Permit Information
Permit NumberBLD13-00839
StatusFinaled
Name EVE CHANDLER
Site Address 1289 S PROTEST RD
Project NameBig Jud's Restaurant
Customer Number 
ePlanReviewNo
Description
Big Jud's Restaurant - To construct a new 2,150 sq. ft., one story, wood framed fast food restaurant and related site improvements. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Second Notice 3/10/20143/10/2014 DONE
owner is in legal preceedings with GC who left before the job was completed. Owner is unable to provice accurate final values.
First Notice 2/17/20142/28/2014 DONE
DetailsChristina Prado
Per tenant in office when received perm occ. Diamond B Cont. not on job, best contact for final values is owner, contact is Eve Chandler. Leave Eve as primary so notices to go her.
mailed 2/28
Permanent Occupancy  2/7/2014 DONE
DetailsTisha Gallop
BLD-Aging Inspection1/14/20141/14/20141/14/2014 DEFR
DetailsJim Storey
final ok pending plm sign off.
BLD-Final11/13/201311/13/201311/14/2013PPASS
DetailsJim Storey
Mark Phone #: ###-#### final ok pending plm sign off.
Temporary Occupancy11/14/20132/12/201411/14/2013 DONE
DetailsBarbara Stitt
Zoning Approval11/14/201311/14/201311/14/2013 PASS
DetailsJosh Wilson
BLD-Final11/12/201311/13/201311/13/2013ADEFR
DetailsJim Storey
Mark Phone #: ###-####
FIRE-Final Inspection11/12/201311/13/201311/13/2013APASS
DetailsCraig D. Hanson
no corrections.
BLD-Other11/12/201311/12/201311/12/2013PNR
DetailsJim Storey
Life/Safety final >> Inspection requested via web by Toni Brown
BLD-Other11/11/201311/12/201311/12/2013ADEFR
DetailsJim Storey
Public Works final Phone #: ###-#### >> Inspection requested via web by Toni Brown to permit desk
FIRE-Conference11/7/201311/8/201311/8/2013ADONE
DetailsForrest France
On site conference with contractor regarding conditions for fire life safety and occupancy approval. Discussed fire code review note items, project schedule, hood permit, etc.
BLD-Other11/7/201311/8/201311/8/2013APASS
DetailsJim Storey
This is for an above ceiling inspection. Phone #: ###-#### >> Inspection requested via web by Toni Brown ceilling ok
FIRE-Conference11/7/201311/7/201311/7/2013PDONE
DetailsTroy Cobbley
Follow up with Mark Brown on the hood suppresion system
BLD-Energy code compliance9/19/20139/20/20139/20/2013PPASS
DetailsJim Storey
Phone #: ###-#### >> Inspection requested via web by Toni Brown walls ok ceilling in progress.
BLD-Framing/Rough-in9/17/20139/18/20139/18/2013PPASS
DetailsJim Storey
Phone #: ###-#### >> Inspection requested via web by Toni Brown
BLD-Wall Bracing9/10/20139/11/20139/11/2013PPASS
DetailsJim Storey
Mark Phone #: ###-#### exterior ok to cover and roof
CHANGE STATUS TO (ISS)  9/5/2013 DONE
DetailsTisha Gallop
picked up and paid for approved plan mod
OVERRIDE  9/4/2013  
Plan assigned to (JCM)8/28/20138/28/20139/4/2013 PASS
DetailsJohn Menard
Routing - MECHANICAL9/3/2013 9/4/2013 PASS
DetailsTroy James
Routing - PLAN CHECK9/4/2013 9/4/2013 PASS
DetailsJohn Menard
PLANS/APPL TAKEN TO FRONT DESK  9/4/2013 DONE
DetailsJohn Menard
Print Occupancy Form  9/4/2013 DONE
Telephone call  9/4/2013 DONE
DetailsChristina Prado
called greg to advise permit is ready and gave fees due
Permit Ready to Issue  9/4/2013 DONE
DetailsChristina Prado
Routing - MECHANICAL9/3/2013 9/3/2013 FAIL
DetailsTroy James
called mechanical contractor to provide new comcheck for additional mechanical unit.
