Case Summary (BLD) | | | 12/29/2014 | | DONE |
|
|
|
|
Third Notice | | 2/26/2013 | 2/21/2013 | | DONE |
|
|
|
|
Third Notice | | 2/3/2013 | 2/21/2013 | | DONE |
|
|
|
faxed and mailed
|
Third Notice | | 1/8/2013 | 1/29/2013 | | DONE |
|
|
|
faxed to EKC
|
Second Notice | | 12/13/2012 | 1/3/2013 | | DONE |
|
|
|
faxed to EKC
|
First Notice | | 11/30/2012 | 12/3/2012 | | DONE |
Christina Prado
|
|
|
mailed 12-4-12
|
BLD-Final | 11/20/2012 | 11/21/2012 | 11/20/2012 | A | PASS |
Jim Storey
|
|
|
james Phone #: ###-####
|
BLD-Final | 11/20/2012 | 11/20/2012 | 11/20/2012 | P | PASS |
Jim Storey
|
|
|
|
Permanent Occupancy | | | 11/20/2012 | | DONE |
|
|
|
|
BLD-Final | 11/16/2012 | 11/19/2012 | 11/19/2012 | A | PART |
Jim Storey
|
|
|
James Phone #: ###-#### temp ok pending top of wall fire stopping./ si final sign off.
|
FIRE-Final Inspection | 11/16/2012 | 11/16/2012 | 11/16/2012 | P | PASS |
Forrest France
|
|
|
Fire life safety inspection passed.
|
Zoning Approval | 11/16/2012 | 11/16/2012 | 11/16/2012 | | DONE |
Andrea Tuning
|
|
|
|
BLD-Framing/Rough-in | 11/13/2012 | 11/13/2012 | 11/13/2012 | P | PART |
Jim Storey
|
|
|
Fire wall - James Phone #: ###-#### seal head of wall at bar joist and roof purlin.
|
OVERRIDE | | | 10/24/2012 | | |
|
|
|
|
Plan assigned to (CJW) | 10/16/2012 | 10/16/2012 | 10/24/2012 | | PASS |
Carl Westfall
|
|
|
plan mod - Campbell and co (10/16)
|
Routing - PLAN CHECK | 10/22/2012 | | 10/24/2012 | | DONE |
Carl Westfall
|
|
|
|
Print Occupancy Form | | | 10/24/2012 | | DONE |
Tisha Gallop
|
|
|
|
Telephone call | | | 10/24/2012 | | DONE |
Christina Prado
|
|
|
E-mail sent
|
Telephone call | | | 10/24/2012 | | DONE |
Tisha Gallop
|
|
|
e-mailed Adam Garcia that plan mod is ready and fees due.
|
CHANGE STATUS TO (ISS) | | | 10/24/2012 | | DONE |
|
|
|
|
(F) Reprint permit | | | 10/24/2012 | | DONE |
|
|
|
|
Routing PW Sewer Rating | 10/19/2012 | | 10/22/2012 | | PASS |
Connie Baumgartner
|
|
|
Additional fixtures on the 2nd story,
|
Routing - Addressing | 10/22/2012 | | 10/22/2012 | | PASS |
April Wing
|
|
|
|
Routing - PLAN CHECK | 10/16/2012 | | 10/19/2012 | | PASS |
Carl Westfall
|
|
|
|
Plan Modification Accepted | | | 10/16/2012 | | DONE |
Tisha Gallop
|
|
|
Plan modification accepted for Bld12-01027 (Campbell & Company) to provide additional toilet room, enlarging janitors room, adding built-in breakfast bar and filling the "Future Office" space with office rooms. All on the second floor; submitted on revised cert of value and plan sheets T2.0, A2.1, A3.0, M1.0, M2.0, M3.0, M4.0, E0.1, E2.1; routed to Carl Westfall.
|
BLD-Framing/Rough-in | 10/12/2012 | 10/12/2012 | 10/12/2012 | P | PASS |
Jim Storey
|
|
|
James Phone #: ###-#### mez and stairs ok
|
BLD-Framing/Rough-in | 9/13/2012 | 9/14/2012 | 9/14/2012 | A | PASS |
Jim Storey
|
|
|
structural and fire wall//James Phone #: ###-#### fire wall ok// bearing wall for mez ok
|
BLD-Other | 9/12/2012 | 9/13/2012 | 9/13/2012 | P | NR |
Jim Sly
|
|
|
JAMES LATE AS POSSIBLE Phone #: ###-#### Met with James Wall not ready.......Holes and breaches to be addressed. Gutter? and behind purlin.........
|
BLD-Framing/Rough-in | 9/12/2012 | 9/13/2012 | 9/13/2012 | P | PART |
Jim Sly
|
|
|
JAMES Phone #: ###-#### Told James that new steel stud wall ......Located at North wall in South room .....should be OK. as you will still be able to look at it when you go out next. They want to hang steel and joists on it.
|
BLD-Framing/Rough-in | 8/28/2012 | 8/29/2012 | 8/29/2012 | A | PART |
Jim Storey
|
|
|
Sheetrock for fire wall - James Phone #: ###-#### 3hr wall gyp progression ok // need arh to provide top of wall detail / si contract to be provided// wall and floor sys to have wall continued thru.
