Permit Information
Permit NumberBLD12-03203
StatusFinaled
Name JORDAN WILCOMB CONSTRUCTION
Site Address 200 W BROAD ST
Project NameWILCOMB OFFICE BUILDING
Customer Number 
ePlanReviewYes
Description
(CSHQA ARCHITECTS - WILCOMB OFFICE BUILDING) (LEED PLATINUM) The fire sprinkler system is used for building area increase. To convert an existing warehouse building to an office building. The total floor area of this building is about 19,243 square feet. This building occupies the entire site. Work is to include interior nonbearing walls, 4 restrooms accessible to the disabled, 2 shower rooms accessible to the disabled, suspended acoustical ceilings, suspended gypsum board ceilings, millwork, interior finishes, wall furring and insulation at exterior walls, a new thermoplastic single-ply roofing system installed over continuous roof insulation, closed cell polyurethane insulation installed below the roof deck in isolated locations, new exterior windows, new exterior doors, new acrylic skylights, interior doors, and a masonry parapet on top of an existing party wall. Structural work includes steel headers and columns at new exterior wall openings, parapets and parapet bracing, additional roof joists, and concrete retaining walls. The seismic upgrade includes wood structural panels installed on top of the existing roof deck, ties between the roof diaphragm and the exterior walls, and new concrete shear walls. Special Inspection is required for concrete, masonry, welding, and epoxy anchors. The work is required to comply with the approved drawings, with the structural design, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice 2/2/20142/7/2014 DONE
Print Statement  2/7/2014 DONE
DetailsTisha Gallop
mailed to Jordan Wilcomb Const.
Second Notice 1/9/20141/28/2014 DONE
mailed
First Notice 11/23/201312/30/2013 DONE
Faxed 12-30-13
BLD-Final11/12/201311/13/201311/13/2013APASS
DetailsDave Hannah
TJ Phone #: ###-####
Permanent Occupancy  11/13/2013 DONE
DetailsChristina Prado
FIRE-Final Inspection11/5/201311/6/201311/6/2013APASS
DetailsForrest France
Fire life safety finaled.
BLD-Final10/31/201310/31/201311/1/2013PNR
DetailsDave Hannah
TJ Wilcomb Phone #: ###-#### needs fire finals signed off first
Temporary Occupancy10/25/20131/23/201410/25/2013 DONE
DetailsChristina Prado
Zoning Approval10/24/201310/24/201310/24/2013 DONE
DetailsAndrea Tuning
BLD-Conference9/27/201310/1/201310/2/2013APEND
DetailsDave Hannah
10:30am please-John Sanchez Phone #: ###-#### ada sinks in restrooms
Change Expiration Date Only  8/8/2013 DONE
DetailsBarbara Stitt
BLD-Other8/2/20138/5/20138/5/2013PPASS
DetailsDave Hannah
soffit for exterior canopy - john Phone #: ###-####
BLD-Final7/26/20137/29/20137/30/2013PPART
DetailsDave Hannah
john Phone #: ###-#### ok for temp occ needs to get other trades to pemp and fix ada restroom and finish ext and one handrail
FIRE-Final Inspection7/26/20137/29/20137/29/2013APART
DetailsForrest France
Final pending revised plan sheet for changes to the meeting rooms/hallway, missing exit discharge lighting, post signage at the fire riser and alarm panel rooms, project related fire alarm permit final also pending.
Temporary Occupancy7/29/201310/27/20137/29/2013 DONE
DetailsChristina Prado
Zoning Approval Temp7/29/20137/29/20137/29/2013 DONE
DetailsAndrea Tuning
The applicant has posted a bond for the landscape improvements. The parking lot striping and the exterior facade improvements are also incomplete at this time. Derick O-Neil has allowed a 90 day temporary occupancy with the lnadscaping bonding in place.
