125/22/20125/22/2012PPART
DetailsTom Arcoraci
Restroom, Office and deck rough in Phone #: ###-#### >> Inspection requested via web by John McCarthy wip ok will return to plan review with as built prior to full cover ok to one side
Telephone call  5/3/2012 DONE
Per fire marshal request, I have spoke with Greg Patrick at TVFP. We aggree that the overhead protection patterns should touch. In other words, if there were no obstructions the entire floor area would be covered. In addtion, there shall be sprinklers in all of the combustible concealed spaces. (Wooden climbing boxes). Therefore, sprinklers could be eliminated under the >48" obstructions caused by the climbing wall. This due to it not being reasonable to put sprinklers in those locations.
BLD-Conference4/24/20124/24/20124/24/2012PPASS
DetailsTom Arcoraci
FIRE-Conference4/13/20124/16/20124/16/2012ADONE
DetailsTroy Cobbley
John McCarthy and I discussed manual fire alarm, exist discharge lighting and combustible concealed space fire sprinkler requirements for the upcoming project.
Issue PAID IN FULL permit  4/11/2012 DONE
DetailsBarbara Stitt
Telephone call  3/26/2012 DONE
DetailsBarbara Stitt
Called Ward and informed him of the new fees//3-26/12 @ 8:36am//BAS
OVERRIDE  3/19/2012  
OVERRIDE  3/19/2012  
OVERRIDE  3/19/2012  
Routing - FIRE3/15/2012 3/19/2012 PASS
DetailsScott Arellano
Attached IFC comments to plans.
Routing - PLAN CHECK3/19/2012 3/19/2012 PASS
DetailsDan Stuart
Review and approval includes all red-lined notes and attached plan review comments & conditions of all plan reviewing agencies as a part of the approval requirements. To permit desk to issue.
PLANS/APPL TAKEN TO FRONT DESK  3/19/2012 PASS
Print Occupancy Form  3/19/2012 DONE
Telephone call  3/19/2012 DONE
DetailsChristina Prado
Called Ward and gave him fees due and advised RP & letter from ACHD are required prior to issuance
Permit Ready to Issue  3/19/2012 DONE
DetailsChristina Prado
Plan assigned to (DRS)12/29/2011 3/19/2012 PASS
DetailsDan Stuart
Routing - PLAN CHECK2/24/2012 3/13/2012 PEND
DetailsDan Stuart
Received new plan sheets in response to fire code analyst plan review.
Plan resubmittals received  3/13/2012 DONE
DetailsTisha Gallop
received two copies of plan sheets A0.0, A2.2; taken to Dan Stuart.
Routing - FIRE2/17/2012 2/24/2012 FAIL
DetailsScott Arellano
Faxed and emailed resubmittal items to architect and building owner.
Routing - PLAN CHECK1/25/2012 2/17/2012 PEND
DetailsDan Stuart
Plans approved as red-lined on and all attached plan reviews of all reviewing agencies
Plan resubmittals received  2/13/2012  
2-13-12 received 1 response,1 occupant load chart,1 statement of special inspections & 2 sets of sheets A0.0,A2.1,A2.2,A2.3,A2.4 & 1 SET OF SHEETS A1.0,A2.0,A3.0,A4.0
Route to Impact Fee Review1/20/20121/25/20121/25/2012 PASS
DetailsCindy M. Gould
No external increase in building all expanded area is inside an existing building. No impact fees
Routing - FIRE1/20/20121/20/20121/25/2012 FAIL
DetailsScott Arellano
Faxed and emailed resubmittal items to architect.
1st review completed  1/25/2012 FAIL
Failed Plan Check, Fire
Routing - PLAN CHECK1/3/2012 1/20/2012 FAIL
DetailsDan Stuart
Resubmittals required. Plans routed to fire code anlayst for review.
Routing - Erosion and Sediment12/30/2011 1/3/2012 PASS
DetailsClint A Smith
ESC11-00905 plan waiver approved with conditions attached to the permit.
Routing - PLANNING1/3/2012 1/3/2012 PASS
DetailsCody Riddle
Cody Riddle - Mezzanine expansions/daycare. Okay per Hal Simmons; This approval does not allow for an increase in enrollment for the daycare.
Routing PW Sewer Rating12/29/2011 12/30/2011 PASS
DetailsConnie Baumgartner
Routing - PUBLIC WORKS12/29/2011 12/30/2011 PASS
DetailsConnie Baumgartner
Routing - Addressing12/29/2011 12/29/2011 PASS
DetailsTerry Records
Pending Assignment by JCB12/28/2011 12/29/2011 DONE
DetailsJason Blais
Application received 12/23/201112/28/2011 DONE
DetailsTisha Gallop
Plans ACCEPTED BY PLAN TECH  12/28/2011 DONE
DetailsTisha Gallop
Recd Pcfee & Taken To Pln CK  12/28/2011 DONE
DetailsTisha Gallop
Intake Approval  12/28/2011 PASS
DetailsSam Zahorka
Intake Approval  12/23/2011 FAIL
DetailsSam Zahorka
Refer to circled items on checklist attached to this case. SRZ