Plan Modification Accepted  8/28/2013 DONE
DetailsTisha Gallop
plan modification accepted for complete change of mechanical layout. Changed to (2) 5-ton single phase RTU from (1) 10-ton 3-phase RTU; submitted on plan sheet M-1 and revised cert of value; routed to John Menard.
BLD-Foundation7/11/20137/11/20137/12/2013PNR
DetailsJim Storey
Dane Phone #: ###-#### forms not set rebar just started/ si to insp. if placing late pending report. hot dip anchor bolts spected ?
BLD-Footing7/10/20137/10/20137/10/2013PPASS
DetailsJim Storey
dane Phone #: ###-####
BLD-Footing7/9/20137/9/20137/9/2013PCANC
DetailsJim Storey
Dane Phone #: ###-####
Issue PAID IN FULL permit  6/14/2013 DONE
OVERRIDE  6/5/2013  
Print Occupancy Form  6/5/2013 DONE
Telephone call  6/5/2013 DONE
DetailsChristina Prado
called Eve to advise permit is ready for pick up pending CG & ACHD - also gave fees due
Permit Ready to Issue  6/5/2013 DONE
DetailsChristina Prado
Routing - PUBLIC WORKS6/3/2013 6/4/2013 PASS
DetailsConnie Baumgartner
Routing PW Sewer Design6/3/2013 6/4/2013 PASS
DetailsKyle S. Rosenmeyer
Routing - PLAN CHECK6/4/2013 6/4/2013 PASS
DetailsJohn Menard
PLANS/APPL TAKEN TO FRONT DESK  6/4/2013 DONE
DetailsJohn Menard
Plan assigned to (JCM)4/12/2013 6/4/2013 PASS
DetailsJohn Menard
1st Review completed 5/1/2013
Routing - PLAN CHECK5/30/2013 6/3/2013  
DetailsJohn Menard
Plan resubmittals received  6/3/2013 DONE
DetailsTisha Gallop
received response from Engineer regarding sanitary sewer comments and five copies of plan sheet C1.4; inserted into plans by LEG and routed to Public Works
Routing - PUBLIC WORKS5/28/2013 5/30/2013 FAIL
DetailsBeverly Mountain
Failed Kyle Sewer Engineering.
Routing PW Sewer Design5/29/2013 5/30/2013 FAIL
DetailsKyle S. Rosenmeyer
Sewer note required for tap permit, Angle of tap in R/W required to be 90 degrees.
Routing PW Drainage  5/30/2013 PASS
DetailsBrian Murphy
Plan resubmittals received  5/29/2013 DONE
DetailsChristina Prado
Received three sets response letter addressed to John Menard, three sets revised structural calcs, five sets of grading & drainage sheets marked C1.2, C1.3, C1.4 & C2 as well as three sets reviswed plan sheets marked T1.0, C1.2, C1.3, C1.4, C2, A0.0, A1.0, A7.0, S0.1, S1.1, S2.1, S5.1, S7.1, m-1, m-2, m-3, P0.1, P1.1, E1.0, E2.0, E3.0 & E4.0. PLans instered by arch rep and taken back to John for review
Routing - PLAN CHECK5/16/2013 5/28/2013  
DetailsJohn Menard
Plan resubmittals received  5/23/2013 DONE
DetailsTisha Gallop
received engineering response, two copies of Storm Water System report, Calcs and Soild Report, and five copies of plan sheets C1, C1.1, C1.2, C1.3, C1.4, C2; inserted by permit tech and taken back to John Menard.
