BLD-Final | 12/5/2013 | 12/6/2013 | 12/6/2013 | A | PASS |
Tony Young
|
|
|
Daniel Phone #: ###-####
|
DOC - Permit Finaled | 12/6/2013 | 12/6/2013 | 12/6/2013 | P | PASS |
Tony Young
|
|
|
c of o issued
|
BLD-Energy code compliance | 10/11/2013 | 10/14/2013 | 10/14/2013 | A | PASS |
Tony Young
|
|
|
Dan Phone #: ###-####
|
BLD-Framing/Rough-in | 10/11/2013 | 10/11/2013 | 10/11/2013 | P | PASS |
Tony Young
|
|
|
Dan Phone #: ###-####
|
BLD-Framing/Rough-in | 10/10/2013 | 10/10/2013 | 10/10/2013 | P | NR |
Tony Young
|
|
|
ok to cover insepction please-Dan Phone #: ###-####,, need fire blocks at ceiling lines and chase tops,,, seal interior walls,, caulk sole plates on exterior walls
|
Plan resubmittals received | | | 9/17/2013 | | DONE |
|
|
|
new manual j
|
Routing - MECHANICAL | 9/17/2013 | | 9/17/2013 | | PASS |
Troy James
|
|
|
resubmitted manual j
|
BLD-Framing/Rough-in | 9/12/2013 | 9/12/2013 | 9/12/2013 | P | PASS |
Jim Sly
|
|
|
doug Phone #: ###-####
|
BLD-Conference | 8/26/2013 | 8/27/2013 | 8/27/2013 | A | FAIL |
Tony Young
|
|
|
Dan Phone #: ###-####,, c/n on trusses,, twisted,, bearing size,, split,, etc,, need ok or fix from engioneer
|
BLD-Wall Bracing | 8/14/2013 | 8/14/2013 | 8/14/2013 | P | PASS |
Tom Arcoraci
|
|
|
dan Phone #: ###-####
|
BLD-Conference | 7/24/2013 | 7/24/2013 | 7/24/2013 | P | PASS |
Tony Young
|
|
|
daniel Phone #: ###-####,, frame ?
|
BLD-Conference | 5/30/2013 | 5/30/2013 | 5/30/2013 | P | PASS |
Tony Young
|
|
|
noise complaint at 6:45 am,, no ordinance
|
BLD-Foundation | 5/30/2013 | 5/30/2013 | 5/30/2013 | P | PASS |
Tony Young
|
|
|
Cal; Phone #: ###-####
|
BLD-Footing | 5/28/2013 | 5/28/2013 | 5/28/2013 | P | PART |
Tony Young
|
|
|
Cal Phone #: ###-####,, work in progress
|
BLD-Foundation | 5/16/2013 | 5/17/2013 | 5/17/2013 | A | PART |
Tony Young
|
|
|
CAL Phone #: ###-####,, basement wall
|
BLD-Foundation | 5/16/2013 | 5/16/2013 | 5/16/2013 | P | PART |
Tony Young
|
|
|
CAL Phone #: ###-####,, work in progress on the basement wall
|
BLD-Footing | 5/15/2013 | 5/15/2013 | 5/15/2013 | P | PART |
Tony Young
|
|
|
Phone #: ###-####,, basement footing per plan
|
Issue PAID IN FULL permit | | | 5/2/2013 | | DONE |
Christina Prado
|
|
|
|
OVERRIDE | | | 3/20/2013 | | |
|
|
|
|
Plan assigned to (AJS) | 3/12/2013 | 3/12/2013 | 3/20/2013 | | DONE |
Adele J Schaffeld-Griffin
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/20/2013 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 3/20/2013 | | DONE |
Adele J Schaffeld-Griffin
|
|
|
|
Case Summary (BLD) | | | 3/20/2013 | | DONE |
Adele J Schaffeld-Griffin
|
|
|
|
Inspection Record Card- Bld | | | 3/20/2013 | | DONE |
Barbara Stitt
|
|
|
|
Telephone call | | | 3/20/2013 | | DONE |
Christina Prado
|
|
|
called daniel to advise permit is ready and gave fees due
|
Permit Ready to Issue | | | 3/20/2013 | | DONE |
Christina Prado
|
|
|
|
Routing - MECHANICAL | 3/19/2013 | | 3/19/2013 | | FAIL |
Troy James
|
|
|
emailed corrections to Western Heating
|
Routing - MECHANICAL | 3/19/2013 | | 3/19/2013 | | PASS |
Troy James
|
|
|
|
Routing - PLANNING | 3/15/2013 | | 3/18/2013 | | PASS |
Colleen T Carroll
|
|
|
|
Routing - PLAN CHECK | 3/15/2013 | | 3/15/2013 | | PASS |
Adele J Schaffeld-Griffin
|
|
|
|
Routing - MECHANICAL | 3/14/2013 | | 3/15/2013 | | FAIL |
Troy James
|
|
|
talked to Ival about a couple corrections from previous correction notice.
