First Notice | | 6/15/2014 | 6/10/2014 | | DONE |
|
|
|
This permit finaled on the web by Mike McHargue
|
BLD-Final | 6/5/2014 | 6/6/2014 | 6/5/2014 | A | PASS |
Mike Jordan
|
|
|
|
Zoning Approval | 6/5/2014 | 6/5/2014 | 6/5/2014 | | PASS |
Josh Wilson
|
|
|
|
Permanent Occupancy | | | 6/5/2014 | | DONE |
Christina Prado
|
|
|
|
BLD-Final | 4/7/2014 | 4/8/2014 | 4/8/2014 | A | PASS |
Mike Jordan
|
|
|
ok for temp. occ. Willbe ok for perm occ. once zoning and public works signs perm.
|
Temporary Occupancy | 4/8/2014 | 7/7/2014 | 4/8/2014 | | DONE |
Christina Prado
|
|
|
|
BLD-Final | 4/4/2014 | 4/7/2014 | 4/7/2014 | P | PART |
Mike Jordan
|
|
|
Phone #: ###-#### >> Inspection requested via web by Mike McHargue. Scheduled inspection in the am to complete remainder.
|
FIRE-Final Inspection | 4/4/2014 | 4/7/2014 | 4/7/2014 | A | PASS |
Forrest France
|
|
|
Fire life safety inspection passed. Noted three dry sidewall fire sprinkler heads which need travel caps removed. Door closure at unit 305 adjusted while on site.
|
Zoning Approval Temp | 3/21/2014 | 3/21/2014 | 3/21/2014 | | PASS |
Josh Wilson
|
|
|
180 day for landscaping. Bond in place.
|
Case Summary (BLD) | | | 1/24/2014 | | DONE |
|
|
|
|
BLD-Wall cover | 1/6/2014 | 1/6/2014 | 1/6/2014 | A | PASS |
Mike Jordan
|
|
|
Phone #: ###-#### >> Inspection requested via web by Mike McHargue. Remaining units completed. ok to tape.
|
BLD-Wall cover | 12/31/2013 | 12/31/2013 | 12/31/2013 | P | PASS |
Mike Jordan
|
|
|
2nd floor, south units and central units ok to tape.
|
BLD-Wall cover | 12/31/2013 | 12/31/2013 | 12/31/2013 | A | NR |
Mike Jordan
|
|
|
Moved to pm inspection.
|
BLD-Wall cover | 12/30/2013 | 12/30/2013 | 12/31/2013 | P | DEFR |
Jim Storey
|
|
|
Wall/Ceiling screw inspection mid/late afternoon. Phone #: ###-#### >> Inspection requested via web by Mike McHargue
|
BLD-Wall cover | 12/27/2013 | 12/30/2013 | 12/30/2013 | A | PART |
Jim Sly
|
|
|
More units ready for 2nd layer on ceiling Some ready for taping
>> Inspection requested via web by Mike McHargue Select units.....OK 1st layer......OK 2nd layer.
|
BLD-Wall cover | 12/20/2013 | 12/23/2013 | 12/23/2013 | A | PART |
Mike Jordan
|
|
|
Wall cover lets try it again. They are suppose to work all weekend >> Inspection requested via web by Mike McHargue. base layers on 1hr. floor ceiling assemblies ok.
|
BLD-Wall cover | 12/19/2013 | 12/20/2013 | 12/20/2013 | P | PART |
Mike Jordan
|
|
|
Phone #: ###-#### >> Inspection requested via web by Mike McHargue3rd floor, north units, south vside only.
|
BLD-Energy code compliance | 12/9/2013 | 12/9/2013 | 12/9/2013 | P | PASS |
Mike Jordan
|
|
|
wall & floor insulation BLDG 13 Phone #: ###-#### >> Inspection requested via web by Mike McHargue
|
BLD-Energy code compliance | 12/3/2013 | 12/4/2013 | 12/4/2013 | A | PART |
Mike Jordan
|
|
|
Phone #: ###-#### >> Inspection requested via web by Mike McHargue. Airseal package only.
|
BLD-Framing/Rough-in | 12/3/2013 | 12/4/2013 | 12/4/2013 | A | PART |
Mike Jordan
|
|
|
Phone #: ###-#### >> Inspection requested via web by Mike McHargue. ok to insulate. Needs to complete fireblocking at furdowns and behind tubs. Also needs to provide straps on top plates at various locations.
