Second Notice | | 5/10/2013 | 5/8/2013 | | DONE |
|
|
|
This permit finaled on the web by Brandon Byington
|
First Notice | | 4/1/2013 | 4/30/2013 | | DONE |
|
|
|
Faxed 4/30/13
|
BLD-Final | 3/21/2013 | 3/22/2013 | 3/22/2013 | P | PASS |
Tom Arcoraci
|
|
|
cecil Phone #: ###-####
|
Permanent Occupancy | | | 3/22/2013 | | DONE |
Christina Prado
|
|
|
|
FIRE-Final Inspection | 3/13/2013 | 3/13/2013 | 3/13/2013 | P | PASS |
Troy Cobbley
|
|
|
Life safety passed
|
BLD-Framing/Rough-in | 1/4/2013 | 1/4/2013 | 1/4/2013 | P | PASS |
Tom Arcoraci
|
|
|
|
Issue PAID IN FULL permit | | | 11/27/2012 | | DONE |
Christina Prado
|
|
|
|
Plan assigned to (CJW) | 9/17/2012 | 9/17/2012 | 11/26/2012 | | PASS |
Carl Westfall
|
|
|
ST AL'S ENDOSCOPY SUITE (20 days - Oct 11)
|
Routing - PLUMBING | 11/19/2012 | | 11/26/2012 | | PASS |
Bill VanDegrift
|
|
|
if the addition adversely impacts the preformance requirements of a system or component, additional upgrades shall be required.
|
Routing - PLAN CHECK | 11/26/2012 | | 11/26/2012 | | DONE |
Carl Westfall
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/26/2012 | | DONE |
|
|
|
|
Print Occupancy Form | | | 11/26/2012 | | DONE |
Christina Prado
|
|
|
|
Permit Ready to Issue | | | 11/26/2012 | | DONE |
|
|
|
|
Telephone call | | | 11/26/2012 | | DONE |
|
|
|
LM for Sam permit ready fees given
|
Routing - PLAN CHECK | 10/22/2012 | | 11/19/2012 | | PASS |
Carl Westfall
|
|
|
Drawings approved with "red lines" after the resubmittal review.
|
Plan resubmittals received | | | 11/16/2012 | | |
|
|
|
Received 1 cover transmittal, 2 copies of response comments dated 11-12-12 from Mike MIller to Sam Burrows, taken to Carl Westafall
|
Plan resubmittals received | | | 11/14/2012 | | |
|
|
|
Received 1 resp[onse letter dated 11-13-12 from Sam Burrows to Carl Westfall, 2 copies of door hardware calcs, 2 copies of sheets 0.0, A0.2, A2.0, A3.0, A7.0, M0.0, M1.2, M1.3, M2.1, M2.2, E2.1F, E2.1S, E4.0 and taken to Carl Westfall
|
Route to Impact Fee Review | 10/19/2012 | 10/24/2012 | 11/5/2012 | | PASS |
Cindy M. Gould
|
|
|
Tenant improvement no impact fees
|
Meeting | | | 11/1/2012 | | DONE |
|
|
|
Meeting with Sam to discuss smoke barriers.
|
Routing - FIRE | 10/19/2012 | 10/19/2012 | 10/22/2012 | | PASS |
Scott Arellano
|
|
|
Attached fire code comments to plans.
|
Telephone call | | | 10/22/2012 | | DONE |
|
|
|
Discussed smoke dampers with the Mechanical Engineer.
|
1st review completed | | | 10/22/2012 | | FAIL |
|
|
|
Failed Plan Check and Plumbing.
|
Routing - PLAN CHECK | 9/19/2012 | | 10/19/2012 | | FAIL |
Carl Westfall
|
|
|
The IBC plan review was started on October 10 and finished on October 19. Revised drawings were required. See the plan review report.
|
Routing - PLUMBING | 9/18/2012 | | 9/19/2012 | | FAIL |
Bill VanDegrift
|
|
|
Provide load data for existing and new medical gas piping.
2003 UPC 1312.2.2
|
Routing - PUBLIC WORKS | | | 9/18/2012 | | PASS |
|
|
|
|
Pending Assignment by JCB | 9/14/2012 | | 9/17/2012 | | DONE |
Jason Blais
|
|
|
|
Routing - Addressing | 9/17/2012 | | 9/17/2012 | | PASS |
April Wing
|
|
|
|
Application received | | 9/14/2012 | 9/14/2012 | | DONE |
Christina Prado
|
|
|
|
Plans ACCEPTED BY PLAN TECH | | | 9/14/2012 | | DONE |
Christina Prado
|
|
|
|
Intake Approval | | | 9/14/2012 | | PASS |
Tim L. Woodard
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 9/14/2012 | | DONE |
Christina Prado
|
|
|
|