Routing PW Drainage5/7/2013 5/16/2013 FAIL
DetailsBrian Murphy
needs s engineer letter
Routing - PUBLIC WORKS5/6/2013 5/16/2013 FAIL
DetailsConnie Baumgartner
Failed by Brian Murphy for drainage issues and Kyle Rosenmeyer for sewer design.
Routing PW Sewer Design5/6/2013 5/7/2013 FAIL
DetailsKyle S. Rosenmeyer
Show point of connection to public sewer. Spoke with BA Engineers 5/7.
Routing - FIRE5/1/20135/1/20135/6/2013 PASS
DetailsScott Arellano
With conditions
Routing - PLAN CHECK5/2/2013 5/6/2013  
DetailsJohn Menard
Telephone call  5/6/2013 DONE
DetailsJason Blais
Telephone call with owner Eve Chandler on correction items outstanding and the need for the registered architect to be in responsible charge of the project as required by code.
Route to Impact Fee Review5/1/20135/6/20135/3/2013 PASS
DetailsCindy M. Gould
1st review completed  5/2/2013 FAIL
Failed - Plan Check
Plan resubmittals requested  5/1/2013 DONE
DetailsJohn Menard
E-mailed the architect a copy of the plan review requesting revisions. JCM
Plan resubmittals received  5/1/2013 DONE
DetailsChristina Prado
Received one set of plans marked C1, C1.1, C1.2, C1.3 & C2 as well as one set storm water report and O& M; plans inserted into plan sheets and taken back to fire review
Routing - PLAN CHECK4/30/2013 5/1/2013 FAIL
DetailsJohn Menard
John Menard
Routing - PLANNING4/26/2013 4/30/2013 PASS
DetailsJosh Wilson
DRH13-00004 Josh W.
Routing - PLUMBING4/25/2013 4/26/2013 PASS
DetailsDaryl Spivey
Venting does not meet cross sectional area venting requirements. Increase to meet requirements.
Mop sink to drain to grease waste line.
Routing - Erosion and Sediment4/24/2013 4/25/2013 PASS
DetailsKimberly M. Johnson
approved with redlines
Routing PW Sewer Rating4/24/2013 4/24/2013 PASS
DetailsConnie Baumgartner
Routing PW Environmental4/24/2013 4/24/2013 PASS
DetailsWalt Baumgartner
Route mop sink to grease line.
Routing - PUBLIC WORKS4/15/2013 4/24/2013 FAIL
DetailsConnie Baumgartner
Failed by Brian Murphy and Kyle Rosenmeyer
Routing PW Solid Waste4/24/2013 4/24/2013 PASS
DetailsPeter J. McCullough
Plan resubmittals requested  4/24/2013 DONE
DetailsJohn Menard
E-mailed the applicant a copy of the structural comments requesting revisions. JCM
Routing PW Sewer Design4/17/2013 4/23/2013 FAIL
DetailsKyle S. Rosenmeyer
Sewer Services - Show point of connection to public sewer.
Routing Off Site - STRUCTURAL4/12/2013 4/22/2013 FAIL
DetailsJohn Menard
Received comment list from consulting structural engineer requesting revsions. JCM
Routing PW Drainage4/16/2013 4/17/2013 FAIL
DetailsBrian Murphy
need calc and st eng letter
Routing - Addressing  4/16/2013 PASS
DetailsJason C. Taylor
Routing - PLANNING Land Div4/12/2013 4/15/2013 PASS
DetailsTodd Tucker
Application received 4/10/20134/12/2013 DONE
DetailsTisha Gallop
Pending Assignment by JCM4/12/2013 4/12/2013 DONE
DetailsJohn Menard
Plans ACCEPTED BY PLAN TECH  4/12/2013 DONE
DetailsTisha Gallop
Recd Pcfee & Taken To Pln CK  4/12/2013 DONE
DetailsTisha Gallop
Telephone call  4/12/2013 DONE
DetailsTisha Gallop
Called Action Couriers for pick up