|
BLD-Energy code compliance | 11/27/2013 | 12/2/2013 | 12/2/2013 | A | NR |
Mike Jordan
|
|
|
air sill Phone #: ###-#### >> Inspection requested via web by Mike McHargue
|
BLD-Framing/Rough-in | 11/27/2013 | 12/2/2013 | 12/2/2013 | A | NR |
Mike Jordan
|
|
|
Phone #: ###-#### >> Inspection requested via web by Mike McHargue
|
BLD-Framing/Rough-in | 11/27/2013 | 11/29/2013 | 11/27/2013 | A | CANC |
Mike Jordan
|
|
|
Phone #: ###-#### >> Inspection requested via web by Mike McHargue Inspection cancelled from web by: Mike McHargue
|
BLD-Wall Bracing | 10/22/2013 | 10/22/2013 | 10/22/2013 | P | PASS |
Mike Jordan
|
|
|
Phone #: ###-#### >> Inspection requested via web by Mike McHargue
|
BLD-Wall Bracing | 10/15/2013 | 10/17/2013 | 10/17/2013 | A | FAIL |
Mike Jordan
|
|
|
Phone #: ###-#### >> Inspection requested via web by Mike McHargue. Nail off belly band at 2nd. 3rd. floor at breezeway.
|
BLD-Wall Bracing | 10/9/2013 | 10/9/2013 | 10/9/2013 | P | FAIL |
Mike Jordan
|
|
|
Phone #: ###-#### >> Inspection requested via web by Mike McHargue. install all holdowns, install all missing floor to floor straps and pick up nailing at missing locations, 1st, 2nd, and 3rd. floors.
|
BLD-Concrete | 8/1/2013 | 8/1/2013 | 8/1/2013 | P | CANC |
Mike Jordan
|
|
|
|
BLD-Concrete | 8/1/2013 | 8/1/2013 | 8/1/2013 | P | PASS |
Mike Jordan
|
|
|
interior footing on south slab of building 13 Phone #: ###-#### >> Inspection requested via web by Mike McHargue
|
BLD-Concrete | 7/31/2013 | 8/1/2013 | 8/1/2013 | A | CANC |
Mike Jordan
|
|
|
north end building 13 interior footings Phone #: ###-#### >> Inspection requested via web by Mike McHargue. Moved to pm.
|
BLD-Energy code compliance | 7/22/2013 | 7/22/2013 | 7/22/2013 | P | PASS |
Mike Jordan
|
|
|
Early afternoon inspection for foundation insulation on building 13. Phone #: ###-#### >> Inspection requested via web by Mike McHargue
|
BLD-Foundation | 7/19/2013 | 7/19/2013 | 7/19/2013 | P | PASS |
Tom Arcoraci
|
|
|
Stemwall/rebar inspection Phone #: ###-#### >> Inspection requested via web by Mike McHargue
|
BLD-Footing | 7/17/2013 | 7/17/2013 | 7/17/2013 | P | PASS |
Tom Arcoraci
|
|
|
john Phone #: ###-####
|
BLD-Footing | 7/16/2013 | 7/16/2013 | 7/16/2013 | P | CANC |
Jim Sly
|
|
|
Bld 13 footing/rebar inspection Phone #: ###-#### >> Inspection requested via web by Mike McHargue Inspection cancelled from web by: Mike McHargue
|
OVERRIDE | | | 7/9/2013 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 7/9/2013 | | DONE |
Christina Prado
|
|
|
|
Print Occupancy Form | | | 7/9/2013 | | DONE |
Christina Prado
|
|
|
|
Permit Ready to Issue | | | 7/9/2013 | | DONE |
Christina Prado
|
|
|
|
Routing PW Sewer Design | 7/3/2013 | | 7/3/2013 | | PASS |
Kyle S. Rosenmeyer
|
|
|
|
Routing - FIRE | 6/28/2013 | 6/28/2013 | 6/28/2013 | | PASS |
Tim Frost
|
|
|
|
Plan assigned to (SRZ) | 5/24/2013 | 5/24/2013 | 6/28/2013 | | PASS |
Sam Zahorka
|
|
|
1st review completed. ePlanReview - Union Square Bldg #13
|
Routing - PLAN CHECK | 6/28/2013 | | 6/28/2013 | | PASS |
Sam Zahorka
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/28/2013 | | DONE |
Sam Zahorka
|
|
|
|
Routing - PUBLIC WORKS | 6/28/2013 | | 6/28/2013 | | PASS |
Beverly Mountain
|
|
|
|
Routing PW Solid Waste | 5/28/2013 | | 6/28/2013 | | PASS |
Peter J. McCullough
|
|
|
Signed off PASS in ePlan Review.
