Third Notice | | 4/28/2013 | 7/22/2013 | | DONE |
|
|
|
|
Third Notice | | 2/24/2013 | 4/23/2013 | | DONE |
|
|
|
mailed
|
Second Notice | | 2/7/2013 | 2/19/2013 | | DONE |
|
|
|
mailed 2-19-13
|
First Notice | 1/3/2013 | 1/3/2013 | 1/28/2013 | | DONE |
Tony Young
|
|
|
|
BLD-Final | 1/2/2013 | 1/3/2013 | 1/4/2013 | A | DONE |
Tony Young
|
|
|
Rob--Please call for access information Phone #: ###-####
|
DOC - Permit Finaled | 1/3/2013 | 1/3/2013 | 1/3/2013 | P | PASS |
Tony Young
|
|
|
done
|
BLD-Final | 1/2/2013 | 1/2/2013 | 1/3/2013 | P | DONE |
Tony Young
|
|
|
Rob--Please call for access information Phone #: ###-####
|
FIRE-Final Inspection | 12/28/2012 | 12/28/2012 | 12/28/2012 | A | PASS |
Forrest France
|
|
|
Fire life safety finaled.
|
FIRE-Final Inspection | 9/5/2012 | 9/6/2012 | 9/6/2012 | A | FAIL |
Troy Cobbley
|
|
|
A fire alarm permit is required for the new and relocated devices (smoke and heat detectors, electrical shunt trip) and their interconnection with the existing fire alarm system. It appears that fire alarm work has already been performed since the elevator recall devices have been relocated to the new mechanical closet and new cover plates installed in the previous locations. Activation of the new fire/smoke damper needs to be addressed as well and its interconnection with the fire alarm system. The permit requirement applies to all four buildings and related building permits BLD12-00090, 91, 92 & 93. Also the emergency lighting at the 2460 address did not function when tested in the first floor lobby. Fire extinguishers appear ok.
|
BLD-Final | 9/5/2012 | 9/5/2012 | 9/5/2012 | P | NR |
Tony Young
|
|
|
Rob Phone #: ###-#### - call for access,, need F/L/S 1st,,
|
BLD-Final | 9/4/2012 | 9/5/2012 | 9/5/2012 | A | NH |
Tony Young
|
|
|
Rob Phone #: ###-#### - call for access
|
Inspection Record Card- Bld | | | 8/27/2012 | | DONE |
Tisha Gallop
|
|
|
|
BLD-Wall cover | 6/18/2012 | 6/19/2012 | 6/19/2012 | A | DONE |
Tony Young
|
|
|
Rob Phone #: ###-####
|
BLD-Wall cover | 6/18/2012 | 6/18/2012 | 6/18/2012 | P | NR |
Tony Young
|
|
|
Rob Phone #: ###-#### - call for access
|
BLD-Wall cover | 6/15/2012 | 6/18/2012 | 6/18/2012 | A | NR |
Tony Young
|
|
|
Rob Phone #: ###-#### - call for access,, needs mech
|
BLD-Framing/Rough-in | 6/15/2012 | 6/15/2012 | 6/15/2012 | P | PART |
Tony Young
|
|
|
Rob Phone #: ###-#### - call for access,, needs mech r/in
|
Issue PAID IN FULL permit | | | 3/2/2012 | | DONE |
Tisha Gallop
|
|
|
|
Plan assigned to (PEP) | 2/24/2012 | 2/24/2012 | 2/29/2012 | | PASS |
Perry Paine
|
|
|
|
1st review completed | | | 2/29/2012 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/29/2012 | | DONE |
|
|
|
|
Case Summary (BLD) | | | 2/29/2012 | | |
|
|
|
|
Inspection Record Card- Bld | | | 2/29/2012 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/29/2012 | | DONE |
Tisha Gallop
|
|
|
|
Telephone call | | | 2/29/2012 | | DONE |
Tisha Gallop
|
|
|
called Rob Mairs and told him permit is ready, fees, and need GC form.
|
Routing - PLAN CHECK | 2/21/2012 | | 2/29/2012 | | PASS |
Carl D Madsen
|
|
|
|
Plan assigned to (CDM) | 2/21/2012 | 2/21/2012 | 2/24/2012 | | DEFR |
Carl D Madsen
|
|
|
|
Application received | | 1/13/2012 | 2/21/2012 | | DONE |
Tisha Gallop
|
|
|
|
CHANGE STATUS TO (REV) | | | 2/17/2012 | | DONE |
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 2/17/2012 | | DONE |
Tisha Gallop
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 2/17/2012 | | DONE |
Tisha Gallop
|
|
|
|
VOIDED CHANGE STATUS | | | 1/24/2012 | | DONE |
|
|
|
|