First Notice | | 2/18/2013 | 2/15/2013 | | DONE |
|
|
|
This permit finaled on the web by Brian Warbis
|
BLD-Final | 2/7/2013 | 2/8/2013 | 2/8/2013 | A | PASS |
Mike Jordan
|
|
|
darin Phone #: ###-####. Ok for perm occ.
|
Permanent Occupancy | | | 2/8/2013 | | DONE |
Christina Prado
|
|
|
|
FIRE-Final Inspection | 2/7/2013 | 2/7/2013 | 2/7/2013 | P | PASS |
Troy Cobbley
|
|
|
Life safety passed
|
FIRE-Conference | 2/5/2013 | 2/6/2013 | 2/6/2013 | A | CANC |
Troy Cobbley
|
|
|
Wrong permit number called in.
|
FIRE-Final Inspection | 2/5/2013 | 2/6/2013 | 2/6/2013 | A | PART |
Troy Cobbley
|
|
|
A temporary occupancy is being given with Scott Arellano's permission until the new fire sprinkler permit has been addressed.
|
BLD-Final | 2/5/2013 | 2/6/2013 | 2/6/2013 | P | PART |
Mike Jordan
|
|
|
Darren Phone #: ###-####. Ok for temp occ. Will be ok for perm occ. once fire/life/safety singns perm.
|
Temporary Occupancy | 2/6/2013 | 5/7/2013 | 2/6/2013 | | DONE |
Christina Prado
|
|
|
|
FIRE-Conference | 2/5/2013 | 2/5/2013 | 2/5/2013 | P | DONE |
Troy Cobbley
|
|
|
Darren and I went over life safety requirements. All life safety items are ok except for what appears to be blocked upright sprinkler heads at new mechanical penatrations. This work was outside of the sprinkler contractors scope of work.
|
BLD-Conference | 2/1/2013 | 2/4/2013 | 2/4/2013 | A | DONE |
Mike Jordan
|
|
|
darren Phone #: ###-####
|
CHANGE STATUS TO (ISS) | | | 1/31/2013 | | DONE |
Tisha Gallop
|
|
|
paid for plan mod
|
BLD-Conference | 1/14/2013 | 1/15/2013 | 1/15/2013 | A | DONE |
Mike Jordan
|
|
|
darren - call 30 mins prior to meet Phone #: ###-####
|
Plan assigned to (TLW) | 1/3/2013 | | 1/15/2013 | | DONE |
Tim L. Woodard
|
|
|
ePlanReview - Plan Modification
|
Routing - FIRE | 1/3/2013 | | 1/14/2013 | | PASS |
Scott Arellano
|
|
|
Attached IFC plan review report to plans.
|
Routing - PLAN CHECK | 1/3/2013 | | 1/10/2013 | | PASS |
Tim L. Woodard
|
|
|
|
Routing - Addressing | 1/4/2013 | | 1/4/2013 | | PASS |
April Wing
|
|
|
|
Routing PW Sewer Rating | 1/3/2013 | | 1/4/2013 | | PASS |
Beverly Mountain
|
|
|
|
Routing PW Environmental | 1/3/2013 | | 1/3/2013 | | PASS |
Walt Baumgartner
|
|
|
oil sediment interceptor must have vented headspace per plumbing code
|
BLD-Framing/Rough-in | 11/30/2012 | 11/30/2012 | 11/30/2012 | P | PASS |
Mike Jordan
|
|
|
Steel stud - Steve Phone #: ###-####. Interior stell stud walls for new washbay and compressor room ok.
|
Permit Ready to Issue | | | 10/30/2012 | | DONE |
Tisha Gallop
|
|
|
|
Print Occupancy Form | | | 10/30/2012 | | DONE |
Christina Prado
|
|
|
|
Issue PAID IN FULL permit | | | 10/30/2012 | | DONE |
Christina Prado
|
|
|
|
Plan assigned to (DRS) | 10/19/2012 | 10/19/2012 | 10/29/2012 | | PASS |
Dan Stuart
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/29/2012 | | PASS |
|
|
|
|
Routing - PLAN CHECK | 10/15/2012 | | 10/29/2012 | | PASS |
Dan Stuart
|
|
|
|
1st review completed | | | 10/29/2012 | | PASS |
Dan Stuart
|
|
|
|
Plan assigned to (TLW) | 10/15/2012 | | 10/19/2012 | | DEFR |
Tim L. Woodard
|
|
|
Review deffered to Dan S.
|
Routing - FIRE | 10/15/2012 | | 10/19/2012 | | PASS |
Scott Arellano
|
|
|
Attached Fire Code comments to plans.
|
Routing PW Sewer Rating | 10/15/2012 | | 10/16/2012 | | PASS |
Connie Baumgartner
|
|
|
|
Routing PW Environmental | 10/15/2012 | | 10/16/2012 | | PASS |
Walt Baumgartner
|
|
|
oil/sed interceptor must comply w/ vented headspace code requirements, plans note one trench drain in car wash area
|
Routing - Addressing | 10/15/2012 | | 10/16/2012 | | PASS |
April Wing
|
|
|
|
Routing - PUBLIC WORKS | 10/15/2012 | | 10/16/2012 | | PASS |
Connie Baumgartner
|
|
|
|
Intake Approval | | | 10/15/2012 | | PASS |
Tim L. Woodard
|
|
|
|
Application received | | | 10/8/2012 | | DONE |
|
|
|
Application submitted via PDS Online on Oct 8 2012 1:14PM
|