|
Plan resubmittals received | | | 3/14/2013 | | DONE |
Christina Prado
|
|
|
received two sets of plans marked 1, 2, 3, 4, 5, 6, rescheck, manual j & spray foam evalutions;reoute to Adele for review
|
Routing - MECHANICAL | 3/13/2013 | | 3/13/2013 | | FAIL |
Troy James
|
|
|
emailed corrections to western heating
|
Plan assigned to (CDM) | 3/5/2013 | 3/5/2013 | 3/12/2013 | | DEFR |
Carl D Madsen
|
|
|
Plans assigned to Adele
|
Plan resubmittals received | | | 3/12/2013 | | DONE |
Tisha Gallop
|
|
|
Per Colleen Carroll request; received 8 1/2 x 11 elevation and floor plan of existing detached garage; put with plans at Colleens desk.
|
1st review completed | | | 3/12/2013 | | FAIL |
Adele J Schaffeld-Griffin
|
|
|
email sent 3/12/13
|
Routing - MECHANICAL | 3/7/2013 | | 3/11/2013 | | FAIL |
Troy James
|
|
|
emailed western heating corrections
|
Route to Impact Fee Review | 3/5/2013 | 3/8/2013 | 3/7/2013 | | PASS |
Cindy M. Gould
|
|
|
|
Routing - PLANNING | 3/6/2013 | | 3/7/2013 | | FAIL |
Colleen T Carroll
|
|
|
Existing SFD per Bld08-02582 needs to be converted back to garage.
|
Routing - Addressing | 3/5/2013 | | 3/6/2013 | | PASS |
Jason C. Taylor
|
|
|
|
Routing - PUBLIC WORKS | 3/6/2013 | | 3/6/2013 | | PASS |
Connie Baumgartner
|
|
|
|
Issue PAID IN FULL permit | | | 3/5/2013 | | DONE |
|
|
|
Payment received via Govolutions
|
Plans ACCEPTED BY PLAN TECH | | | 3/5/2013 | | DONE |
Barbara Stitt
|
|
|
|
Intake Approval | | | 3/5/2013 | | PASS |
Barbara Stitt
|
|
|
|
Intake Approval | | | 2/19/2013 | | FAIL |
Tisha Gallop
|
|
|
|
Application received | | | 1/10/2013 | | DONE |
|
|
|
Application submitted via PDS Online on Jan 10 2013 11:46AM
|
Routing - PLAN CHECK | 3/11/2013 | | | | FAIL |
Adele J Schaffeld-Griffin
|
|
|
email sent 11/12/13
I have competed the 1st plan review for the project listed above under the 2009 IRC. Please provide 2 set of revised documents or additional documents.
1. Commercial ranges are not permitted in residential homes. Please clarify that the range installed with be listed for residential use.
2. Please indicate the method of damp proofing that will be installed on the stem walls/ basement walls. R406
3. Landings are required at the top and bottom of all stairs. Please provide a min 3x3 landing at the top of the stairs from the basement. R311.7.5
4. Please indicate the footings and footing size for the front porch load bearing post.
5. Please provide a complete cross section of the building. Please see the submittal check list for specific information needed on the plans.
The footing and floor joist size is shown on the foundation page but the distance from grade to the bottom of joist is not shown, floor sheathing, siding material, under floor insulation, the distance from exterior siding to grade, anchor bolts size and spacing, P.T plate and etc.
The plans reference 2x6 construction but does not indicate spacing, wall interior and exterior finishes, spacing required from concrete for basement wall locations and etc.
6. Please indicate attic access location and size.
7. Please note all safety glazing locations on the plans.
8. The reinforcement called out for the 8 foot basement wall does not meet the minimum requirements from T404.1.1(2). Vertical reinforcement would need to be every 48 inches instead of 72 inches as noted on the plans.
9. Please indicate how the requirements for roof ventilation will be met. R806
10. Please provide 2 copies of the specific ICC-ES Evaluation Service Report for the spay foam insulation that is indicated on the plans. R316.3
11. Please provide a complete stairway detail. Please include handrails, guardrail information. R311.7.7.1 and R312.
If you have any questions please refer to the New Residential Check list or please call and I will be happy to go over these items with you.
Adele J. Schaffeld-Griffin
City of Boise
Plans Examiner II
###-####
|