Information based on query as of Tuesday, July 16, 2024.
Permit Information
Permit NumberBLD12-00415
StatusFinaled
Name WOOD RIVER BUILDERS
Site Address 2215 W WINTER CAMP DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Permit for the construction of a new 3,168 sq. ft., two story (first story 2,607 sq. ft., second story 679 sq. ft.) single family dwelling with 4 bedrooms, 3 bathrooms, approximately 604 sq. ft. of covered patio/porch and a 940 sq. ft. attached garage per the approved plans, plan review report, the attached engineering and any notations. This structure is located in WUI zone A and requires a class A fire rated roofing material, one hour fire rated soffits and noncombustible exterior siding products. A-1 zoning and setbacks per planning. CDM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final7/6/20127/9/20127/9/2012PPASS
DetailsTom Arcoraci
Phone #: ###-#### >> Inspection requested via web by Todd Blackwell
DOC - Permit Finaled7/9/20127/9/20127/9/2012PPASS
DetailsTom Arcoraci
BLD-Grading Inspection7/6/20127/6/20127/6/2012PDONE
DetailsTerry Records
BLD-Other5/24/20125/25/20125/25/2012APASS
DetailsTom Arcoraci
fire rated soffit//Bobby Phone #: ###-####
BLD-Energy code compliance5/17/20125/21/20125/21/2012PPASS
DetailsTony Young
bobby Phone #: ###-####
BLD-Framing/Rough-in5/17/20125/18/20125/18/2012APASS
DetailsTony Young
bobby Phone #: ###-####
BLD-Wall Bracing5/10/20125/14/20125/14/2012APASS
DetailsJim Storey
Robert Phone #: ###-#### exterior nailling ok/holddowns ok/ girder nailling ok
BLD-Footing4/5/20124/6/20124/6/2012APART
DetailsTony Young
pat mitchel Phone #: ###-#### >> Inspection requested via web by Todd Blackwell
PubWorks Subgrade Approval4/6/20124/6/20124/6/2012 DONE
DetailsTerry Records
Footing subgrade approved by the geotechnical engineer
Issue & PRINT permit  4/5/2012 DONE
DetailsBarbara Stitt
Plan assigned to (CDM)3/5/20123/5/20124/4/2012 PASS
DetailsCarl D Madsen
Routing - PLAN CHECK  4/4/2012 PASS
DetailsCarl D Madsen
Carl Madsen
PLANS/APPL TAKEN TO FRONT DESK  4/4/2012  
Inspection Record Card- Bld  4/4/2012 DONE
DetailsBarbara Stitt
Permit Ready to Issue  4/4/2012 DONE
DetailsTisha Gallop
Telephone call  4/4/2012 DONE
DetailsTisha Gallop
called Todd and told him permit is ready.
Route to Impact Fee Review4/2/20124/5/20124/3/2012 PASS
DetailsCindy M. Gould
Routing - FIRE 4/2/20124/2/2012 PASS
DetailsScott Arellano
Routing - Erosion and Sediment3/29/2012 4/2/2012 PASS
DetailsClint A Smith
Full size ESC plan map submitted and approved.
Routing - PLANNING  3/29/2012 PASS
DetailsSusan Riggs
Site plan revised to bring house 13 feet forward to comply with fire requirements. New plan complies with all setbacks.
Routing PW Grading-Hillside3/27/2012 3/29/2012 PASS
DetailsTerry Records
Plan resubmittals received  3/27/2012  
Received 3 sets of sheets C1.0, C2.0 and ESC1.0 added to plans and started re-routing
1st review completed  3/20/2012 FAIL
failed pending resubmittals to comply with fire department requirements. 3-20-12 CDM
Case Summary (BLD)  3/20/2012 DONE
Routing - PLAN CHECK  3/20/2012 PASS
DetailsCarl D Madsen
Routing - Erosion and Sediment3/12/2012 3/14/2012 PASS
DetailsClint A Smith
ESC12-00180 plan approved with conditions attached to the permit.
Routing - FIRE3/14/2012 3/14/2012 FAIL
DetailsScott Arellano
Emailed resubmittal items to applicant.

Fire department apparatus must be able to reach within 150 feet of the furthest exterior portion of the building from approved roadways in order to comply with IFC 503.1.1. Resubmit plans indicating the furtherst exterior portion of the residence will be within 150 feet of the near edge of Winter Camp Drive, as measured around the exterior of the structure.
Routing - MECHANICAL3/8/2012 3/12/2012 PASS
DetailsTroy James
Route to Impact Fee Review3/5/20123/8/20123/8/2012 PASS
DetailsCindy M. Gould
Routing PW Grading-Hillside3/8/2012 3/8/2012 PASS
DetailsTerry Records
Routing - PUBLIC WORKS3/6/2012 3/7/2012 PASS
DetailsConnie Baumgartner
Routing - PLANNING3/7/2012 3/7/2012 PASS
DetailsSusan Riggs
Routing - Addressing3/5/2012 3/6/2012 PASS
DetailsTerry Records
Routing PW Grading-Hillside3/6/2012 3/6/2012 FAIL
DetailsTerry Records
Needs geotechnical engineer to recommend revised setback from ascending slope behind house.
Application received 3/5/20123/5/2012 DONE
DetailsTisha Gallop
Plans ACCEPTED BY PLAN TECH  3/5/2012 DONE
DetailsTisha Gallop
Recd Pcfee & Taken To Pln CK  3/5/2012 DONE
DetailsTisha Gallop
Intake Approval  3/5/2012 PASS
DetailsTisha Gallop