|
Routing - PLAN CHECK | 6/24/2013 | | 6/28/2013 | | PASS |
Sam Zahorka
|
|
|
|
Routing PW Street Lights | 6/27/2013 | | 6/27/2013 | | PASS |
Mike D Hedge
|
|
|
|
Routing - FIRE | 6/24/2013 | 6/24/2013 | 6/24/2013 | | FAIL |
Tim Frost
|
|
|
|
Routing - PLUMBING | 6/24/2013 | | 6/24/2013 | | PASS |
Bill VanDegrift
|
|
|
see bld13-01288 for review comments
|
Routing - PLAN CHECK | 6/21/2013 | | 6/21/2013 | | PEND |
Sam Zahorka
|
|
|
Pending Plumbing, Fire, Public Works, Street lights, and Sewer Design to PASS prior to issuance.
|
Routing Off Site - STRUCTURAL | 6/21/2013 | | 6/21/2013 | | PASS |
Sam Zahorka
|
|
|
|
Routing PW Street Lights | 5/28/2013 | | 6/17/2013 | | FAIL |
Mike D Hedge
|
|
|
Signed off FAIL in ePlanReview
|
Routing PW Sewer Design | 5/28/2013 | | 6/17/2013 | | FAIL |
Kyle S. Rosenmeyer
|
|
|
Signed off FAIL in ePlanReview
|
1st review completed | | | 6/17/2013 | | DONE |
Sam Zahorka
|
|
|
|
Routing - PLAN CHECK | 5/24/2013 | | 6/17/2013 | | FAIL |
Sam Zahorka
|
|
|
|
Routing - PLANNING Land Div | 5/24/2013 | | 6/17/2013 | | PASS |
Dave Abo
|
|
|
Signed off PASS in ePlanReview
|
Routing - Erosion and Sediment | 5/24/2013 | | 6/17/2013 | | FAIL |
Kimberly M. Johnson
|
|
|
Signed off FAIL in ePlanReview
|
Routing PW Drainage | 5/28/2013 | | 6/12/2013 | | PASS |
Brian Murphy
|
|
|
|
Routing - PLANNING | 5/24/2013 | | 6/6/2013 | | PASS |
Susan Riggs
|
|
|
Susan Riggs - CUP12-00064
|
Route to Impact Fee Review | 5/24/2013 | 5/30/2013 | 6/5/2013 | | PASS |
Cindy M. Gould
|
|
|
|
Routing Off Site - STRUCTURAL | 5/24/2013 | | 6/3/2013 | | FAIL |
Ron Hill
|
|
|
Sent comments to Architect Billy Edwards 6/03/13
|
Routing - Erosion and Sediment | 6/3/2013 | | 6/3/2013 | | PASS |
Kimberly M. Johnson
|
|
|
|
Routing - PLUMBING | 5/24/2013 | | 5/31/2013 | | FAIL |
Bill VanDegrift
|
|
|
SEE BLD13-01288 FOR REVIEW COMMENTS
|
Routing - MECHANICAL | 5/24/2013 | | 5/30/2013 | | PASS |
Troy James
|
|
|
|
Routing - FIRE | 5/24/2013 | | 5/29/2013 | | FAIL |
Scott Arellano
|
|
|
Attached plan revie report to case and emailed report to architect.
|
Routing - Addressing | 5/24/2013 | | 5/28/2013 | | PASS |
Jason C. Taylor
|
|
|
New addresses have been added to the buildings with correct apartment numbers. Please see uploaded sheets in Project Dox. Jason Taylor ###-####.
|
Routing - PUBLIC WORKS | 5/24/2013 | | 5/28/2013 | | FAIL |
Beverly Mountain
|
|
|
Signed off FAIL (PW Sewer Design, Street Lights) in ePlanReview
|
Routing PW Sewer Rating | 5/28/2013 | | 5/28/2013 | | PASS |
Beverly Mountain
|
|
|
|
Routing - Design Review | 5/24/2013 | | 5/28/2013 | | PASS |
Josh Wilson
|
|
|
Josh Wilson - DRH13-00005
|
Pending Assignment by JCB | 5/24/2013 | | 5/24/2013 | | DONE |
Jason Blais
|
|
|
|
Intake Approval | | | 5/23/2013 | | PASS |
Sam Zahorka
|
|
|
|
Application received | | | 5/21/2013 | | DONE |
|
|
|
Application submitted via PDS Online on May 21 2013 4:17PM
|