|
Issue PAID IN FULL permit | | | 8/17/2012 | | DONE |
Barbara Stitt
|
|
|
|
OVERRIDE | | | 8/8/2012 | | |
|
|
|
|
Print Occupancy Form | | | 8/8/2012 | | DONE |
|
|
|
|
Telephone call | | | 8/8/2012 | | DONE |
Christina Prado
|
|
|
Called Adam and gave fees due and advised GC Form & ACHD are required prior to issuance
|
Permit Ready to Issue | | | 8/8/2012 | | DONE |
Christina Prado
|
|
|
|
Plan assigned to (CJW) | 5/7/2012 | 5/7/2012 | 8/7/2012 | | PASS |
Carl Westfall
|
|
|
CAMPBELL & COMPANY (20 days - May 31)
|
Routing - PLAN CHECK | 8/6/2012 | | 8/7/2012 | | DONE |
Carl Westfall
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/7/2012 | | DONE |
|
|
|
|
Routing - Design Review | 8/6/2012 | | 8/6/2012 | | PASS |
Sarah Schafer
|
|
|
Approved. Office space is not to exceed 25% of the tenant floor area unless a conditional use permit is obtained.
|
Routing - PLAN CHECK | 6/4/2012 | | 8/6/2012 | | PASS |
Carl Westfall
|
|
|
(7-24-12) Completed the resubmittal review. Waiting for the Consultant to finish his. More information needed. (7-26-12) Sent the Project Structural Engineer's response to the Consultant Structural Engineer. Had to split it into 3 separate files because it was too big. Sent 3 separate Emails. (8-6-12) Drawings approved after 3rd review by the Consultant Structural Engineer.
|
Routing Off Site - STRUCTURAL | 7/26/2012 | | 8/3/2012 | | PASS |
Carl Westfall
|
|
|
All issues resolved
|
Routing Off Site - STRUCTURAL | 7/20/2012 | | 7/25/2012 | | FAIL |
Carl Westfall
|
|
|
Several items were not addressed.
|
Plan resubmittals received | | | 7/25/2012 | | |
|
|
|
Response from project Structural Engineer
|
Telephone call | | | 7/20/2012 | | DONE |
Tisha Gallop
|
|
|
called action couriers for pick up of resub from 7/18
|
Plan resubmittals received | | | 7/18/2012 | | DONE |
Tisha Gallop
|
|
|
received response letter from architect, response letter from engineer, three copies of plan sheets T1.0, T2.0, T3.0, A1.0, A1.1, A2.0, A2.1, A3.0, M1.0, M2.0, M3.0, M4.0, E0.0, E0.1, E2.1; taken to Carl Westfall.
|
Routing - FIRE | 5/31/2012 | 5/31/2012 | 6/4/2012 | | PASS |
Scott Arellano
|
|
|
Attached IFC comments to plans
|
1st review completed | | | 6/4/2012 | | FAIL |
|
|
|
Failed Design Review, Structural, Plan Checke
|
Route to Impact Fee Review | 5/31/2012 | 6/5/2012 | 6/1/2012 | | PASS |
Cindy M. Gould
|
|
|
|
Routing - PLAN CHECK | 5/11/2012 | | 5/31/2012 | | FAIL |
Carl Westfall
|
|
|
The IBC plan review was started on May 29 and was finished on May 31. Revised drawings were required. See the plan review report.
|
Routing Off Site - STRUCTURAL | 5/9/2012 | | 5/17/2012 | | FAIL |
Carl Westfall
|
|
|
|
Routing - Design Review | 5/10/2012 | | 5/11/2012 | | FAIL |
Sarah Schafer
|
|
|
Sarah Schafer - Exterior wall infill - new 2nd floor office in M-1D
The office space exceeds 25% of the floor plan. Per ordinance it must be seen as accessory. I have notified Adam Garcia and he will let us know how he wants to proceed. He may be submitting a Conditional Use Permit for approval.
|
Routing - Erosion and Sediment | 5/9/2012 | | 5/10/2012 | | PASS |
Clint A Smith
|
|
|
ESC12-00453 plan waiver approved with conditions attached to the permit.
|
Routing - PUBLIC WORKS | 5/7/2012 | | 5/9/2012 | | PASS |
|
|
|
|
Routing PW Sewer Rating | 5/8/2012 | | 5/9/2012 | | PASS |
Connie Baumgartner
|
|
|
|
Plan resubmittals received | | | 5/8/2012 | | DONE |
Christina Prado
|
|
|
Received 4 sets of plans marked E0.1 as well as one complete set of plans (T1.0, T2.0, A1.0, A1.1, A2.0, A2.1, A3.0, M1.0, M2.0, M3.0, M4.0, E0.0, E0.1 & E2.1) and one additional structural calcs. Plans given to Carl Westfall for additional review
|
Routing - Addressing | 5/7/2012 | | 5/8/2012 | | PASS |
Terry Records
|
|
|
|
Pending Assignment by JCB | 5/4/2012 | | 5/7/2012 | | DONE |
Jason Blais
|
|
|
|
Intake Approval | | | 5/4/2012 | | PASS |
Sam Zahorka
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 5/4/2012 | | DONE |
Christina Prado
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 5/4/2012 | | DONE |
Christina Prado
|
|
|
|
Application received | | | 5/1/2012 | | DONE |
|
|
|
Application submitted via PDS Online on May 1 2012 3:12PM
|