FIRE-Final Inspection7/25/20137/26/20137/26/2013ANR
DetailsForrest France
john - life safety Phone #: ###-####
BLD-Final7/25/20137/26/20137/26/2013PNR
DetailsDave Hannah
john Phone #: ###-####
BLD-Ceiling Grid Inspection7/23/20137/24/20137/24/2013APART
DetailsDave Hannah
john Phone #: ###-#### ok to cover ceiling on west side
BLD-Other7/12/20137/12/20137/12/2013PPART
DetailsJim Sly
structural celing cover//John Phone #: ###-####
Framing for hard lid ceiling in Ext. patio area.....OK.
BLD-Ceiling Grid Inspection6/19/20136/20/20136/21/2013APART
DetailsDave Hannah
john Phone #: ###-#### ok to cover ceilings with hard lids
BLD-Framing/Rough-in6/3/20136/4/20136/6/2013PPASS
DetailsDave Hannah
john Phone #: ###-#### ok to cover ext walls
BLD-Framing/Rough-in5/29/20135/30/20136/4/2013APART
DetailsDave Hannah
John Phone #: ###-#### ok to cover int walls
FIRE-Supply Line Cover5/23/20135/23/20135/23/2013APART
DetailsForrest France
UG fire supply line okayed for cover
FIRE-Conference5/7/20135/8/20135/13/2013PDONE
DetailsForrest France
On site conference regarding project schedule, fire sprinkler and alarm permit work.
BLD-Conference5/7/20135/8/20135/8/2013PDONE
DetailsJim Sly
Johna Sanchez-at 2:30 please Phone #: ###-####
Met with contractor. OK'd the use of fiberglass insulation for fireblocking if installed properly..
BLD-Framing/Rough-in5/2/20135/3/20135/6/2013APART
DetailsDave Hannah
john Phone #: ###-#### ok to one side elec room
BLD-Framing/Rough-in3/26/20133/27/20133/28/2013APASS
DetailsDave Hannah
Roof inspection please-John Phone #: ###-####
BLD-Framing/Rough-in3/19/20133/19/20133/21/2013PPART
DetailsDave Hannah
John Phone #: ###-#### roof sheeting north half ok to cover after they finish edge nailing
BLD-Footing3/15/20133/18/20133/19/2013PPASS
DetailsDave Hannah
john Phone #: ###-#### ADA ramp
BLD-Concrete3/11/20133/12/20133/12/2013PPASS
DetailsDave Hannah
concrete slab- John Phone #: ###-####
BLD-Foundation3/4/20133/5/20133/5/2013APASS
DetailsDave Hannah
stem wall, pre column insp//john Phone #: ###-####
BLD-Footing2/26/20132/27/20132/27/2013APASS
DetailsDave Hannah
jon Phone #: ###-####
Issue PAID IN FULL permit  2/12/2013 DONE
(F) Reprint permit  2/12/2013 DONE
Print Occupancy Form  2/12/2013 DONE
OVERRIDE  2/8/2013  
Plan assigned to (CJW)12/14/201212/14/20122/8/2013 PASS
DetailsCarl Westfall
CSHQA ARCHITECTS - WILCOMB OFFICE BUILDING (10 days - Dec 27) ePlanReview ***PRIORITY PROCESSING - LEED PLATINUM***
Routing - PLAN CHECK2/7/2013 2/8/2013 PASS
DetailsCarl Westfall
Drawings approved after the 3rd review.
PLANS/APPL TAKEN TO FRONT DESK  2/8/2013 DONE
Permit Ready to Issue  2/8/2013 DONE
DetailsChristina Prado
Spoke with Tj with Jordan WIlcomb Const - Verbally gave new value over the phone so I quoted him total fees due. Will bring in forms 302 & 306 as well as ACHD when ready to pick up
Plan resubmittals received  2/7/2013 DONE
Routing - PLAN CHECK2/5/2013 2/6/2013 DONE
DetailsCarl Westfall
Rrouting completed
Routing PW Solid Waste2/4/2013 2/6/2013 PASS
DetailsPeter J. McCullough
Routing PW Geothermal2/4/2013 2/6/2013 PASS
DetailsJarom Gray
Routing - FIRE2/4/2013 2/5/2013 PASS
DetailsScott Arellano
Attached comments to plans.
Routing - PLAN CHECK1/28/2013 2/5/2013 FAIL
DetailsCarl Westfall
Completed the 2nd plan review. Corrections to the plans required. See the abbreviated 2nd plan review report.
Routing - PLANNING2/4/2013 2/5/2013 PASS
DetailsDavid Moser
The parking layout is OK as per the V2 C3 Grading and Drainage Plan. The angled parking can not block the trash room door.
Routing - PLUMBING2/4/2013 2/4/2013 PASS
DetailsBill VanDegrift
per pans and ISPC
Routing - FIRE2/1/2013 2/1/2013 FAIL
DetailsScott Arellano
Correction needed on plumbing plan P2.2 which shows fire service line running underneath building. See changemark on plan.
Plan resubmittals received  1/28/2013 DONE
Resubmittal review delayed because of other committments and time frames. 8.5 hours overtime was worked that week after the resubmittal came in.
1st review completed  1/7/2013 FAIL
DetailsCarl Westfall
Routing - PLAN CHECK12/14/2012 1/7/2013 FAIL
DetailsCarl Westfall
Routing - FIRE12/18/2012 1/2/2013 PASS
DetailsScott Arellano
Attached IFC comments to plans.
Routing PW Street Lights12/18/2012 12/20/2012 PASS
DetailsMike D Hedge
Street Light inspection required.
Routing PW Solid Waste12/18/2012 12/20/2012 FAIL
DetailsPeter J. McCullough
Routing - PLUMBING12/14/2012 12/18/2012 FAIL
DetailsBill VanDegrift
1. UPC 1101.11.2- provide secondary roof drainage sized per section 1101.11.1
2. UPC 419 future water for urinal must be tied to water closet supply drop
3. UPC 313.6 provide freeze protection information for domestic water at solar system.
Routing PW Sewer Rating12/14/2012 12/17/2012 PASS
DetailsConnie Baumgartner
Routing PW Sewer Design12/14/2012 12/17/2012 DONE
DetailsJon R. Gunnerson
Really for geothermal.
Routing - PLANNING12/14/2012 12/17/2012 FAIL
DetailsDavid Moser
David Moser - CUP12-00045, the end angled parking space shall be removed since it blocks access to the indoor trash room.
Routing - Design Review12/14/2012 12/17/2012 PASS
DetailsAndrea Tuning
Andrea Tuning - DRH12-00316
Routing - Erosion and Sediment12/14/2012 12/17/2012 PASS
DetailsKimberly M. Johnson
Routing - Addressing12/14/2012 12/17/2012 PASS
Details
Routing PW Geothermal12/14/2012 12/17/2012 FAIL
Payment Received  12/14/2012 DONE
Payment received via Govolutions
Intake Approval  12/14/2012 PASS
DetailsTim L. Woodard
Pending Assignment by JCB12/14/2012 12/14/2012 DONE
DetailsJason Blais
Plan Reviewer's activity  12/14/2012 DONE
DetailsJason Blais
Emailed architect to have him contact ACHD for evaluation of any impact fees due. Written verification from ACHD will need to be provided to our Permit Counter prior to the building permit being issued.
Routing - PUBLIC WORKS12/14/2012 12/14/2012 PASS
DetailsBeverly Mountain
Intake Approval  12/12/2012 FAIL
DetailsTim L. Woodard
Hello Ted,

Thank you for using the new E-plan system. I will need a #528 Major TI Checklist filled out and uploaded prior to completing the full prescreen review. However; I did notice that sheet #304 Registered Design Professional Form was not signed by the owner. That sheet will need to be signed by the owner prior to the review taking place. I was able to correct sheet # A2.3 and make that sheet horizontal vs. vertical orientation. Also the survey appears to not have the required stamping area required; since that sheet is for reference we will not require that sheet to be corrected either. At this point we just need the checklist filled out and uploaded to help in determining if the required items are available and sheet # 304 signed by the owner.

Best regards,
Tim Woodard
###-####
twoodard@cityofboise.org
Application received  12/7/2012 DONE
Application submitted via PDS Online on Dec 7 2012 7:54AM